![GSi Protek PD Series Скачать руководство пользователя страница 88](http://html1.mh-extra.com/html/gsi/protek-pd-series/protek-pd-series_user-manual_2275134088.webp)
CHAPTER 12 SPECIFICATION
88
Overvoltage / Overcurrent
Protection
0 ~ 110% of rated voltage ; 0 ~ 110% of rated current
Power Factor (PF)
0.99 (at 115VAC, rated output)
Withstand voltage
Input-Output - AC2000V:1 minute
Input-Ground - AC2000V:1 minute
Cooling
Forced air by speed controlled fan
Noise
<70 dB(A)
Weight
1UH type : approx. 5.1 kg
1U type : approx. 9.0 kg
2UH type : approx. 8.2 kg
2U type : approx. 15.1 kg
Operating environment
Temperature : 0~40°C (for 750W series models)
0~50°C (for 1500W and 3000W series models)
Humidity: 30%~90% relative humidity (no condensation)
Storage environment
Temperature: -20~70°C;
Humidity: 10%~90% relative humidity (no condensation)
EMC Standard
EN 61326-1:2006
EMC Emissions
(EN 61326-1)
EN 55011:2007 +A2:2007, (group 1, class B)
EN 61000-3-2:2006
EN 61000-3-3:2008
EMC lmmunity
(EN 61326-1)
EN 61000-4-2:2009
EN 61000-4-3:2006 + A1:2008 + A2:2010
EN 61000-4-4:2004 + A1:2010
EN 61000-4-5:2006
EN 61000-4-6:2009
EN 61000-4-11:2004
Low Voltage Drective
2006/95/EC
IEC 61010-1:2010(3
rd
Edition)
Vibration Test
ISTA 2A
Drop Test
JIS Z 0200
Note 1. Programming time = Command response time + Output response time. Different models may have different
output response time, from 30ms ~ 200ms.