powerway enclosures and components
U-PWE/U-PWK
58
U-PW powerway System Manual
Cross-wiring in the enclosure
Front
Side
Top
–
The vertical auxiliary circuit can be routed along the supports (on the left and right of the device com-
partment) depending on the enclosure design.
–
The horizontal circuit can be routed above and below the ACB. It is also possible to connect the auxili-
ary circuit from the switch/circuit breaker to the terminals at the top and bottom of the enclosure.
–
The preferred horizontally routed auxiliary circuit should be routed under the enclosure roof or on the
floor (instead of the PE).
–
The PE and auxiliary circuit should be routed separately.
–
The PE must be routed in front and the auxiliary circuit in the back when PE and auxiliary circuit cannot
be routed separately. This ensures that the auxiliary circuit will not collide with the wiring of the installed
equipment.
–
The horizontal auxiliary circuit can also be routed along the roof of the switchgear and controlgear as-
sembly enclosure (metal cable conduit on the enclosure roof. Cover plate perforated as for 2b partition)