background image

 

NS3000 Series User Manual 

Chapter 7 Maintenance 

This chapter introduces UPS maintenance, including the maintenance instructions of power module, 

monitoring bypass module and the change method of dust filter.   

7.1 Instruction of Maintenance Operation 

7.1.1 Precautions 

1. 

Only maintaining engineers can do this job.   

2. 

In principle, the broken elements should be disassembled from top to bottom, so as to prevent any 

inclination from high gravity centre of the cabinet.   

3. 

To  ensure  the  safety  before  maintaining  power  module  and  bypass  module,  be  sure  to  use  a 

multimeter to  measure the DC  bus capacitor voltage  and ensure  the voltage is  below  60V  before 

operation, and use a multimeter to  measure the voltage between operating parts and the earth to 

ensure  the voltage is lower  than  hazardous  voltage, i.e. DC  voltage is lower  than 60Vdc, and  AC 

maximum Voltage is lower than 42.4Vac. 

4. 

Only after 10 minutes removing the power components and bypass components, the maintenance 

can be carried out. 

7.1.2 Instruction to Bypass Module   

Suppose UPS were in normal mode, and the bypass were normal: 

1. 

Select manual switch of bypass in LCD screen, the UPS power will be supplied by bypass. 

2. 

Close maintenance bypass switch, the UPS power will be supplied by maintenance bypass. 

3. 

Open UPS output switch and input switch. 

4. 

Open external battery switch and internal battery switch. 

5. 

Take the door sheet of UPS off, remove and repair the damage components,   

6. 

Reinstall the corresponding components in the cabinet after maintenance, reinstall the internal door 

sheet, and complete connection of the flat cables at the front of the internal door.   

7. 

Close the bypass switch of UPS and switch the rotary switch to UPS output. 

After  5  seconds,  the  indicator  light  of  the  operating control  display  panel  works,  which  shows  the 

power is normally supply by the bypass. 

8. 

Open  maintenance  bypass  switch  and  close  mains  input  switch,  the  inverter  automatically  starts, 

and UPS operates in the normal mode after 60 seconds. 

9. 

Close  external  battery  switch  or  internal  battery  switch,  the  battery  light  on  the  panel  turns  off, 

which show connection with the battery; inspect the battery voltage is normal or not which is shown 

on the panel.   

 

NS3000 Series User Manual 

Chapter 8 Product Specification 

This chapter describes the product specification of UPS   

8.1 Applicable Standards 

UPS design meets the European and national standards given in Table 8-1.

 

Item 

Normative reference 

General  safety  requirements  for  UPS 

used in operator access areas 

EN50091-1-1/IEC62040-1-1/AS 62040-1:2009 

Electromagnetic  compatibility  (EMC) 

requirements for UPS 

EN50091-2/IEC62040-2/AS 62040-2 

Method  of  specifying  the  performance 

and test requirements of UPS 

EN50091-3/IEC62040-3/AS 62040-3(VFI SS 111) 

Note: The above mentioned product standards incorporate relevant compliance clauses with generic IEC 

and  EN  standards  for  safety  (IEC/EN/AS60950),  electromagnetic  emission  and  immunity  (IEC/EN/ 

AS61000 series) and construction (IEC/EN/AS60146 series and 60950) 

8.2 Environmental Characteristics 

  Table 8-2

 

Items 

Unit 

Requirements 

Acoustic noise level at 1 meter 

dB 

55 

Altitude of Operation   

1000m above sea level, derate power by 1% per 

100m between 1000m and 2000m 

Relative Humidity 

RH 

0 to 95% non condensing 

Operating Temperature 

°C

 

0 to 40 deg , Battery life is halved for every 10°C 

increase above 20°C 

UPS Storage-Transport Temperature 

°C

 

20 +70°C 

Recommended Battery Storage 

Temperature 

°C

 

20 +30 (20°C for optimum battery storage) 

8.3 Mechanical Characteristics 

  Table 8-3   

Cabinet Specification 

Unit 

NS3010, NS3020 

NS3030 

Mechanical Dimension, W×D×H 

mm 

 

540x690x1240 

 

Weight 

kg 

106Kg (Without battery) 

220Kg (with 40pcs 9A/h) 

332Kg (with 80pcs 9A/h)

 

118Kg (Without battery) 

344Kg (with 80pcs 9A/h)

 

Color 

N/A 

RAL 7016 

Protection Level, IEC(60529) 

N/A 

IP20 

Содержание NS3000 10 kVA

Страница 1: ...1 NS3000 Series User Manual Rev 01 UPS NS3000 10 20 30kVA USER Manual 2 NS3000 Series User Manual Rev 01...

Страница 2: ...te the static switch if excessive voltage is present at the bypass input when the bypass source is deenergized If this function is not installed and enabled there must be a warning label on the extern...

Страница 3: ...al rev 01 3 2 3 Auto Restart Mode 29 3 2 4 Bypass Mode 29 3 2 5 Maintenance Mode 29 3 2 6 ECO Mode 29 3 2 7 Frequency Converters Mode 29 3 2 8 Parallel connection redundancy mode 30 3 3 Battery Manage...

Страница 4: ...s any mistake for accessories contact with shipper or provider 1 3 Environment Checking Before installing UPS please check these items as below 1 Is the UPS operation environment temperature above 25...

Страница 5: ...sary a system of extractor fans should be installed to aid cooling air flow An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain a...

Страница 6: ...l Against ambient corrosive gases l Against excessive humidity and heat sources l Against dust l With the current fire prevention requirements l The operating environment temperature is within 20 25...

Страница 7: ...supply the installed device should l Sensitive to DC Class B or class A in the network l Insensitive to transient current pulses l Have an average sensitivity that is adjustable between 0 3A 1A 14 NS3...

Страница 8: ...epartment After the equipment has been finally positioned and secured connect the power cables as described in the following procedures 1 Verify that all the external input distribution switches of th...

Страница 9: ...2 5 A Pay attention all cable are marked and have different color 6 Connect the battery according fig 2 5 A don t connect A and B cable in the shelf 1 7 In shelf 1 on the left connect the cable mark...

Страница 10: ...d be double insulated with a typical 0 5 to 1 5 mm 2 cross section area for a maximum connection length between 25 and 50 meters 2 6 1 Dry Contact Interface of Battery and Environmental Temperature De...

Страница 11: ...Note 1 The emergency stop action within the UPS will shut down the rectifier inverter and static bypass However it does not internally disconnect the mains input and batterypower supply To disconnect...

Страница 12: ...neral warning dry contact interface diagram Table 2 7 Position Name Purpose J9 1 ALARM_NC Integrated warning relay normally closed will be open during warning J9 2 ALARM_NO Integrated warning relay no...

Страница 13: ...25 NS3000 Series User Manual rev 01 2 7 Installation Diagram 26 NS3000 Series User Manual rev 01 a 10KVA 30KVA terminal block NS3030 NS3010 NS3020...

Страница 14: ...ss module can be removed for maintenance Fig 3 1 System principle framework 28 NS3000 Series User Manual rev 01 3 1 2 Bypass During normal system operation the load is connected to the inverter but in...

Страница 15: ...e output frequency The range of output frequency is 40Hz 70Hz Under this mode static bypass is unavailable but battery can be selected according to the actual requirements of battery mode Frequency Co...

Страница 16: ...4 1 Typical 1 N parallel operation system Note when the load exceeds the capacity of the single device we recommended an external manual Bypass The cables for the parallel operation provide double in...

Страница 17: ...Warning Please confirm that UPS output rotating switch point to UPS with anti misoperation stop plate for rotating switch is fixed well 1 Close UPS bypass input switch and input switch in turns The LC...

Страница 18: ...aution Before making this operation read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it so as not to risk a short interruption in powering the loa...

Страница 19: ...chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail and provides LCD display information including LCD display types detailed...

Страница 20: ...tus indicator Steady red Failure 6 1 2 Audible Alarm buzzer There are two different types of audible alarm during UPS operation as shown in table 6 3 Table 6 3 Description of audible alarm Alarm Purpo...

Страница 21: ...rface you can select each function and press ENTER press ENTER again it will display Confirm interface 6 2 5 State Display The alarm page as below press left and right arrow to select STA in homepage...

Страница 22: ...inverted power supply status Bypass power supply The system is in bypass power supply status No power supply System no output Battery equalized charging Battery is in boost charging Battery float char...

Страница 23: ...hows the power is normally supply by the bypass 8 Open maintenance bypass switch and close mains input switch the inverter automatically starts and UPS operates in the normal mode after 60 seconds 9 C...

Страница 24: ...harge V cell 2 4V cell selectable from 2 3V cell 2 45V cell Constant current and constant voltage charge mode Battery Charging Power Max Current kW 10 UPS capacity selectable from 0 20 UPS capacity NS...

Страница 25: ...eutral cable A 1 7 In Frequency2 Hz 50 60 Switch time between bypass and inverter ms Synchronized switch 1ms Bypass voltage tolerance Vac Upper limit 10 15 or 20 default 20 Lower limit 10 20 30 or 40...

Отзывы: