PRIMARY APPLIANCE CONTROL

 – is done utilizing the FMT 914 PCB as custom manufactured by SIT Controls of the 

Netherlands for Hamilton Engineering, Inc.

POWER SUPPLY

In all scenarios shown below, 208 – 240 volt single phase power is connected to leads labeled Power L, Power L and 

Ground. Appliance primary pump is wired to leads labeled Pump L, Pump L and Ground, pumps must be rated for 208v - 

240v power supply. 

Maximum total allowable externally connected load to the FMT 914 is 550 watts.

SENSORS

Through the following pages you will see sensors (all 10k ohm) in the drawings listed as:

  

 

S-1 Flow

 – this is the leaving water from the heater/boiler.

 

S-2 Return

 – this is the entering water to the heater/boiler.

 

S-3 External

 – this is the storage tank sensor on water heaters and the common loop/low loss header sensor on boilers.

 

S-5 Tank

 – this is the Domestic Hot Water sensor on a heating boiler application only.

 

S-6 Outdoor

 – the is the sensor to be mounted outdoors for temperature reset control on a heating boiler application only.

PUMP CONTROL

 

• All water heaters and boilers are designed to operate with their own 240v pump that will be controlled and the 

 

 power to it supplied by the internal wiring. 

 

• If a second 240v pump or diverting valve is utilized

the control is by the FMT 914, but the power 

 

 to the pump or diverting valve must be supplied and switched through a field supplied relay if the total wattage 

 

 draw exceeds 550 for all pumps 

(an additional wiring harness (P/N WRE 74090) is required on all pre-universal 

 

 heating models; please refer to our technical bulletin TB025, “EVO Universal Model: Starting Serial Numbers”, 

 

 to determine whether your unit is universal or not).

 

• Standard post burn cycle running of the pumps is as follows:

 

 

Water Heater – 1 minute 

Pump P3

 

 

Heating Boiler – 5 minutes 

Pump P1

 

 

Domestic Hot Water heating zone pump – 1 minute – 

Pump P2/Diverting Valve

 

 

Zone/Transport Pump – 5 minutes 

Pump P3

DISPLAY

The 3 digit display will show different information during normal operation based on the configuration of the appliance:

 • 

Stand alone Water Heater

 – the temperature setpoint, or code, or flashing fault code

 • 

Cascade Water Heater 

– the Lead heater will always display the temperature setpoint, or code, or flashing a  

 

 fault code; the 

Lag

 heater(s) will either display “0.” If they are not burning or the same temperature as the Lead 

 

 when they are burning, or their own code, or a flashing fault code if applicable. If the blinking ”.” is not visible on 

 

 the 

Lag

 heaters within 30 seconds of powering up, the Cascade system is not properly connected. This “.” 

 

 should be visible whenever power is on to the 

Lag

 heater.

 • 

Stand alone Heating Boiler

 – the temperature setpoint if the boiler has not reached it or A3 if there is still a heat 

 

 demand but the boiler has reached setpoint or code a or flashing fault code 

 

• Cascade Heating Boiler

 – the 

Lead

 heater will always display the temperature setpoint or a code or flashing 

 

 fault code the 

Lag

 heater(s) will either display “0.” If they are not burning or the same temperature as the Lead 

 

 when they are burning, or their own code or flashing fault code if applicable. If the blinking ”.” is not visible on the 

  

Lag

 boilers within 30 seconds of powering up, the Cascade system is not properly connected. This “.” should be 

 

 visible whenever power is on to the 

Lag

 boiler.

 

• See Operating Manuals for Fault Codes and their explanations.

PARAMETER CHANGES

Only parameters that need to be changed for that particular configuration will be noted on the various configurations, all 

others are standard in the base programs.

LEGIONELLA CONTROL

In all of the configurations shown in the following pages, the FMT 914 has the ability to implement a program to heat the 

DHW as required for Legionella control. 

Parameters involved are: 2 IC for on/off, 2 DC for number of days between use 

and 2 DD for water temperature during use.

GENERAL DESCRIPTION 

Содержание EVO 129-599

Страница 1: ...causing property damage personal injury or death WARNING New York Massachusetts SCAQMD CEC Listed MEA 425 05 E Boilers G1 06 06 24A Compliant Rule1146 2 California Energy Commission Heaters G1 06 06 2...

Страница 2: ...Central Heating Only Single Boiler 8 CONFIGURATION 4 Central Heating Only Multiple Boiler Cascade 9 CONFIGURATION 5 Residential Heating w Pumped DHW Single Combi Boiler 10 CONFIGURATION 6 Central Hea...

Страница 3: ...ng Boiler 5 minutes Pump P1 Domestic Hot Water heating zone pump 1 minute Pump P2 Diverting Valve Zone Transport Pump 5 minutes Pump P3 DISPLAY The 3 digit display will show different information duri...

Страница 4: ...EV 06 2018 GENERAL DESCRIPTION That are represented by The following pages contain drawings that apply to all models of EVO products In addition most drawings reference a Low Loss Header which may als...

Страница 5: ...wing can be done 1 Adjust the heater minimum and maximum temperature setting via the red wheel located on the display panel within the range of 50 159 F Parameter 2 EA 2 EB 2 An external on off tank t...

Страница 6: ...range of 50 159 F Parameter 2 EA 2 EB It is important to set the red potentiometer wheel to the desired setpoint on the Lag heaters with the power off to the Lead heater This way in the event of a con...

Страница 7: ...ermistor is connected to terminals 1 2 or 9 10 26 27 depending on model The control will automatically sense the presence of the sensor When an outside temperature sensor is connected the flow tempera...

Страница 8: ...195 F Parameter 2 EB 2 EA 2 Outdoor temperature reset can be enabled by connecting a 10k ohm sensor to terminals 1 2 or 9 10 26 27 depending on model this will be automatically sensed by the FMT 914...

Страница 9: ...be controlled based on the Room Thermostat must add heating harness WRE74090 and wire to P3 leads Caution maximum available wattage for external load on the FMT 914 control board is 550 watts If pumps...

Страница 10: ...ry heating loop In this configuration the following can be done 1 Adjust the boiler minimum and maximum temperature setting via the potentiometer located on the display panel within the range of 50 19...

Страница 11: ...nfiguration the following can be done 1 Adjust the boiler minimum and maximum temperature setting via the potentiometer located on the display panel within the range of 50 192 F Parameter 2 EB 2 EA 2...

Страница 12: ...entiometer located on the display panel within the range of 50 192 F Parameter 2 EB 2 EA 2 Set boiler water temperature to the DHW tank Factory default is 185 Parameter 2 CE 3 Set the DHW water temper...

Страница 13: ...ting valve is to be connected to the harness leads labeled 3 way Open 3 way Close and 3 way L In this configuration the following can be done 1 Adjust the boiler minimum and maximum temperature settin...

Страница 14: ...maximum temperature setting via the potentiometer located on the display panel within the range of 95 195 F Parameter 2 EB 2 EA 2 Set the flow temperature to the DHW tank Factory default is 185 F Par...

Страница 15: ...15 34000 Autry Street Livonia MI 48150 800 968 5530 Fax 734 419 0209 www hamiltonengineering com LIT91110 REV 06 2018 HWD 129 199 8 STANDARD WIRING...

Страница 16: ...1 1 2 K6 K2 K2 K10 K6 On Off Switch 4 3 2 1 K6 K10 K2 Printed Circuit Board FMT914 K6 K2 K10 K1 K0 K10 K6 K2 K2 K2 K2 K2 K5 K5 K3 K3 K6 K10 K2 K7 K8 K6 K10 K6 K2 K10 K6 K2 K6 K2 K6 K6 3 15 Amp Pressu...

Страница 17: ...17 34000 Autry Street Livonia MI 48150 800 968 5530 Fax 734 419 0209 www hamiltonengineering com LIT91110 REV 06 2018 HWH 129 199 8 W 3 WAY...

Страница 18: ...ow white blue white red white black white K10 K12 K17 K18 K19 K5 K6 K7 K8 K9 orange blue red black purple white yellow brown green gray K0 K1 K2 K3 K4 K6 K6 K2 K6 K2 K6 K10 K2 K6 K10 K6 K8 K7 K2 K10 K...

Страница 19: ...X 4 X 2 X 1 Gas valve 1 Power Supply Cascade Connection 15 3 16 17 20 19 18 4 2 1 4 3 2 1 X 3 K2 K6 K10 K10 K6 K2 6 5 Thermostat Central Heat Room K1 K1 K4 K4 0 10 VDC 7 8 10 9 Sensor Outside K8 K8 1...

Страница 20: ...Fuse X 10 X 9 X 8 X5 X 4 X 2 X 1 Gas valve 1 Power Supply Cascade Connection 15 3 16 17 20 19 18 4 2 1 4 3 2 1 X 3 K2 K6 K10 K10 K6 K2 6 5 Thermostat Central Heat Room K1 K1 K4 K4 0 10 VDC 7 8 10 9 S...

Страница 21: ...ndirect OPEN THERM PCB BURNER L1 24 ST 3 8 7 Thermostat Remote Additional Heat Source Dry Contact Dry Contact Signal Lock Out External L2 K2 Pressure switch Open switch indicates as H 1 High limit the...

Отзывы: