Page 45
UNDERWRITER'S LABORATORIES (UL) INSTALLATION REQUIREMENTS
The OmniLT control unit (21A00-1) is suitable for Grade A household burglar and fire applications. Refer to UL1641 for installation
requirements.
1.
The line carrier (X-10) operation is considered supplementary. Operation of the line carrier devices was not investigated by UL.
2.
For those zones programmed as PANIC, DURESS or POLICE EMERGENCY, the initiating device shall be a UL Listed Hold Up Device switch.
3.
Connections to phone circuit must be made via the supplied cable and RJ31X Jack as shown under RJ31X JACK CONNECTIONS in this manual.
4.
For connection of smoke detectors to the controller, refer to requirements under FIRE ZONE HOOKUP and FIRE ZONE CONNECTIONS diagrams in this
manual.
5.
For fire detection, maximum current ratings for 24 hours must be observed.
6.
Recognized energy limited cable shall be employed, 22 AWG minimum for all connections.
7.
The audible signal appliance shall be the Listed Wheelock Model MT-12/24-R Multitone Signal, rated 10.5 - 15.6 VDC, 95 dB(A) with 2 reflecting planes.
The audible signal shall be mounted indoors in a central location. The audible signal appliance should be connected to the "BELL" circuit.
8.
If used, the OUTSIDE SIREN DELAY shall be set to 0 seconds.
9.
If the remote arm/disarm switch is used, it shall be the Listed Ademco Model 9789.
10.
Operation of the controls with the Programmable Energy Saver Module was not conducted by UL.
11.
Operation of the Model 12A00 Wireless Receiver was not verified by UL.
12.
Operation of the Two-Way Audio Module was not verified by UL.
13.
Refer to the OmniLT Owner's Manual (Document No. 21R00-1) for programming requirements in UL Listed Installations.
14.
For the monitoring of burglar alarm initiating devices, the zone type shall provide an audible output (i.e., not DURESS).
15.
The OmniLT controller must be connected (when employed) to listed carbon monoxide gas detectors (i.e. Sentrol -Model 240-CO).
16.
All connections to energy sensors and modules must be done to listed Class 2 circuits only.
17.
The OmniLT must be used in Residential Applications that are under a single ownership.
When used in UL Listed Installations, the following items apply:
1.
The "High Security Mode" must be ON.
2.
The "Enable Auto Bypass" must be OFF.
3.
The "Zone Resistors" must be YES.
4.
The "Supervise Bell" must be YES.
5.
The "Beep On Trouble" must be ON.
6.
The ENTRY DELAY SHALL NOT EXCEED 45 SECONDS for Residential Applications.
7.
The EXIT DELAY shall not exceed 60 seconds.
8.
Double Delay and Quad Delay zone types shall not be used.
9.
For Residential Applications, the sounding device may be mounted indoors. If, however, the sounding device is connected to a circuit configured as an
"Exterior Sounder", the OUTSIDE SIREN DELAY shall be set to 0.
10.
Installer: NAME: __________________________________ NUMBER: _______________________________