99
Expert Power Control 8041/8045
© 2022 GUDE Systems GmbH
Specifications
2
Temperature, Humidity, Air Pressure
7006, 7106, 7206
External Sensor Field Table "{sen_field}"
Index
Description
Unit
0
Temperature
°C
1
Humidity
%
2
Digital Input
bool
3
Air Pressure
hPa
4
Dew Point
°C
5
Dew Point Temperature Difference
°C
4.8.4
Serial Console
If the device has a serial port, the entire console command set for Telnet is also available
at the serial console. Connect your PC to the device via an RS232 serial cable (9-pin
RS232). To use the editing functions, the serial terminal must support VT100 emulation,
and "echo" must not be activated. In the device configuration on the other hand, "Activ-
ate echo" should be set to "yes" and "Raw mode" to "no". Start your terminal program
and select the COM port to which the RS232 cable is connected. Use the following set-
tings for the serial port:
Baudrate
115200
Databits
8
Parity
No
Stoppbits
1
Flow Control
No
KVM Protocol
For compatibility reasons, the KVM protocol can also be activated on the serial port.
These binary control sequences can be used for devices with power ports, to turn the re-
lays on and off individually.
Syntax:
w x y z
·
w
prefix 0x80
·
x
command (0x31 to turn on, 0x32 for turning off)
·
y
port number (0x01 ... )
·
z
check byte, must be: \x xor \y
Before the KVM protocol is recognized, the Enable binary KVM protocol entry must
be activated in the "Console" configuration.
KVM Examples