9. Startup

Prior to start-up, the connection and settings must have been 
carried out according to sections 

8.3 Electrical connection

 and 

8.4 Setting of LC 221

.

Start-up must be carried out by authorised personnel.
Proceed as follows:
1. Check all connections.
2. Connect the plug to the power supply and follow the controller 

start-up sequence.

Note:

 It will take up to 45 seconds to boot the controller. 

This time can be reduced to 5 seconds by pressing the OK 
button. When the power supply is connected for the first time, 
three values for the start level can be chosen (180, 250 or 
315 mm above floor level) according to the inlet height to the 
collecting tank. If the inlet height is between two levels, 
choose the lower level for start in the display. All other 
settings are preset. Some settings can be changed. 
See section 

8.4 Setting of LC 221

. Now the controller is ready 

for automatic mode (selector switch in pos. AUTO).

3. Open the isolating valves in discharge and inlet lines.
4. Activate a sanitary appliance connected to the inflow of the 

Multilift MD or MLD and monitor the increasing liquid level in 
the tank up to the start level. Check the starts and stops at 
least twice.

10. Maintenance and service

The Multilift MD and MLD require a minimum of maintenance.

According to EN 12056-4 lifting stations must be checked at the 
following regular intervals:
• every 12 months in single-family houses
• every 6 months in multi-family dwellings
• every 3 months in commercial and industrial applications.
During the check, local regulations must be observed.
The periodic checks of the lifting station must be carried out by 
authorised personnel and must comprise electrical and 
mechanical maintenance. 
Check the following points:

Discharge and inlet connections

Check all connections to the lifting station for tightness and 
leakages. Make sure that weight from the inlet, discharge and 
venting pipes does not rest on the tank. Long pipe sections, 
valves, etc. must be supported.

Power consumption

See nameplate.

Cable entry

Make sure that the cable entry is watertight and that the 
cables are not bent sharply and/or pinched.

Pump parts

Remove eight screws and dismantle the pump from the tank 
and check that the vent hole of the pump housing is clear. 
When the pumps is mounted again, we recommend to replace 
the O-ring between pump and tank. Make a test run with clean 
water. In case of noise, vibration or abnormal running, contact 
Grundfos.

Ball bearings

Check the shaft for noisy or heavy operation. Replace defective 
ball bearings. A general overhaul of the pump is usually 
required in case of defective ball bearings or poor motor 
function. This work must be carried out by the manufacturer or 
an authorised service workshop.

Cleaning the non-return valve (if required)

Proceed as follows:
1. Close the isolating valves in the discharge pipe and in the 

inlet pipe (if fitted) or drain the discharge pipe by tightening 
the drain screw on the side of the non-return valve. See fig. 

5

.

2. Clean the non-return valve via its inspection cover. 

Replace the gasket of the inspection cover when 
reassembling the non-return valve. 

Warning
Before starting any work on a pump used for 
pumping liquids which could be hazardous to health, 
clean and vent the pump, pit, etc., thoroughly 
according to local regulations.

Warning
Before making any connections in LC 221 or working 
on pump, pit, etc., make sure that the power supply 
has been switched off and that it cannot be 
accidentally switched on.

Note

If the pump cable was disconnected from the 
controller, for instance to lead the cable through an 
empty cable conduit, check the direction of rotation 
of the pump.

 

See section 

10.2 Motor

.

Warning
Before carrying out maintenance and service on 
lifting stations used for pumping liquids which might 
be hazardous to health, make sure that the lifting 
station has been thoroughly flushed with clean water 
and that the discharge pipe has been drained. Rinse 
the parts in water after dismantling. Make sure that 
the isolating valves have been closed. The work 
must be carried out in accordance with local 
regulations.

Warning
Before making any connections in LC 221 or working 
on lifting stations, make sure that the power supply 
has been switched off and that it cannot be 
accidentally switched on.

Содержание Multifit MD Series

Страница 1: ...Multilift MD MLD Installation and operating instructions GRUNDFOS INSTRUCTIONS Other languages http net grundfos com qr i 98127059...

Страница 2: ...clamps DN 50 for diaphragm pump connection or inlet DN 50 1 x gasket kit DN 80 4 bolts M16 nuts and washers galvanized 1 Symbols used in this document 2 2 Scope of delivery 2 2 1 MD 2 2 2 MLD 2 3 Gene...

Страница 3: ...pening 6 Vertical inlet DN 150 seal is accessory 7 Fixing point 8 Non return butterfly valve DN 80 with inspection cover and drain screw to lift up the valve flap 9 Discharge adapter flange DN 80 to p...

Страница 4: ...ong period of storage the pumps must be inspected before they are started up again Make sure that the impellers can rotate freely 5 Product description The MD and MLD Multilift lifting stations are de...

Страница 5: ...or is made of cast iron The pump has a mechanical shaft seal See more technical data in section 12 Technical data Single phase motors are protected by a thermal switch in the windings and run via a ca...

Страница 6: ...vel sensor When the first start level is reached the first pump will start and when the liquid level has been lowered to the stop level the pump will be stopped by the controller If the liquid level r...

Страница 7: ...water pipe burst an alarm will be indicated by the controller connecting a piezoresistive pressure sensor PCB pre assembled connecting an external alarm reset connecting the thermal switch of the moto...

Страница 8: ...in section 6 1 Description of display Operating buttons pos 2 The level controller is operated by the operating buttons placed under the display The functions of the operating buttons are described in...

Страница 9: ...free changeover NO NC contacts with max 250 V 2 A Attention Connect these terminals to supply network potential or low voltage but do not mix the two X11 9 Terminals for high water level alarm X10 10...

Страница 10: ...ible if the level controller detects a fault and the fault will be written into the fault log After you have entered the fault log the symbol will switch off See section 6 3 Information menu Setup The...

Страница 11: ...pump 1 The symbol is visible when pump 1 is running and flashes when pump 1 has a fault In case of fault it can be combined with other symbols or fault codes in the display Pump operation and pump fa...

Страница 12: ...sing the button Enter values or select settings from a list by means of the buttons and Save the settings by pressing the button See also fig 12 The following settings can be made start level rated cu...

Страница 13: ...enu by means of the buttons and Select the desired menu item by pressing the button See also fig 13 In the information menu the following data can be read fault indications operating hours number of s...

Страница 14: ...is functioning A leaky non return valve can allow liquid in the outlet pipe to flow back in to the collecting tank Remove any blockage from the venting system see fig 33 F012 Operating time exceeded...

Страница 15: ...button The fault indication will be reset when the fault has disappeared has been removed or the ON OFF AUTO switch has been set to OFF position You can get an overview of faults in the fault log in i...

Страница 16: ...g 15 Installation sketch Multilift MD Fig 16 Installation sketch Multilift MLD TM05 1864 3811 4 7 2 1 6 5 3 TM05 1865 3811 3 4 6 5 Pos Accessories Product number 1 Socket seal DN 100 97726942 2 Socket...

Страница 17: ...ves accessory must be placed outside the building If the wastewater is discharged into a collecting line this collecting line must have a filling ratio of at least h d 0 7 The collecting line must be...

Страница 18: ...et pipe and lifting station to avoid inflow during maintenance and service We recommend an easy to handle PVC isolating valve Fig 22 Installation of isolating valve TM05 0336 1011 Caution Multilift MD...

Страница 19: ...n the discharge side To facilitate servicing of the diaphragm pump we recommend fitting a 1 1 2 isolating valve to the tank port 4 Fix the tank to the floor Fig 25 Fixing point for fixation of tank to...

Страница 20: ...ts for lifting stations except on a houseboat or pontoon boat The preset value is 0 Alarm delay High temporary inflow can cause short time high level alarm This situation may arise when a backwash fil...

Страница 21: ...diagram three phase Multilift MD MLD 12 3 4 and MD MLD 15 3 4 Fig 29 Wiring diagram three phase Multilift MD MLD 22 3 4 with contactors Fig 30 Wiring diagram three phase Multilift MD MLD 24 3 2 MD ML...

Страница 22: ...hat the cable entry is watertight and that the cables are not bent sharply and or pinched Pump parts Remove eight screws and dismantle the pump from the tank and check that the vent hole of the pump h...

Страница 23: ...Lifting eye Fig 32 Top of slotted motor shaft Fig 33 Vent holes in pump housing and collecting tank Fig 34 Alignment marks on tank and pump flange 10 3 Electrical maintenance Check the gasket of the L...

Страница 24: ...ift MD MLD Fig 35 Removing the level sensor 10 5 Contaminated lifting station or components If Grundfos is requested to service the lifting station Grundfos must be contacted with details about the pu...

Страница 25: ...range All pumps are started and high level alarm is on a Discharge valves are not all opened Open all discharge isolating valves b There is a blockage in the tank or pump Remove blockage c The pump v...

Страница 26: ...ngs NBR rubber Controller Voltage variants rated voltages 1 x 230 V 3 x 230 V 3 x 400 V Voltage tolerances for LC 221 10 6 of rated voltage Mains frequency for LC 221 50 60 Hz Supply system earthing F...

Страница 27: ...Appendix 27 Appendix 1 Fig A Dimensional sketches MD TM05 0441 1011...

Страница 28: ...Appendix 28 Fig B Dimensional sketches MLD TM05 0442 1011...

Страница 29: ...53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava b...

Страница 30: ...splayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2018 Grundfos Holding A...

Отзывы: