5.1.1 Collecting tank

The gas-, odour- and pressure-tight collecting tank is made of 
wastewater resistant polyethylene (PE) and has all necessary 
ports for the connection of inlet pipes, discharge pipe, venting 
pipe and a manually operated diaphragm pump, which is 
available as an accessory. 

The MD collecting tank

 has a turnable, eccentric disk in the 

back allowing adjustment of the inlet to any height between 180 
and 315 mm above the floor. The most common heights are 
marked beside the inlet. See section 

7.3 Procedure for 

installation of lifting station

Furthermore, the MD collecting tank offers four horizontal inlets in 
the sides (2 x DN 100 and 2 x DN 50) and three vertical inlets at 
the top of the tank (2 x DN 150 and 1 x DN 50). The centres of the 
horizontal inlets are 120 mm (DN 50) and 250 mm (DN 150) 
above the floor. 
The side and back inlets 180 and 250 mm above the floor are for 
direct connection to wall-hung or floor-standing toilet according to 
EN 33 and EN 37. Further sanitary appliances can be connected 
to the other ports.

The MLD collecting tank

 offers one vertical inlet, DN 50, at the 

top of the tank and one vertical inlet, DN 150, in the stepped part 
of the tank.
The tank volume and effective volume (volume between start and 
stop) for Multilift MD and MLD lifting stations appear from the 
following table:

Setting to the relevant start inlet level must be made during the 
start-up phase via the setup menu. See section 

6.2 Setup menu

.

The first step after power supply connection is a start-up phase 
with level setting.
To minimise sedimentation, the tank bottom is chamfered to lead 
the wastewater to the pump.

5.1.2 Pumps

The pump impellers are designed as free-flow vortex impellers, 
ensuring almost unchanged performance throughout the entire 
life of the pump. The stator housing of the motor is made of cast 
iron. The pump has a mechanical shaft seal.
See more technical data in section 

12. Technical data

.

Single-phase motors are protected by a thermal switch in the 
windings and run via a capacitor inside the controller cabinet.
Three-phase motors are protected by a thermal switch in the 
windings and an additional thermal circuit breaker in the cabinet 
of Multilift MD/MLD22, 24, 32 and 38 to cut out the motor in case 
of overload.
If the phase sequence for three-phase pumps is wrong, the 
controller will indicate fault and prevent the pump(s) from starting. 
For correction of phase sequence, see fig. 

14

. For direction of 

rotation, see section 

10.2 Motor

.

Performance curves are available in the databooklet, which you 
can download via the QR code or link below:

5.1.3 Shaft seal

The pumps have three shaft seals, the oil chambers in between are 
filled for life and therefore require no maintenance. 
For replacement in case of service, please see service 
instructions.

5.1.4 Motor cable

The motor cable is fitted to the motor via a cable entry. 
The enclosure class is IP68. The length of the cable is either 4 m 
or 10 m.

Nameplate, motor

Fig. 4

Nameplate, motor

MD

Inlet level [mm]

180

250

315

Total tank volume [l]

130

Effective tank volume [l]

49

69

86

MLD

Inlet level [mm]

560

Total tank volume [l]

270

Effective tank volume [l]

190

Note

If the motor is overloaded, it will stop automatically.
When it has cooled to normal temperature, it will 
restart automatically.

http://net.grundfos.com/qr/i/98288126

TM

03

 36

18

 05

06

Pos.

Description

1

Product number and model

2

Production code (year/week)

3

Frequency

4

Number of phases

5

Rated voltage

6

Rated current

7

Input power

8

Shaft power

9

Serial number

10

Operating mode

11

Power factor

12

Rated speed

13

Insulation class

14

Weight

15

Production country

DK - 8850 Bjerringbro, Denmark

1217

001

98189706 - A

0.77

S3-40%-1min

1405

F

24

50

3

400

5.3

2.8

2.2

Phases

f

U

P.c.

Prod.-Nr.

I

1/1

P

1

P

2

kg

IP68

98189706

Made in Germany

kW

A

V

Hz

n

G

Serial no.

min

-1

1

2

3

4

5

6
7

8

9

10

11

12

13

14

15

Содержание Multifit MD Series

Страница 1: ...Multilift MD MLD Installation and operating instructions GRUNDFOS INSTRUCTIONS Other languages http net grundfos com qr i 98127059...

Страница 2: ...clamps DN 50 for diaphragm pump connection or inlet DN 50 1 x gasket kit DN 80 4 bolts M16 nuts and washers galvanized 1 Symbols used in this document 2 2 Scope of delivery 2 2 1 MD 2 2 2 MLD 2 3 Gene...

Страница 3: ...pening 6 Vertical inlet DN 150 seal is accessory 7 Fixing point 8 Non return butterfly valve DN 80 with inspection cover and drain screw to lift up the valve flap 9 Discharge adapter flange DN 80 to p...

Страница 4: ...ong period of storage the pumps must be inspected before they are started up again Make sure that the impellers can rotate freely 5 Product description The MD and MLD Multilift lifting stations are de...

Страница 5: ...or is made of cast iron The pump has a mechanical shaft seal See more technical data in section 12 Technical data Single phase motors are protected by a thermal switch in the windings and run via a ca...

Страница 6: ...vel sensor When the first start level is reached the first pump will start and when the liquid level has been lowered to the stop level the pump will be stopped by the controller If the liquid level r...

Страница 7: ...water pipe burst an alarm will be indicated by the controller connecting a piezoresistive pressure sensor PCB pre assembled connecting an external alarm reset connecting the thermal switch of the moto...

Страница 8: ...in section 6 1 Description of display Operating buttons pos 2 The level controller is operated by the operating buttons placed under the display The functions of the operating buttons are described in...

Страница 9: ...free changeover NO NC contacts with max 250 V 2 A Attention Connect these terminals to supply network potential or low voltage but do not mix the two X11 9 Terminals for high water level alarm X10 10...

Страница 10: ...ible if the level controller detects a fault and the fault will be written into the fault log After you have entered the fault log the symbol will switch off See section 6 3 Information menu Setup The...

Страница 11: ...pump 1 The symbol is visible when pump 1 is running and flashes when pump 1 has a fault In case of fault it can be combined with other symbols or fault codes in the display Pump operation and pump fa...

Страница 12: ...sing the button Enter values or select settings from a list by means of the buttons and Save the settings by pressing the button See also fig 12 The following settings can be made start level rated cu...

Страница 13: ...enu by means of the buttons and Select the desired menu item by pressing the button See also fig 13 In the information menu the following data can be read fault indications operating hours number of s...

Страница 14: ...is functioning A leaky non return valve can allow liquid in the outlet pipe to flow back in to the collecting tank Remove any blockage from the venting system see fig 33 F012 Operating time exceeded...

Страница 15: ...button The fault indication will be reset when the fault has disappeared has been removed or the ON OFF AUTO switch has been set to OFF position You can get an overview of faults in the fault log in i...

Страница 16: ...g 15 Installation sketch Multilift MD Fig 16 Installation sketch Multilift MLD TM05 1864 3811 4 7 2 1 6 5 3 TM05 1865 3811 3 4 6 5 Pos Accessories Product number 1 Socket seal DN 100 97726942 2 Socket...

Страница 17: ...ves accessory must be placed outside the building If the wastewater is discharged into a collecting line this collecting line must have a filling ratio of at least h d 0 7 The collecting line must be...

Страница 18: ...et pipe and lifting station to avoid inflow during maintenance and service We recommend an easy to handle PVC isolating valve Fig 22 Installation of isolating valve TM05 0336 1011 Caution Multilift MD...

Страница 19: ...n the discharge side To facilitate servicing of the diaphragm pump we recommend fitting a 1 1 2 isolating valve to the tank port 4 Fix the tank to the floor Fig 25 Fixing point for fixation of tank to...

Страница 20: ...ts for lifting stations except on a houseboat or pontoon boat The preset value is 0 Alarm delay High temporary inflow can cause short time high level alarm This situation may arise when a backwash fil...

Страница 21: ...diagram three phase Multilift MD MLD 12 3 4 and MD MLD 15 3 4 Fig 29 Wiring diagram three phase Multilift MD MLD 22 3 4 with contactors Fig 30 Wiring diagram three phase Multilift MD MLD 24 3 2 MD ML...

Страница 22: ...hat the cable entry is watertight and that the cables are not bent sharply and or pinched Pump parts Remove eight screws and dismantle the pump from the tank and check that the vent hole of the pump h...

Страница 23: ...Lifting eye Fig 32 Top of slotted motor shaft Fig 33 Vent holes in pump housing and collecting tank Fig 34 Alignment marks on tank and pump flange 10 3 Electrical maintenance Check the gasket of the L...

Страница 24: ...ift MD MLD Fig 35 Removing the level sensor 10 5 Contaminated lifting station or components If Grundfos is requested to service the lifting station Grundfos must be contacted with details about the pu...

Страница 25: ...range All pumps are started and high level alarm is on a Discharge valves are not all opened Open all discharge isolating valves b There is a blockage in the tank or pump Remove blockage c The pump v...

Страница 26: ...ngs NBR rubber Controller Voltage variants rated voltages 1 x 230 V 3 x 230 V 3 x 400 V Voltage tolerances for LC 221 10 6 of rated voltage Mains frequency for LC 221 50 60 Hz Supply system earthing F...

Страница 27: ...Appendix 27 Appendix 1 Fig A Dimensional sketches MD TM05 0441 1011...

Страница 28: ...Appendix 28 Fig B Dimensional sketches MLD TM05 0442 1011...

Страница 29: ...53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava b...

Страница 30: ...splayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2018 Grundfos Holding A...

Отзывы: