UPS Specifications
The main power supply to the CyScan sensor and the computer(s) running the CSI and
Dashboard must come directly from a UPS (Un-interruptible Power Supply), which will also
act as the power disconnection point.
The CyScan system comprises the following components and the UPS system used must
meet these minimum specifications:
CyScan Sensor
•
The UPS must be Marine Type Approved
•
Output Power = 3W / 35 dBm
•
Input Power = 45W
•
Voltage Range = 85-264 Vac
•
Peak Current draw at 110V = 1.14A RMS
•
Nominal Current draw at 110V = 0.68A RMS
•
Peak Current draw at 240V = 0.52A RMS
•
Nominal Current draw at 240V = 0.4A RMS
Type 2 Marine Processor Power Adaptor
•
Voltage Range = 100-240V
•
Frequency Range = 50-60Hz
•
Peak Current draw = 1.5A RMS
The CyScan UPS should be able to run on back-up power for at least the same duration as
that specified for the DP System UPS.
The power cable to the CyScan Sensor must be rated to withstand the maximum current
output of the UPS.
The specifications given above apply when the UPS is connected to a CyScan
system only.
Type 3 Marine Processor Power Adaptor
•
Voltage Range = 100-240V
•
Frequency Range = 50-60Hz
•
Peak Current draw = 1.8A RMS
Hatteland Panel PC
•
Voltage Range = 115 & 230V
•
Frequency Range = 50-60Hz
•
Nominal Current draw at 115V = 0.52A RMS
•
Nominal Current draw at 230V = 0.26A RMS