background image

-

29

NS3000 Series User Manual    rev.01 

3.2.1 Normal Mode 

The UPS inverter power modules continuously supply the critical AC load. The rectifier/charger derives power from 

the  AC  mains input source  and supplies  DC power to  the inverter  while simultaneously FLOAT  or  BOOST  charging its 

associated backup battery. 

3.2.2 Battery Mode 

Upon  failure  of  the  AC  mains  input  power;  the  inverter  power  modules,  which  obtains  power  from  the  battery, 

supplies the critical AC load. There is no interruption in power to the critical load upon failure. After restoration of the AC 

mains input power, the “Normal Mode” operation will continue automatically without the necessity of user intervention. 

Note:  UPS  can  also  be  started  through  battery  mode  via  battery  cold  start  function  upon  failure  of  the  AC  mains. 

Therefore, the battery power can be used independently to improve the utilization rate of UPS. 

3.2.3 Auto-Restart Mode 

The  battery  may  become  exhausted  following  an  extended  AC  mains  failure.  The  inverter  shuts  down  when  the 

battery reaches the End of Discharge voltage (EOD). The UPS may be programmed to “Auto Recovery after EOD” after 

a delay time if the AC main recovers. This mode and any delay time are programmed by the commissioning engineer. 

During the  process  of delay  time,  the battery  will  be  charged by UPS to prevent  any risks to load equipment  from 

future mains failure. 

3.2.4 Bypass Mode 

If  the  inverter  overload  capacity  is  exceeded  under  normal  mode,  or  if  the  inverter  becomes  unavailable  for  any 

reason,  the  static  transfer  switch  will  perform  a  transfer  of  the  load  from  the  inverter  to  the  bypass  source,  with  no 

interruption in power to the critical AC load. 

3.2.5 Maintenance Mode 

A  manual  bypass  switch  is  available  to  ensure  continuity  of  supply  to  the  critical  load  when  the  UPS  becomes 

unavailable e.g. during a maintenance procedure. 

It is noticed that after UPS system supplies the power with the bypass mode, the maintenance bypass rotary switch 

Q3, in this situation    is closed Q1, Q2, Q3-2 out put contacts and battery switches are disconnected.   

  Warning: Hazard may occur after transferring to maintenance bypass 

After UPS being transferred to maintenance bypass, UPS battery, input and output terminals and are 

charged.

 

3.2.6 ECO Mode 

If economical (ECO) mode is selected, the double-conversion UPS will stop to work so as to save energy. During the 

operation of ECO mode, the load power will be supplied by bypass preferentially. When bypass power is within the range 

of  normal  frequency  and  voltage, load  power  will  be supplied  by  bypass,  or  the  system  will  transfer  to  inverter  output, 

followed  by  load  power  interruption  which  extends  within  3/4  of  the  period.  E.g.  when  the  frequency  is  50Hz,  the 

interruption time will be less than 15ms; when the frequency is 60Hz, the time will be less than 12.5ms. 

Eco mode have to set by customer service 

 

3.2.7 Frequency Converters Mode 

If the frequency  converter  configuration is  used by UPS, it will  provide 50Hz  or  60Hz stable output frequency. The 

range  of  output  frequency  is  40Hz-70Hz.  Under  this  mode,  static  bypass  is  unavailable,  but  battery  can  be  selected 

according to the actual requirements of battery mode. 

Frequency Converte Mode have to set by customer service 

-

30

NS3000 Series User Manual    rev.01 

3.2.8 Parallel connection redundancy mode   

  Several  UPS  devices  may  be  parallel  connected  directly  and  the  parallel  operation  control  logic  in  single  UPS 

devices ensures all single device automatically share the load to improve the capacity or reliability of the system, or both 

the capacity and reliability of the system. The capacity of a parallel operation system can be up to 6 units. 

3.3 Battery Management 

3.3.1 Normal Function 

The following functions should be fitted by commissioning engineers with specified software. 

1. 

Constant current boost charging 

Current can be set up   

2. 

Constant voltage boost charging 

Voltage of boost charging can be set as required by the type of battery. 

For Valve Regulated Lead Acid (VRLA) batteries, maximum boost charge voltage should not exceed 2.4V / cell. 

3. 

Float charge 

Voltage of float charging can be set as required by the type of battery. 

For VRLA, float charge voltage should be between 2.2V to 2.3V. 

4. 

Float charge temperature compensation (optional)   

A coefficient of temperature compensation can be set as required by the type of battery. 

5. 

End of discharge (EOD) protection. 

If the battery voltage is lower than the EOD, the battery converter will shut down and the battery is isolated to avoid 

further battery discharge. EOD is adjustable from 1.6V to 1.75V per cell (VRLA) or 0.9 to 1.1 V per cell   

6. 

Battery low warning time 

It is adjustable between 3 and 60 minutes. The default is 5 minutes. 

3.3.2 Advanced Functions (Battery Self-checking and Maintenance) 

At  periodic intervals,  20%  of  the rated capacity of  the  battery  will be discharged automatically, and the  actual load 

must exceed 20% of the rated UPS (KVA) capacity. If the load is less than 20%, auto-discharge cannot be executed. The 

periodic interval can be set from 30 to 360 days. The battery self-test can be disabled. 

Conditions—Battery at float charge for at least 5 hours, load equal to 20~100% of rated UPS capacity 

Trigger—Manually through the command of “Battery Maintenance Test” in LCD panel or automatically 

3.4 Battery Protection 

The following functions should be fitted by commissioning engineers with specified software. 

1. 

Battery Low Pre-warning 

The battery undervoltage pre-warning occurs before the end of discharge. After this pre-warning, the battery should 

have the capacity for 3 remaining minutes discharging with full load. The time is user configured from 3 to 60 minutes. 

2. 

Battery discharge (EOD)off protection   

If the battery voltage is lower than the EOD, the battery converter will be shut down. EOD is adjustable from 1.6V to 

1.75V per cell (VRLA) or 0.9 to 1.1 V per cell (NiCd)   

3. 

Battery Circuit Breaker (BCB) Alarm (Optional) 

The  alarm  occurs  when  the  battery  disconnect  device  disconnects.  The  external  battery  connects  to  the  UPS 

through the external battery circuit breaker. The circuit breaker is manually closed and tripped by the UPS control circuit. 

See relay    card optionals 

 

Содержание NS3000 10 kVA

Страница 1: ...1 NS3000 Series User Manual Rev 01 UPS NS3000 10 20 30kVA USER Manual 2 NS3000 Series User Manual Rev 01...

Страница 2: ...te the static switch if excessive voltage is present at the bypass input when the bypass source is deenergized If this function is not installed and enabled there must be a warning label on the extern...

Страница 3: ...al rev 01 3 2 3 Auto Restart Mode 29 3 2 4 Bypass Mode 29 3 2 5 Maintenance Mode 29 3 2 6 ECO Mode 29 3 2 7 Frequency Converters Mode 29 3 2 8 Parallel connection redundancy mode 30 3 3 Battery Manage...

Страница 4: ...s any mistake for accessories contact with shipper or provider 1 3 Environment Checking Before installing UPS please check these items as below 1 Is the UPS operation environment temperature above 25...

Страница 5: ...sary a system of extractor fans should be installed to aid cooling air flow An air filter should be used when the UPS is to operate in a dirty environment and should be regularly cleaned to maintain a...

Страница 6: ...l Against ambient corrosive gases l Against excessive humidity and heat sources l Against dust l With the current fire prevention requirements l The operating environment temperature is within 20 25...

Страница 7: ...supply the installed device should l Sensitive to DC Class B or class A in the network l Insensitive to transient current pulses l Have an average sensitivity that is adjustable between 0 3A 1A 14 NS3...

Страница 8: ...epartment After the equipment has been finally positioned and secured connect the power cables as described in the following procedures 1 Verify that all the external input distribution switches of th...

Страница 9: ...2 5 A Pay attention all cable are marked and have different color 6 Connect the battery according fig 2 5 A don t connect A and B cable in the shelf 1 7 In shelf 1 on the left connect the cable mark...

Страница 10: ...d be double insulated with a typical 0 5 to 1 5 mm 2 cross section area for a maximum connection length between 25 and 50 meters 2 6 1 Dry Contact Interface of Battery and Environmental Temperature De...

Страница 11: ...Note 1 The emergency stop action within the UPS will shut down the rectifier inverter and static bypass However it does not internally disconnect the mains input and batterypower supply To disconnect...

Страница 12: ...neral warning dry contact interface diagram Table 2 7 Position Name Purpose J9 1 ALARM_NC Integrated warning relay normally closed will be open during warning J9 2 ALARM_NO Integrated warning relay no...

Страница 13: ...25 NS3000 Series User Manual rev 01 2 7 Installation Diagram 26 NS3000 Series User Manual rev 01 a 10KVA 30KVA terminal block NS3030 NS3010 NS3020...

Страница 14: ...ss module can be removed for maintenance Fig 3 1 System principle framework 28 NS3000 Series User Manual rev 01 3 1 2 Bypass During normal system operation the load is connected to the inverter but in...

Страница 15: ...e output frequency The range of output frequency is 40Hz 70Hz Under this mode static bypass is unavailable but battery can be selected according to the actual requirements of battery mode Frequency Co...

Страница 16: ...4 1 Typical 1 N parallel operation system Note when the load exceeds the capacity of the single device we recommended an external manual Bypass The cables for the parallel operation provide double in...

Страница 17: ...Warning Please confirm that UPS output rotating switch point to UPS with anti misoperation stop plate for rotating switch is fixed well 1 Close UPS bypass input switch and input switch in turns The LC...

Страница 18: ...aution Before making this operation read messages on display to be sure that bypass supply is regular and the inverter is synchronous with it so as not to risk a short interruption in powering the loa...

Страница 19: ...chapter introduces the functions and operation instructions of the parts on UPS operator control and display panel in detail and provides LCD display information including LCD display types detailed...

Страница 20: ...tus indicator Steady red Failure 6 1 2 Audible Alarm buzzer There are two different types of audible alarm during UPS operation as shown in table 6 3 Table 6 3 Description of audible alarm Alarm Purpo...

Страница 21: ...rface you can select each function and press ENTER press ENTER again it will display Confirm interface 6 2 5 State Display The alarm page as below press left and right arrow to select STA in homepage...

Страница 22: ...inverted power supply status Bypass power supply The system is in bypass power supply status No power supply System no output Battery equalized charging Battery is in boost charging Battery float char...

Страница 23: ...hows the power is normally supply by the bypass 8 Open maintenance bypass switch and close mains input switch the inverter automatically starts and UPS operates in the normal mode after 60 seconds 9 C...

Страница 24: ...harge V cell 2 4V cell selectable from 2 3V cell 2 45V cell Constant current and constant voltage charge mode Battery Charging Power Max Current kW 10 UPS capacity selectable from 0 20 UPS capacity NS...

Страница 25: ...eutral cable A 1 7 In Frequency2 Hz 50 60 Switch time between bypass and inverter ms Synchronized switch 1ms Bypass voltage tolerance Vac Upper limit 10 15 or 20 default 20 Lower limit 10 20 30 or 40...

Отзывы: