powerway enclosures and components
Technical data
U-PW powerway System Manual
21
03.02
Technical data
03.02.01
unimes H
General characteristic features of the switchgear and controlgear assembly interfaces
Degree of pollution
3
Installation site
Fixed indoor installation
Protection type
–
Devices can be operated from the outsi-
de
≤ IP3x
–
Devices can be operated behind the door
≤ IP4x
Outer design
Enclosure design
Protection against mechanical influence
–
IK8
Configurations with glazed doors
–
IK10
Configurations with solid and module doors including fixed fronts
Rated insulation voltage U
i
Material group
Minimum creepage distances
250 V
I
3.2 mm
II
3.6 mm
IIIa
4 mm
IIIb
4 mm
400 V
I
5 mm
II
5.6 mm
IIIa
6.3 mm
IIIb
6.3 mm
630 V
I
8 mm
II
9 mm
IIIa
10 mm
IIIb
10 mm
1000 V
I
12.5 mm
II
14 mm
IIIa
16 mm
Relationship between nominal voltage of the energy distribution and the rated impulse withstand voltage of the
equipment in accordance with IEC EN 61439-1 table G.1
Overvoltage category
III
IV
230 / 400 V
4 kV
6 kV
400 / 690 V
6 kV
8 kV
690 / 1000 V
8 kV
12 kV
Type of earth connection
TN-S
Neutral conductor (N) and protective earth (PE) are routed separately in the entire system.
TN-C
Neutral conductor (N) and protective earth (PE) are consolidated in a single conductor, the PEN
conductor, in the entire system
TN-C-S
In the distribution network, the neutral conductor (N) and the protective earth (PE) are combined (PEN
conductor) and separated in the consumption system.
TT
With the TT network, the star point of the transformer and the bodies of the equipment are directly
earthed. The protective earth is thus not in contact with the neutral conductor.
IT
The IT network does not have a direct connection between active conductors and earthed parts; the
bodies of the electrical system are earthed.
Содержание unimes H U-PW powerway
Страница 2: ......
Страница 5: ......
Страница 15: ......
Страница 17: ...02 Page Intended use 16 Misuse 16 General safety instructions 17...
Страница 61: ......
Страница 71: ......
Страница 73: ...05 Page Personnel requirements 72 hw circuit breakers Quick guide 73...