Page 38
To disable the digital communicator for a specific zone, set the alarm code to 0 or 00. The digital dialer will
not report when this zone is tripped.
ZONE 1 ALARM CODE: 01
0-FF
↕
THROUGH
USER 8 CLOSE CODE: 68
0-FF
↑
SETUP TEMPERATURES
To configure temperatures from the Installer Setup Menu, press the 5 (Temp) key.
TEMPERATURE DISPLAY
This allows you to choose between Fahrenheit or Celsius temperature format.
TEMPERATURE DISPLAY: 1
1=FAHRENHEIT 2=CELSIUS
↓
THERMOSTAT TYPE
If thermostats are part of the system, this item specifies the thermostat type for each thermostat (this enables the thermostat).
For thermostat types, the current setting is shown on the bottom line.
THERMOSTAT 1 TYPE: 1
AUTO HEAT/COOL #=CHNG
↕
THERMOSTAT 2 TYPE: 0
NOT USED #=CHNG
↑
To change a thermostat type, use the arrow keys to scroll through the list of thermostat types, then press ' # ' to select a new type
.
TYPE
NUMBER
DESCRIPTION
AUTO HEAT/COOL
1
Automatic changeover heat and cool thermostat
HEAT/COOL
2
Manual changeover heat and cool thermostat
HEAT ONLY
3
Heating only thermostat
COOL ONLY
4
Cooling only thermostat
SETPOINT ONLY
5
Setpoint only thermostat