94
Expert Power Control 8041/8045
© 2022 GUDE Systems GmbH
Specifications
portsensor {port_num} {energy_sensor} publish
delta set {float}
sets publish delta value
portsensor {port_num} {energy_sensor} publish
delta show
show s publish delta value
portsensor {port_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port set {port_num} set
sets pow er port for sensor values action
portsensor {port_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state set {OFF=0|ON=1|
DISABLED=2}
sets state for sensor values action
portsensor {port_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} port show
show s port for sensor values action
portsensor {port_num} {energy_sensor}
{BELOWMIN=0|ABOVEMIN=1|ABOVEMAX=2|
BELOWMAX=3} state show
show s state for sensor values action
portsensor {port_num} events set {OFF=0|ON=1} LEGACY - enables sensor events on/off
L
portsensor {port_num} events show
LEGACY - show s if sensor events are enabled
L
portsensor {port_num} events type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2,E
VT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER=5,E
VT_DISPLAY=6,EVT_CONSOLE=7,EVT_MQTT=8}
"
LEGACY - enables different event types
1
portsensor {port_num} events type show
LEGACY - show s w hat event types are enabled
L
portsensor {port_num} maxval set {num}
LEGACY - sets maximum value for sensor
L
portsensor {port_num} maxval show
LEGACY - show s maximum value for sensor
L
portsensor {port_num} minval set {num}
LEGACY - sets minimum value for sensor
L
portsensor {port_num} minval show
LEGACY - show s minimum value for sensor
L
portsensor {port_num} hyst set {num}
LEGACY - sets hysterese value for sensor
L
portsensor {port_num} hyst show
LEGACY - show s hysterese value for sensor
L
portsensor {port_num} {BELOWMIN=0|
ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} port
set {port_num} set
LEGACY - sets pow er port for sensor values
action
L
portsensor {port_num} {BELOWMIN=0|
ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3}
state set {OFF=0|ON=1|DISABLED=2}
LEGACY - sets state for sensor values action
L
portsensor {port_num} {BELOWMIN=0|
ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3} port
show
LEGACY - show s port for sensor values action
L
portsensor {port_num} {BELOWMIN=0|
ABOVEMIN=1|ABOVEMAX=2|BELOWMAX=3}
state show
LEGACY - show s state for sensor values action
L
radius
enters cmd group "radius"
radius {PRIMARY=0|SECONDARY=1} enabled set
<off=0/on=1>
enables radius client
radius {PRIMARY=0|SECONDARY=1} enabled
show
show if radius client enabled
radius {PRIMARY=0|SECONDARY=1} server set
"<dns_name>"
sets radius server address
radius {PRIMARY=0|SECONDARY=1} server
show
show s radius server address
radius {PRIMARY=0|SECONDARY=1} passw ord
set "{passw d}"
sets radius server shared secret
radius {PRIMARY=0|SECONDARY=1} passw ord
hash set "{passw d}"
sets radius server crypted shared secret
radius {PRIMARY=0|SECONDARY=1} auth timeout
set {num_secs}
sets server request timeout
radius {PRIMARY=0|SECONDARY=1} auth timeout
show
show s server request timeout
radius {PRIMARY=0|SECONDARY=1} retries set
{0..99}
sets server number of retries
radius {PRIMARY=0|SECONDARY=1} retries
show
show s server number of retries