U-PWE/U-PWK
40
U-PW powerway System Manual
Device compartment
Control compartment
Module heights
12 MU = 600 mm
Expansion
–
Control compartment, swivelled (mounting plate)
–
Control compartment, fixed (clear polycarbonate plate)
Derating factors ACB
Derating factors I
e
/I
n
for incoming, outgoing and cross coupling unit function at 35°C ambient tempe-
rature in protection type version IP2x, IP3x and IP4x.
Enclosure type
U-PWE
U-PWK
Enclosure width
600 mm
Enclosure depth
600/800 mm
Device size I
N
400 A, 630 A, 800 A, 1000 A, 1250 A, 1600 A
Rated device current I
nA
400 A, 630 A, 800 A, 1000 A, 1250 A, 1600 A
Derating factor F
Base-roof without ventilation
0.92
0 cm²
0.81
0 cm²
Derating factor F
Base-module roof IP40 with ventilation
0.95
330 cm²
0.93
330 cm²
Max. mountable power loss Pv for devices
(I
N
on H-SaS and F-SaS max. load)
Cover plate closed
Cover plate of module roof IP40
458 W
458 W
458 W
458 W