6.4 Description of fault indications

If a fault occurs, the symbol 

 will be visible, an audible alarm will be given by the buzzer and the fault code will be written by means of 

the 14-segment characters in the display. To see the kind of fault, if it is automatically reset and the code is not longer visible, open the 
fault log (see fig. 

13

). When you leave the fault log, the symbol 

 will disappear.

The last 20 faults are stored in the fault log as fault codes. The meaning of the fault codes are described in the table below:

Fault 

code

Meaning

Displayed 

text

Flashing 

symbols

Reset of 

fault 

indications Description

Auto Man

F001

Phase sequence 
failure

F001

(Only three-phase pumps)
The phase sequence between control board and power supply is 
wrong. See fig. 

14

.

F002

One phase 
missing

F002

(Only three-phase pumps)
One phase is missing.

F003

High liquid level

F003

The liquid level is high in relation to preset value.

F004

Sensor failure

SENSOR

-

Sensor signal out of range or lost.

F005

Overtemperature, 
pump 1

TEMP

Motor thermal switches connected to the controller will stop pump 1 
in case of overheating.

F006

Overtemperature, 
pump 2

TEMP

Motor thermal switches connected to the controller will stop pump 2 
in case of overheating.

F007

Overcurrent, 
pump 1

F007

Pump 1 is stopped if an overcurrent is measured for a certain period 
of time (blockage protection).

F008

Overcurrent, 
pump 2

F008

Pump 2 is stopped if an overcurrent is measured for a certain period 
of time (blockage protection).

F011

Operating time 
exceeded, pump 
1

F011

The pump has run for more than the allowed operating time and the 
controller has stopped the pump for a defined cool-down period in 
order to prevent overheating. The operating time and cool down 
period depends on the pump. See duty type on nameplate.
Check that the outlet isolating valve is open.
Check that the non-return valve is functioning. A leaky non-return 
valve can allow liquid in the outlet pipe to flow back in to the 
collecting tank.
Remove any blockage from the venting system, see fig. 

33

.

F012

Operating time 
exceeded, pump 
2

F012

F013

External fault

EXT

-

An external level switch can be connected to the controller to give 
an alarm when basement outside the lifting station is flooded by 
groundwater or water from burst water pipe.

F014

Battery failure

BAT

-

The battery is empty and must be replaced.

F015

Relay or 
contactor does 
not open, pump 1

RELAY

Pump 1 receives a signal to stop, but does not react. This situation 
is detected by current measurement.

F016

Relay or 
contactor does 
not close, pump 1

RELAY

Pump 1 receives a signal to start, but does not react. This situation 
is detected by current measurement.

F017

Relay or 
contactor does 
not open, pump 2

RELAY

Pump 2 receives a signal to stop, but does not react. This situation 
is detected by current measurement.

F018

Relay or 
contactor does 
not close, pump 2

RELAY

Pump 2 receives a signal to start, but does not react. This situation 
is detected by current measurement.

F019

Display 
communication 
failure

Display is 

off.

Communication failure between the main board and the display. As 
the display is off, the fault code can be found via PC tool only. 
Check the patch cable RJ45 between the main board and the 
display.

F117

F117

Communication failure between the main board and the display. 
The display is still on and is displaying the fault code F117. Check 
the patch cable RJ45 between the main board and the display.

F020

High level alarm 
in tank

F020

Alarm triggered by the additional float switch inside the tank. The 
piezoresistive sensor has failed to detect the start level. The float 
switch is triggered and starts a pump for 20 seconds (preset value, 
changeable via PC tool).
Check the tank, the level sensor hose and the hose connections for 
any air leakage.
The level sensor hose is connected correctly to the pneumatic 
coupling underneath the controller when you cannot pull it out 
without pressing the locking mechanism.

Содержание Multifit MD Series

Страница 1: ...Multilift MD MLD Installation and operating instructions GRUNDFOS INSTRUCTIONS Other languages http net grundfos com qr i 98127059...

Страница 2: ...clamps DN 50 for diaphragm pump connection or inlet DN 50 1 x gasket kit DN 80 4 bolts M16 nuts and washers galvanized 1 Symbols used in this document 2 2 Scope of delivery 2 2 1 MD 2 2 2 MLD 2 3 Gene...

Страница 3: ...pening 6 Vertical inlet DN 150 seal is accessory 7 Fixing point 8 Non return butterfly valve DN 80 with inspection cover and drain screw to lift up the valve flap 9 Discharge adapter flange DN 80 to p...

Страница 4: ...ong period of storage the pumps must be inspected before they are started up again Make sure that the impellers can rotate freely 5 Product description The MD and MLD Multilift lifting stations are de...

Страница 5: ...or is made of cast iron The pump has a mechanical shaft seal See more technical data in section 12 Technical data Single phase motors are protected by a thermal switch in the windings and run via a ca...

Страница 6: ...vel sensor When the first start level is reached the first pump will start and when the liquid level has been lowered to the stop level the pump will be stopped by the controller If the liquid level r...

Страница 7: ...water pipe burst an alarm will be indicated by the controller connecting a piezoresistive pressure sensor PCB pre assembled connecting an external alarm reset connecting the thermal switch of the moto...

Страница 8: ...in section 6 1 Description of display Operating buttons pos 2 The level controller is operated by the operating buttons placed under the display The functions of the operating buttons are described in...

Страница 9: ...free changeover NO NC contacts with max 250 V 2 A Attention Connect these terminals to supply network potential or low voltage but do not mix the two X11 9 Terminals for high water level alarm X10 10...

Страница 10: ...ible if the level controller detects a fault and the fault will be written into the fault log After you have entered the fault log the symbol will switch off See section 6 3 Information menu Setup The...

Страница 11: ...pump 1 The symbol is visible when pump 1 is running and flashes when pump 1 has a fault In case of fault it can be combined with other symbols or fault codes in the display Pump operation and pump fa...

Страница 12: ...sing the button Enter values or select settings from a list by means of the buttons and Save the settings by pressing the button See also fig 12 The following settings can be made start level rated cu...

Страница 13: ...enu by means of the buttons and Select the desired menu item by pressing the button See also fig 13 In the information menu the following data can be read fault indications operating hours number of s...

Страница 14: ...is functioning A leaky non return valve can allow liquid in the outlet pipe to flow back in to the collecting tank Remove any blockage from the venting system see fig 33 F012 Operating time exceeded...

Страница 15: ...button The fault indication will be reset when the fault has disappeared has been removed or the ON OFF AUTO switch has been set to OFF position You can get an overview of faults in the fault log in i...

Страница 16: ...g 15 Installation sketch Multilift MD Fig 16 Installation sketch Multilift MLD TM05 1864 3811 4 7 2 1 6 5 3 TM05 1865 3811 3 4 6 5 Pos Accessories Product number 1 Socket seal DN 100 97726942 2 Socket...

Страница 17: ...ves accessory must be placed outside the building If the wastewater is discharged into a collecting line this collecting line must have a filling ratio of at least h d 0 7 The collecting line must be...

Страница 18: ...et pipe and lifting station to avoid inflow during maintenance and service We recommend an easy to handle PVC isolating valve Fig 22 Installation of isolating valve TM05 0336 1011 Caution Multilift MD...

Страница 19: ...n the discharge side To facilitate servicing of the diaphragm pump we recommend fitting a 1 1 2 isolating valve to the tank port 4 Fix the tank to the floor Fig 25 Fixing point for fixation of tank to...

Страница 20: ...ts for lifting stations except on a houseboat or pontoon boat The preset value is 0 Alarm delay High temporary inflow can cause short time high level alarm This situation may arise when a backwash fil...

Страница 21: ...diagram three phase Multilift MD MLD 12 3 4 and MD MLD 15 3 4 Fig 29 Wiring diagram three phase Multilift MD MLD 22 3 4 with contactors Fig 30 Wiring diagram three phase Multilift MD MLD 24 3 2 MD ML...

Страница 22: ...hat the cable entry is watertight and that the cables are not bent sharply and or pinched Pump parts Remove eight screws and dismantle the pump from the tank and check that the vent hole of the pump h...

Страница 23: ...Lifting eye Fig 32 Top of slotted motor shaft Fig 33 Vent holes in pump housing and collecting tank Fig 34 Alignment marks on tank and pump flange 10 3 Electrical maintenance Check the gasket of the L...

Страница 24: ...ift MD MLD Fig 35 Removing the level sensor 10 5 Contaminated lifting station or components If Grundfos is requested to service the lifting station Grundfos must be contacted with details about the pu...

Страница 25: ...range All pumps are started and high level alarm is on a Discharge valves are not all opened Open all discharge isolating valves b There is a blockage in the tank or pump Remove blockage c The pump v...

Страница 26: ...ngs NBR rubber Controller Voltage variants rated voltages 1 x 230 V 3 x 230 V 3 x 400 V Voltage tolerances for LC 221 10 6 of rated voltage Mains frequency for LC 221 50 60 Hz Supply system earthing F...

Страница 27: ...Appendix 27 Appendix 1 Fig A Dimensional sketches MD TM05 0441 1011...

Страница 28: ...Appendix 28 Fig B Dimensional sketches MLD TM05 0442 1011...

Страница 29: ...53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava b...

Страница 30: ...splayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2018 Grundfos Holding A...

Отзывы: