Instruction Manual PUC 28
44
8.2 Adjusting the analogue inputs and outputs
After selecting the “TEACH” submenu, the request to enter the code appears (“CODE -
TEACH”). Please proceed as follows:
1.
Press the “Scroll right” key - an “X” appears
2.
Confirm using “Enter” and “Scroll up” until “SIGNAL” is activated
3.
Using the “Scroll right” key, select between the current (“I”) and voltage input (“V”) and
confirm using “Enter”
4.
Use “Scroll up” to select the input or output (“OUT-P”, “IN1” or “IN2”) and confirm using
“Enter”
7. Continue to repeat this process until no more target values appear
8. E
xit the menu using the “Menu” key and briefly interrupt the voltage (hardware reset) or
choose “Reset” in the Menu [ SETTINGS ]
9 Care instructions for PUC 28
To clean the PUC 28 surface please only use mild dishwashing detergent.
Don’t use any abrasive or acidly detergent, because the surface can be damaged.
Don’t use any detergent containing isopropanol, because the Display-Window will be cloudy.
If
“IN1” or “IN2” has been selected:
5. Apply the target value (current or
voltage) shown on the display to the
input
6.
Confirm using the “Enter” key and
continue with 5
If
“OUT-P” has been selected:
5.
Using the “Scroll up” and “Scroll right”
keys, continue to change the value in
the center line until the current or
voltage target value specified in the top
line appears at the output terminals.
The 4-digit value in the center of the
display must be selected to be as large
as possible while maintaining the target
value. That is, it has to be found the
highest possible 4-digit value for that
the desired current or voltage target
value appears at the output terminals
(when teaching 0 V and 0 mA, there’s
an interval between 0 and a value, from
which the output signal begins to rise
up).
6. Confirm using the “Enter” key and
continue with 5