OID keys:
OID
Description
Type
.1.3.6.1.4.1.22626.1.6.1
Device information
.1.3.6.1.4.1.22626.1.6.1.1.0
Device name
String
.1.3.6.1.4.1.22626.1.6.1.2.0
Serial number
String
.1.3.6.1.4.1.22626.1.6.1.3.0
Device type
Integer
.1.3.6.1.4.1.22626.1.6.2.ch
Measured value (where ch is channel number)
.1.3.6.1.4.1.22626.1.6.2.ch.1.0
Channel name
String
.1.3.6.1.4.1.22626.1.6.2.ch.2.0
Unit
String
.1.3.6.1.4.1.22626.1.6.2.ch.3.0
Value
String
.1.3.6.1.4.1.22626.1.6.2.ch.4.0
Actual value
–
16bit (12dgrC=12)
Integer
.1.3.6.1.4.1.22626.1.6.2.ch.5.0
Actual value
–
16bit (12.5dgrC=125)
Int*10
.1.3.6.1.4.1.22626.1.6.2.ch.6.0
Actual value
–
16bit (12.53dgrC=1253) Int*100
.1.3.6.1.4.1.22626.1.6.2.ch.7.0
Actual value
–
16bit (12dgrC=12)
Integer
.1.3.6.1.4.1.22626.1.6.2.ch.8.0
Actual value
–
32bit (12.5dgrC=125)
Int*10
.1.3.6.1.4.1.22626.1.6.2.ch.9.0
Actual value
–
32bit (12.53dgrC=1253) Int*100
.1.3.6.1.4.1.22626.1.6.2.ch.10.0
Actual current [mA]
String
.1.3.6.1.4.1.22626.1.6.2.ch.11.0
Actual current [uA] (120uA=120)
Integer
.1.3.6.1.4.1.22626.1.6.2.ch.12.0
Alarm on channel (0, 1, 2)
Integer
.1.3.6.1.4.1.22626.1.6.2.ch.13.0
Alarm on channel (none, high, low)
String
.1.3.6.1.4.1.22626.1.6.3.1.0
SNMP Trap text
String
When alarm occurred a warning messages (trap) can be sent to selected IP addresses.
Addresses can be set using web interface. Traps are sent via
UDP
protocol on
port 162
. The
device can send following traps:
Trap
Description
0/0
Reset of the device
1/0
Settings was changed
6/0
Testing Trap
6/1
NTP synchronization error
6/2
E-mail sending
error
SMTP server login error
6/3
SMTP authentication error
6/4
Some error occurred during SMTP communication
6/5
TCP connection to server cannot be opened
6/6
DNS error
6/7
SOAP message
sending error
SOAP file not found inside web memory
6/8
DNS error or MAC address cannot be obtained
6/9
TCP connection to server cannot be opened
6/10
Wrong response code from the SOAP server
6/11, 6/12
Upper alarm on channel
6/21, 6/22
Lower alarm on channel
6/31, 6/32
Clearing alarm on channel
6/41, 6/42
Measuring error