9
Expert Power Control 8041/8045
© 2022 GUDE Systems GmbH
Device Description
9. RS232 connector
Expert Power Control 8041/8045 - 1
10. Mains supply (IEC C20, max.16 A)
11. 12 x Load outputs (IEC C13, max. 16 A)
Expert Power Control 8041/8045 - 2
12. Mains supply (IEC C20, max.16 A)
13. 12 x Load outputs (IEC C13, max. 16 A, IEC-Lock)
Start-up the device
·
Connect the power cord (IEC C19, max. 16A) to the mains supply. The cable connect-
ors are secured as regards their type against unintentional loosening. They must be
inserted up to the stop, otherwise there is no secure connection. The plug must not
wobble in the socket, or there is no tight connection.
·
Plug the network cable into the Ethernet socket (RJ45).
·
If required, setup a serial connection to the RS232 port.
·
Insert the optional external sensors into the sensor connectors.
·
Connect the consumers with the load outputs (IEC C13, max. 10A).
1.5
Overvoltage Protection
The device contains an overvoltage protection. The protection is based on input side
varistors with thermal fuse between phase (L) and neutral (N) to protect the internal elec-
tronics and power ports with failure detection (permanently triggered thermal fuse). The
state of the protection is indicated on the front panel by a flash.
·
An invisible flash means that the protection is active, a red flash symbolizes that the
overvoltage protection fails. (Revision 1 device)