34000 Autry Street, Livonia, MI 48150  |  800.968.5530  |  Fax 734.419.0209  |  www.hamiltonengineering.com  |  LIT91110 REV 06/2018

CONFIGURATION #7

Configuration #7 – CASCADE BOILERS WITH DOMESTIC HOT WATER PUMP   

(Requires additional wiring harness – p/n WRE 74090 on the Lead boiler only)

 

• A room thermostat is to be connected to terminals 5 & 6 (or 13 & 14, 57 & 58 depending on model) of the 

LEAD 

 

  BOILER ONLY

. If no yellow jumper wire is attached to 5 & 6 (or 13 & 14, 57 & 58 depending on model), which 

 

  will be removed to connect room thermostat, additional wiring is required. Consult local supplier.

  

 

• In this configuration an external sensor or aquastat MUST be connected to terminals 1 & 2 (or 3 & 4, 28 & 29  

 

  depending on model) on the 

LEAD BOILER ONLY

 to sense common loop temperature (after/at low loss header).

 

• The tank sensor or aquastat is to be connected to leads labeled “Tank Sensor” on the Lead boiler.

 

• The DHW pump is to be connected to the harness leads labeled “L and Close” in the Lead boiler, be sure and 

 

  cap the wire labeled “Open”.

 

• A flow check must be installed on the domestic hot water loop and the heating loop.

 

In this configuration the following can be done:  

 

   1. Adjust the boiler minimum and maximum temperature setting via the potentiometer located on the display 

 

       panel, within the range of 50 - 192°F. 

(Parameter 2 EB, 2 EA )

 

   2. Set boiler water temperature to the DHW tank. (

Factory default is 185°)      (Parameter 2 CE)

 

   3. Set the DHW water temperature   

 (Factory default is 140°F (must be less than 2CC)).      (Parameter 2 LF)

 

   4. Pump P3 can be controlled based on the Room Thermostat, wire to P3 leads. 

Caution: Maximum available 

 

       wattage for external load on the FMT 914 control board is 550 watts. If pumps P1 & P3 total less, they 

 

       both can be powered directly off the board, if not a relay (240v coil) must be used for pump P3.

 

It is important to set the red potentiometer wheel to the desired setpoint on the Lag boilers with the power off to  

 

the Lead boiler. This way, in the event of a control or power failure to the Lead boiler, the Lag boilers will operate 

 

at the desired temperature.

BPD

8/11/09

1/2"=1'

Dwg. By:

34000 Autry
Livonia, MI 48150

PH: (800) 968-5530
Fax: (734) 419-0209

Description:

Date:

Scale:

Customer:

HAMILTON

ENGINEERING

Dwg. 
No.:

Checked. 
By:

Cascade Boiler

With External Sensor

Pumped Domestic Hot Water

Utilizing Full Cascade Output

Stainless

Indirect

Heater

Pump 1

Pump 1

Pump 1

Zone
Load

Pump 3

Low Loss Header

S3
(Cascade)

Outside Wall

S6

Outside Sensor

(Optional)

Lead

Lag 1

Lag 2

Room
Thermostat

Pump 2

0-10 VDC

(Optional)

Required parameter changes

from base program

Default

Change to

Base Program - HXXXKPCO.pia

All Boilers

1

0

All Lag Boilers - 2IA

0

1 - 7

Содержание EVO 129-599

Страница 1: ...causing property damage personal injury or death WARNING New York Massachusetts SCAQMD CEC Listed MEA 425 05 E Boilers G1 06 06 24A Compliant Rule1146 2 California Energy Commission Heaters G1 06 06 2...

Страница 2: ...Central Heating Only Single Boiler 8 CONFIGURATION 4 Central Heating Only Multiple Boiler Cascade 9 CONFIGURATION 5 Residential Heating w Pumped DHW Single Combi Boiler 10 CONFIGURATION 6 Central Hea...

Страница 3: ...ng Boiler 5 minutes Pump P1 Domestic Hot Water heating zone pump 1 minute Pump P2 Diverting Valve Zone Transport Pump 5 minutes Pump P3 DISPLAY The 3 digit display will show different information duri...

Страница 4: ...EV 06 2018 GENERAL DESCRIPTION That are represented by The following pages contain drawings that apply to all models of EVO products In addition most drawings reference a Low Loss Header which may als...

Страница 5: ...wing can be done 1 Adjust the heater minimum and maximum temperature setting via the red wheel located on the display panel within the range of 50 159 F Parameter 2 EA 2 EB 2 An external on off tank t...

Страница 6: ...range of 50 159 F Parameter 2 EA 2 EB It is important to set the red potentiometer wheel to the desired setpoint on the Lag heaters with the power off to the Lead heater This way in the event of a con...

Страница 7: ...ermistor is connected to terminals 1 2 or 9 10 26 27 depending on model The control will automatically sense the presence of the sensor When an outside temperature sensor is connected the flow tempera...

Страница 8: ...195 F Parameter 2 EB 2 EA 2 Outdoor temperature reset can be enabled by connecting a 10k ohm sensor to terminals 1 2 or 9 10 26 27 depending on model this will be automatically sensed by the FMT 914...

Страница 9: ...be controlled based on the Room Thermostat must add heating harness WRE74090 and wire to P3 leads Caution maximum available wattage for external load on the FMT 914 control board is 550 watts If pumps...

Страница 10: ...ry heating loop In this configuration the following can be done 1 Adjust the boiler minimum and maximum temperature setting via the potentiometer located on the display panel within the range of 50 19...

Страница 11: ...nfiguration the following can be done 1 Adjust the boiler minimum and maximum temperature setting via the potentiometer located on the display panel within the range of 50 192 F Parameter 2 EB 2 EA 2...

Страница 12: ...entiometer located on the display panel within the range of 50 192 F Parameter 2 EB 2 EA 2 Set boiler water temperature to the DHW tank Factory default is 185 Parameter 2 CE 3 Set the DHW water temper...

Страница 13: ...ting valve is to be connected to the harness leads labeled 3 way Open 3 way Close and 3 way L In this configuration the following can be done 1 Adjust the boiler minimum and maximum temperature settin...

Страница 14: ...maximum temperature setting via the potentiometer located on the display panel within the range of 95 195 F Parameter 2 EB 2 EA 2 Set the flow temperature to the DHW tank Factory default is 185 F Par...

Страница 15: ...15 34000 Autry Street Livonia MI 48150 800 968 5530 Fax 734 419 0209 www hamiltonengineering com LIT91110 REV 06 2018 HWD 129 199 8 STANDARD WIRING...

Страница 16: ...1 1 2 K6 K2 K2 K10 K6 On Off Switch 4 3 2 1 K6 K10 K2 Printed Circuit Board FMT914 K6 K2 K10 K1 K0 K10 K6 K2 K2 K2 K2 K2 K5 K5 K3 K3 K6 K10 K2 K7 K8 K6 K10 K6 K2 K10 K6 K2 K6 K2 K6 K6 3 15 Amp Pressu...

Страница 17: ...17 34000 Autry Street Livonia MI 48150 800 968 5530 Fax 734 419 0209 www hamiltonengineering com LIT91110 REV 06 2018 HWH 129 199 8 W 3 WAY...

Страница 18: ...ow white blue white red white black white K10 K12 K17 K18 K19 K5 K6 K7 K8 K9 orange blue red black purple white yellow brown green gray K0 K1 K2 K3 K4 K6 K6 K2 K6 K2 K6 K10 K2 K6 K10 K6 K8 K7 K2 K10 K...

Страница 19: ...X 4 X 2 X 1 Gas valve 1 Power Supply Cascade Connection 15 3 16 17 20 19 18 4 2 1 4 3 2 1 X 3 K2 K6 K10 K10 K6 K2 6 5 Thermostat Central Heat Room K1 K1 K4 K4 0 10 VDC 7 8 10 9 Sensor Outside K8 K8 1...

Страница 20: ...Fuse X 10 X 9 X 8 X5 X 4 X 2 X 1 Gas valve 1 Power Supply Cascade Connection 15 3 16 17 20 19 18 4 2 1 4 3 2 1 X 3 K2 K6 K10 K10 K6 K2 6 5 Thermostat Central Heat Room K1 K1 K4 K4 0 10 VDC 7 8 10 9 S...

Страница 21: ...ndirect OPEN THERM PCB BURNER L1 24 ST 3 8 7 Thermostat Remote Additional Heat Source Dry Contact Dry Contact Signal Lock Out External L2 K2 Pressure switch Open switch indicates as H 1 High limit the...

Отзывы: