Instruction Manual PUC 28
28
No.
Name
Format
Unit
Description
25
WarnIN2PHyst
float
Pa
Warning of IN2, hysteresis (input IN2 as
pressure)
26
FilterP
integer
msec
Filter time internal pressure
27
FilterIN1
integer
msec
Filter time IN1
28
FilterIN2
integer
msec
Filter time IN2
29
Lang
integer
Language
0 = german; 1 = english
30
Password
integer
Password (4-digit)
31
MeasRange
integer
measurement range
0 = ±250Pa; 1 = ±100Pa
32
ExtPress
integer
Configuration for external pressure
0 = no external pressure sensors
1 = only at IN-2
2 = only at IN-1
3 = at both analogue inputs
33
UnitP
integer
Display of internal pressure
0 = Pa; 1 = hPa; 2 = mbar; 3 = off
34
UnitIN1
integer
Display of IN-1
0 = °C or Pa; 1 = hPa; 2 = mbar; 3 = off
35
UnitIN2
integer
Display of IN-2
0 = %rH or Pa; 1 = hPa; 2 = mbar; 3 = off
36
SignalP
integer
Signal at analogue output
0 = 0 - 20mA; 1 = 4 - 20mA; 2 = 0 - 10V
37
SignalIN1
integer
Signal at IN-1
0 = 0 - 20mA; 1 = 4 - 20mA; 2 = 0 - 10V
38
SignalIN2
integer
Signal at IN-2
0 = 0 - 20mA; 1 = 4 - 20mA; 2 = 0 - 10V
39
Sound
integer
Warning sound
0 = off; 1 = on
40
SoundTime
integer
msec
Length of warning sound
41
DecPlP
integer
decimal places of internal pressure
0 = off; 1 = on
42
DecPlIN1T
integer
decimal places of IN1 as temperature
0 = off; 1 = on
43
DecPlIN1P
integer
decimal places of IN1 as pressure
0 = off; 1 = on
44
DecPlIN2H
integer
decimal places of IN2 as humidity
0 = off; 1 = on
45
DecPlIN2P
integer
decimal places of IN2 as pressure
0 = off; 1 = on
46
RelAssign
integer
Relay-Channel-Assignment
0 = never switched on
1 = when IN2 is exceeded/dropped
2 = when IN1 is exceeded/dropped
3 = when IN1 + IN2 is exceeded/dropped
4 = when int. pressure is exceeded/dropped
5 = when int. pr IN2 is exceeded/
dropped
6 = when int. pr IN1 is exceeded/
dropped
7 = when int. pr IN1 + IN2 is exceeded/
dropped