background image

-

35

NS3000 Series User Manual    rev.01 

Table 5-3 Indicator status 

LED 

Status 

Rectifier indicator 

Green 

Battery indicator 

Green 

Bypass indicator 

Off 

Inverter indicator 

Green 

Load indicator 

Green 

Load indicator 

Green 

5.2.2 Battery Module Start 

Only Applicable for the UPS with Battery Cold Start Elements

 

1.  Check if the batteries have been connected, close the external battery switch.   

2.  Press the red start-up button of battery on the back door panel. 

3.    The LCD starts up at this time, press battery cold start again for about 5 seconds. The green battery 

indicator flashes. The rectifier  enters  normal  operation states and  after  about 30s,  the battery indicator 

goes steady green. 

4.    The inverter starts up automatically, the green inverter indicator flashes. The inverter will output after 

60s. Then UPS run in battery mode. 

 

b. 10KVA~30KVA   

Fig. 5-2 diagrammatic drawing for battery starting button location 

5.3 Procedure for Switching between Operation Modes 

5.3.1 Procedure for Switching the UPS into Battery from Normal Mode 

Open input switch to cut off the mains, UPS enters the battery mode. If UPS should be switched to 

normal mode, wait for a few seconds before closing input switch, so as to supply the mains again. 10s 

later, the rectifier will start up automatically to supply power to the inverter. 

5.3.2 Procedure for Switching the UPS into Bypass from Normal Mode 

Select the manual bypass menu of "function 1” of “function/ setting” 

 

  Note 

In bypass mode, the load is directly fed by the mains power instead of the pure AC power from the 

inverter.

 

 

-

36

NS3000 Series User Manual    rev.01 

5.3.3 Procedure for Switching the UPS into Normal from Bypass Mode 

Select  “exit  bypass  mode”  on  the  LCD,  about  3  seconds  later,  UPS  transfer  to  inverter  mode 

automatically. 

5.3.4 Procedure for Switching the UPS into a Maintenance Bypass from Normal Mode 

In normal operation, this operation instruction will switch the load from inverted input to maintenance 

bypass. 

  Caution 

Before making this operation, read messages on display to be sure that bypass supply is regular and 

the inverter is synchronous with it, so as not to risk a short interruption in powering the load.

 

1. Switch UPS from normal mode to bypass mode according to 5.3.2.   

The inverter indicator and status indicator go off, the buzzer alarms. The load will be transferred to 

static bypass, and the inverter is closed. 

2. Remove anti-misoperation stop plate for rotary air switch, then the rotary air switch is switched to the 

maintenance bypass side in order that the load power supply is supplied by the maintenance bypass Q3, 

and the mains switch Q1, the bypass switch Q2, the output switch    Q3-2    and the internal and external 

battery switches are disconnected.   

  Warning 

If it is required to mainten the modules, the cabinet is opened for internal maitenance after waiting for 

5

 minutes in order that the capacitor voltage in the internal DC bus automatically dischages.   

5.3.5 Procedure for Switching the UPS into Normal from a Maintenance Bypass Mode 

This  procedure  can  transfer  the  load  to  normal  main  mode  when  the  UPS  is  operating  under  the 

maintenance bypass mode. 

1. 

Close the bypass switch Q2 and switch the rotary switch to “UPS output” side. 

The  indicator  light  of  the  bypass  become  green  and  the  power  is  supplied  for  the  load  by  the 

bypass.   

2. 

Close the mains input air switch Q1   

The power is supplied for the load by the bypass. At the same time, the rectifier begins to operate, 

the  indicator  light  of  the  rectifier  become  green  after  30  seconds,  and  the  power  is  automatically 

supplied with the inverter after 2 minutes.   

3. 

Close  internal  and  external  battery  switches.  If  the  indicator  light  of  the  battery  does  not  work, 

please confirm the voltage of the LCD display battery is normal. 

4. 

Replace the anti-misoperation stop plate for rotary switch.   

5.4 Procedure for Completely Powering down a UPS 

If you need to power down the UPS completely, follow the procedures in section 5.3.4 to transfer the 

UPS from normal mode to maintenance bypass mode. 

If you need to isolate the UPS from the AC power supply, you should open the external input switch. 

 

 

 

Содержание NS3000 10 kVA

Страница 1: ...1 NS3000 Series User Manual Rev 01 UPS NS3000 10 20 30kVA USER Manual 2 NS3000 Series User Manual Rev 01...

Страница 2: ...te the static switch if excessive voltage is present at the bypass input when the bypass source is deenergized If this function is not installed and enabled there must be a warning label on the extern...

Страница 3: ...al rev 01 3 2 3 Auto Restart Mode 29 3 2 4 Bypass Mode 29 3 2 5 Maintenance Mode 29 3 2 6 ECO Mode 29 3 2 7 Frequency Converters Mode 29 3 2 8 Parallel connection redundancy mode 30 3 3 Battery Manage...

Страница 4: ...s any mistake for accessories contact with shipper or provider 1 3 Environment Checking Before installing UPS please check these items as below 1 Is the UPS operation environment temperature above 25...

Страница 5: ...sary a system of extractor fans should be installed to aid cooling air flow An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain a...

Страница 6: ...l Against ambient corrosive gases l Against excessive humidity and heat sources l Against dust l With the current fire prevention requirements l The operating environment temperature is within 20 25...

Страница 7: ...supply the installed device should l Sensitive to DC Class B or class A in the network l Insensitive to transient current pulses l Have an average sensitivity that is adjustable between 0 3A 1A 14 NS3...

Страница 8: ...epartment After the equipment has been finally positioned and secured connect the power cables as described in the following procedures 1 Verify that all the external input distribution switches of th...

Страница 9: ...2 5 A Pay attention all cable are marked and have different color 6 Connect the battery according fig 2 5 A don t connect A and B cable in the shelf 1 7 In shelf 1 on the left connect the cable mark...

Страница 10: ...d be double insulated with a typical 0 5 to 1 5 mm 2 cross section area for a maximum connection length between 25 and 50 meters 2 6 1 Dry Contact Interface of Battery and Environmental Temperature De...

Страница 11: ...Note 1 The emergency stop action within the UPS will shut down the rectifier inverter and static bypass However it does not internally disconnect the mains input and batterypower supply To disconnect...

Страница 12: ...neral warning dry contact interface diagram Table 2 7 Position Name Purpose J9 1 ALARM_NC Integrated warning relay normally closed will be open during warning J9 2 ALARM_NO Integrated warning relay no...

Страница 13: ...25 NS3000 Series User Manual rev 01 2 7 Installation Diagram 26 NS3000 Series User Manual rev 01 a 10KVA 30KVA terminal block NS3030 NS3010 NS3020...

Страница 14: ...ss module can be removed for maintenance Fig 3 1 System principle framework 28 NS3000 Series User Manual rev 01 3 1 2 Bypass During normal system operation the load is connected to the inverter but in...

Страница 15: ...e output frequency The range of output frequency is 40Hz 70Hz Under this mode static bypass is unavailable but battery can be selected according to the actual requirements of battery mode Frequency Co...

Страница 16: ...4 1 Typical 1 N parallel operation system Note when the load exceeds the capacity of the single device we recommended an external manual Bypass The cables for the parallel operation provide double in...

Страница 17: ...Warning Please confirm that UPS output rotating switch point to UPS with anti misoperation stop plate for rotating switch is fixed well 1 Close UPS bypass input switch and input switch in turns The LC...

Страница 18: ...aution Before making this operation read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it so as not to risk a short interruption in powering the loa...

Страница 19: ...chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail and provides LCD display information including LCD display types detailed...

Страница 20: ...tus indicator Steady red Failure 6 1 2 Audible Alarm buzzer There are two different types of audible alarm during UPS operation as shown in table 6 3 Table 6 3 Description of audible alarm Alarm Purpo...

Страница 21: ...rface you can select each function and press ENTER press ENTER again it will display Confirm interface 6 2 5 State Display The alarm page as below press left and right arrow to select STA in homepage...

Страница 22: ...inverted power supply status Bypass power supply The system is in bypass power supply status No power supply System no output Battery equalized charging Battery is in boost charging Battery float char...

Страница 23: ...hows the power is normally supply by the bypass 8 Open maintenance bypass switch and close mains input switch the inverter automatically starts and UPS operates in the normal mode after 60 seconds 9 C...

Страница 24: ...harge V cell 2 4V cell selectable from 2 3V cell 2 45V cell Constant current and constant voltage charge mode Battery Charging Power Max Current kW 10 UPS capacity selectable from 0 20 UPS capacity NS...

Страница 25: ...eutral cable A 1 7 In Frequency2 Hz 50 60 Switch time between bypass and inverter ms Synchronized switch 1ms Bypass voltage tolerance Vac Upper limit 10 15 or 20 default 20 Lower limit 10 20 30 or 40...

Отзывы: