powerway enclosures and components
U-PWE/U-PWK
46
U-PW powerway System Manual
Electrical features of the H-SaS
Enclosure depth
600 mm
800 mm
Rated current per busbar system initial
supply
≤ 2950 A
≤ 4000 A
Rated current I
nA
(H-SaS top)
2x 30 x 10: 1250 A
2x 40 x 10: 1600 A
2x 60 x 10: 2000 A
2x 80 x 10: 2850 A
4x 60 x 10: 3200 A
4x 80 x 10: 4000 A
Rated current I
nA
(H-SaS bottom/middle)
2x 30 x 10: 1250 A
2x 40 x 10: 1600 A
2x 60 x 10: 2000 A
2x 80 x 10: 2950 A
4x 60 x 10: 3200 A
4x 80 x 10: 4000 A
Rated current I
nA
(2x H-SaS top/middle or top/bottom)
2x H-SaS 2 x 30 x 10: 1250 A
2x H-SaS 2 x 40 x 10: 1600 A
2x H-SaS 2 x 60 x 10: 2000 A
2x H-SaS 2 x 80 x 10: 2500 A
2x H-SaS 4 x 60 x 10: 3200 A
2x H-SaS 4 x 80 x 10: 4000 A
Rated current I
nA
(2x H-SaS middle/bottom)
2x H-SaS 2 x 30 x 10: 1250 A
2x H-SaS 2 x 40 x 10: 1600 A
2x H-SaS 2 x 60 x 10: 2000 A
2x H-SaS 2 x 80 x 10: 2600 A
2x H-SaS 4 x 60 x 10: 3200 A
2x H-SaS 4 x 80 x 10: 4000 A
Rated short-time withstand current I
cw
(1
s)
(system-related distance between
supports)
2x 30 x 10: 60 kA
2x 40 x 10: 65 kA
2x 60 x 10: 85 kA
2x 80 x 10: 85 kA
2x 60 x 10: 100 kA with FG
[1]
2x 80 x 10: 100 kA with FG
[1]
4x 60 x 10: 85 kA
4x 80 x 10: 85 kA
4x 60 x 10: 120 kA with FG
[1]
4x 80 x 10: 120 kA FG
[1]
Содержание unimes H U-PW powerway
Страница 2: ......
Страница 5: ......
Страница 15: ......
Страница 17: ...02 Page Intended use 16 Misuse 16 General safety instructions 17...
Страница 61: ......
Страница 71: ......
Страница 73: ...05 Page Personnel requirements 72 hw circuit breakers Quick guide 73...
Страница 79: ...06 Page Maintenance 78...