Sensor Connections - Separate Ethernet Connection Box (3 Glands)
21
Live
Neutral
Earth
TX-
TX+
Signal GND
Signal GND
Screen
Earth
Lid and
Case Earth
1
2
3
6
1
2
3
6
RS422 Link
to Vessel’s
DP System
Ethernet Link
to RadaScan
Type 2 Marine
Processor
RS422 Link
9600 baud
8 bits
1 stop bit
No parity
Cables from
RadaScan
Sensor
Power
DP Feed
Dashboard
CAT 5e Cable
CAT 5e Cable
*
*
RadaScan Sensor
Connection
Box
Default IP Addresses:
†
RadaScan Sensor:
192.168.2.231
Subnet Mask:
255.255.255.0
Type 2 Marine Processor (LAN1):
192.168.2.241
Subnet Mask:
255.255.255.0
!
CAUTION
Double Pole/
Neutral Fusing
*
RadaScan Fuse Rating:
2 x T4A H 250V
OR
2 x T8A H 125V
(5 x 20mm)
Connection Box
Patch Cable
Mains Power
115VAC 45-65Hz
300W
OR
240VAC 45-65Hz
300W
!
NOTE: This connection box
should not be used with the Low
Temperature Sensor as it does not
provide heater power
The
Patch Cable
can be disconnected
at one end and connected to a service
laptop.
The laptop can then be used to check the
Ethernet link by ‘pinging’ either the Type 2
Marine Processor or the RadaScan Sensor.
†
Changing the Sensor IP Address Setting
Guidance Marine if alternative settings are required.
Network IP
Address