Client and DP Feed Connections - Ethernet Client, Dual Serial DP
To Connect an Ethernet Sensor with Ethernet to the Client and Serial to Two DP Systems:
Connect
Ethernet Port 0
to the
Client Computer
,
Serial Port 0
to
DP System 1
and
Serial Port 1
to
DP system 2
.
Configure the serial connections as shown below:
1 RX-
2 RX+
3 TX-
4 TX+
5 GND
DP
Feed 2
RS422
Link to DP
System 1
Mains Power
85–264V AC
45–65Hz 45W
Serial 1
Ferrite Bead
Serial 0
Serial 1
Power
Power LED
VFD Screen
Fuses
Stern
Bow
Service Connections
RS422 Link
9600 baud
8 bits
1 stop bit
No parity
Ethernet Link to
Client
Computer
To Connect Cables
to Power/Serial
Plugs:
.
.
Hook lever-tool into
slot above
connector-hole in
plug.
.
3
Whilst holding down
lever, insert cable
end into connector-
hole.
.
$
Release and remove
the lever-tool.
RS422
Link to DP
System 2
1 RX-
2 RX+
3 TX-
4 TX+
5 GND
DP
Feed 1
Serial 0
The Kongsberg Maritime CyScan Sensor (continued)
Patch
Lead
†
Ethernet
6
3
2
1
802.3u
MDI-II
†
Only use KRONE
Insertion Tool 6089 2
003-00 to terminate
Ethernet wires into
push-down connector
Client Network Protocol:
Ethernet
Default Ethernet Settings:
†
IP Address:
192.168.0.86
Subnet Mask:
255.255.255.0
†
Contact Guidance
Marine if
alternative settings
are required