86
Expert Power Control 8041/8045
© 2022 GUDE Systems GmbH
Specifications
External Sensor Type Table "{sen_type}"
Constants "{7x01=0|7x04=0|7x02=1|7x05=1|7x06=2}"
Index
Description
Products
0
Temperature
7001, 7101, 7201
0
Temperature
7004, 7104, 7204
1
Temperature, Humidity
7002, 7102, 7202
1
Temperature, Humidity
7005, 7105, 7205
2
Temperature, Humidity, Air Pressure
7006, 7106, 7206
External Sensor Field Table "{sen_field}"
Index
Description
Unit
0
Temperature
°C
1
Humidity
%
2
Digital Input
bool
3
Air Pressure
hPa
4
Dew Point
°C
5
Dew Point Temperature Difference
°C
4.8.3
Console Cmd 8045
Command
Description
Note
logout
go to login prompt w hen enabled
2
quit
quits telnet session - nothing in serial console
2
back
back one cmd level
2
help
show all cmds from this level
2
help all
show all cmds
2
clock
enters cmd group "clock"
clock ntp enabled set {OFF=0|ON=1}
enables ntp
clock ntp enabled show
show s if ntp enabled
clock timezone set {minutes}
sets timezone
clock timezone show
show s timezone
clock dst enabled set {OFF=0|ON=1}
enables dst
clock dst enabled show
show s if dst is enabled
clock manual set "{hh:mm:ss yyyy-mm-dd}"
sets time and date manually
clock show
show s actual time and date
clock ntp server {PRIMARY=0|BACKUP=1} set
"{dns_name}"
sets ntp server name
clock ntp server {PRIMARY=0|BACKUP=1} show show s ntp server name
console
enters cmd group "console"
console version
show s unique console version number
console telnet enabled set {OFF=0|ON=1}
enables telnet on/off
console telnet enabled show
show s if telnet enabled
console telnet port set {ip_port}
sets telnet port
console telnet port show
show s telnet port
console telnet raw set {OFF=0|ON=1}
sets raw mode (disables editing) on/off
console telnet raw show
show s if raw mode enabled
console telnet echo set {OFF=0|ON=1}
enables echo on/off
console telnet echo show
show s if echo enabled
console telnet activeneg set {OFF=0|ON=1}
enables telnet active negotiation (IAC) on/off
console telnet activeneg show
show s if active negotiation enabled
console telnet login set {OFF=0|ON=1}
enables login on/off