_________________________________ ___EN__________________________________30
Query mode
Simultaneously press the ‘
E-HEATER
’ and ‘
DISINFECT
’ buttons for 1 second
to enter the query menu. You can check the operational parameters and
settings of the appliance here by using the
‘DOWN’
or
‘UP’
arrow.
To quit the query mode, press and hold down the ‘
CANCEL
’ button for 1
second or do not press any button for 30 seconds.
Information displayed:
No.
Second digit of
clock display
First digit of
minutes
Second
digit of
minutes
Quantity
Explanation
1
Temperature (°C)
T5U
2
Temperature (°C)
T5L
3
Temperature (°C)
T3
4
Temperature (°C)
T4
5
Temperature (°C)
TP
6
Temperature (°C)
Th
7
Amperage (A)
Compressor
8
Last error code
9
Previous 1st error or self
protection code
10
Previous 2nd error or self
protection code
11
Software Version
Defreezing function
When the external temperature falls below T3 ≤0℃ and the compressor runs more than
40 minutes continuously. (If the compressor tries to switch on too often in a period of 10
minutes.) From the beginning of every cycle started, the system measures operating time,
and when it reaches 40 minutes, the defreezing cycle is activated 2 minutes after the start
of the compressor.
Defreezing stops when the following conditions are met.
3.
10 minutes after the start of defreezing.
4.
T3≥15
°C
.
Operating cycle of the main cooling circuit elements during defreezing: