background image

English (GB)

25

11. Fault finding

Warning
Before carrying out any work on lifting stations used for pumping liquids which might be hazardous to health, make sure that 
the lifting station has been thoroughly flushed with clean water and that the discharge pipe has been drained. Rinse the parts 
in water after dismantling. Make sure that the isolating valves have been closed. The work must be carried out in accordance 
with local regulations.
Before making any connections in the LC 221 or work on lifting stations, etc., it must be ensured that the power supply has 
been switched off and that it cannot be accidentally switched on.

Fault

Cause

Remedy

1. The pump(s) 

does/do not run.

a) No power supply.

None of the indicator lights are on.

With battery back-up:

 

See section 

5.2 LC 221 controller

.

Switch on the power supply or wait until the power cut 
is over. During the power cut, drain the collecting tank 
with diaphragm pump.

b) The ON-OFF-AUTO selector switch is in position 

OFF ( ), see section 

6. Operating LC 221 

controller

.

Push the ON-OFF-AUTO selector switch into position 
ON ( ) or AUTO ( ).

c) Control circuit fuses are blown.

Check and eliminate the cause. Replace the control 
circuit fuses.

d) The motor-protective circuit breaker has cut out 

the pump (only relevant if a motor-protective 
circuit breaker has been installed). The pump 
symbol in the display is flashing and the red 
indicator light for fault is flashing. The fault 
indication in the display is RELAY and the fault 
code is F018.

Check the pump and tank as well as the setting of the 
motor-protective circuit breaker. If the pump is 
blocked, remove the blockage. If the setting of the 
motor-protective circuit breaker is wrong, readjust it 
(compare the setting with the nameplate).

e) Motor/supply cable is defective or the connections 

have become loose.

Check motor and supply cable. Replace cable or 
retighten connections if necessary.

f)

The fault indication in the display is SENSOR and 
in the fault code is F005 and/or F006.

Clean the level sensor (see section 

10.4 Cleaning the 

level sensor

), and start up again. Check the cable and 

the connection on the controller board. If the signal is 
still wrong, please call Grundfos service.

g) The module power circuit board or the LCD board 

is defective.

Replace the PCB or LCD board.

2. The sensor signal is 

out of range. 
All pumps are 
started and high 
level alarm is on.

a) Discharge valves are not all opened.

Open all discharge isolating valves.

b) There is a blockage in the tank or pump.

Remove blockage.

c) The pump venting is not working, which means 

that the pump cannot built pressure.

Remove blockage from the pump venting hole, 
located above the impeller.

d) The lifting station is undersized.

Recalculate the inflow parameters and compare with 
the size and pumping volume of the lifting station. 
Contact the nearest Grundfos sales company for 
ordering a new product if needed.

3. The pump(s) is/are 

starting/stopping 
too frequently and 
even if there is no 
inflow.

a) The level sensor fails. The sensor gives wrong 

signal.

Clean the level sensor 
(see section 

10.4 Cleaning the level sensor

).

b) The operating time protection is activated, the 

pump and time symbols are flashing, the red LED 
is flashing and the display indicates fault code 
F011 and/or F012. If the pump runs longer than 3 
minutes, a protection program of the controller will 
stop the pump for 3 minutes and the other pump 
will take over. At the next start impulse, the first 
pump will be activated again. If the venting 
problem persists, the pump will be stopped after 3 
minutes and so on.

Note:

 Normal operating times are up to 

60 seconds depending on duty point and effective 
tank volume.

Check that the discharge valve is open. Check the 
venting of the pump housing. If blocked clean the vent 
hole. See fig. 

33

.

c) The thermal switch has cut out the pump. The 

pump and thermal switch symbols on the display 
are flashing, and the red indicator light for fault is 
permanently on. The fault indication in the display 
is TEMP and in the fault code is F005 and/or 
F006.

Allow the pump to cool. After cooling, the pump will 
restart automatically unless the LC 221 has been set 
to manual restarting. See section 

8.4 Setting of LC 

221

. If so, the ON-OFF-AUTO selector switch must be 

pushed into position OFF ( ) for a short period.
Check the inflow parameters and the non-return valve.
The risk is low, but if the non-return valve flap is leaky, 
liquid in the discharge pipe can flow back.
A high number of starts without cooling time in 
between over a longer period can cause thermal 
cut-out. Consider S3 duty. See section 

12. Technical 

data

.

See also section 

10.4 Cleaning the level sensor

.

4. One pump starts 

sometimes without 
visible reason.

a) Test run 24 hours after last operation.

No action necessary. It is a safety function that 
prevents the shaft sealing from seizing up.

Содержание Multifit MD Series

Страница 1: ...Multilift MD MLD Installation and operating instructions GRUNDFOS INSTRUCTIONS Other languages http net grundfos com qr i 98127059...

Страница 2: ...clamps DN 50 for diaphragm pump connection or inlet DN 50 1 x gasket kit DN 80 4 bolts M16 nuts and washers galvanized 1 Symbols used in this document 2 2 Scope of delivery 2 2 1 MD 2 2 2 MLD 2 3 Gene...

Страница 3: ...pening 6 Vertical inlet DN 150 seal is accessory 7 Fixing point 8 Non return butterfly valve DN 80 with inspection cover and drain screw to lift up the valve flap 9 Discharge adapter flange DN 80 to p...

Страница 4: ...ong period of storage the pumps must be inspected before they are started up again Make sure that the impellers can rotate freely 5 Product description The MD and MLD Multilift lifting stations are de...

Страница 5: ...or is made of cast iron The pump has a mechanical shaft seal See more technical data in section 12 Technical data Single phase motors are protected by a thermal switch in the windings and run via a ca...

Страница 6: ...vel sensor When the first start level is reached the first pump will start and when the liquid level has been lowered to the stop level the pump will be stopped by the controller If the liquid level r...

Страница 7: ...water pipe burst an alarm will be indicated by the controller connecting a piezoresistive pressure sensor PCB pre assembled connecting an external alarm reset connecting the thermal switch of the moto...

Страница 8: ...in section 6 1 Description of display Operating buttons pos 2 The level controller is operated by the operating buttons placed under the display The functions of the operating buttons are described in...

Страница 9: ...free changeover NO NC contacts with max 250 V 2 A Attention Connect these terminals to supply network potential or low voltage but do not mix the two X11 9 Terminals for high water level alarm X10 10...

Страница 10: ...ible if the level controller detects a fault and the fault will be written into the fault log After you have entered the fault log the symbol will switch off See section 6 3 Information menu Setup The...

Страница 11: ...pump 1 The symbol is visible when pump 1 is running and flashes when pump 1 has a fault In case of fault it can be combined with other symbols or fault codes in the display Pump operation and pump fa...

Страница 12: ...sing the button Enter values or select settings from a list by means of the buttons and Save the settings by pressing the button See also fig 12 The following settings can be made start level rated cu...

Страница 13: ...enu by means of the buttons and Select the desired menu item by pressing the button See also fig 13 In the information menu the following data can be read fault indications operating hours number of s...

Страница 14: ...is functioning A leaky non return valve can allow liquid in the outlet pipe to flow back in to the collecting tank Remove any blockage from the venting system see fig 33 F012 Operating time exceeded...

Страница 15: ...button The fault indication will be reset when the fault has disappeared has been removed or the ON OFF AUTO switch has been set to OFF position You can get an overview of faults in the fault log in i...

Страница 16: ...g 15 Installation sketch Multilift MD Fig 16 Installation sketch Multilift MLD TM05 1864 3811 4 7 2 1 6 5 3 TM05 1865 3811 3 4 6 5 Pos Accessories Product number 1 Socket seal DN 100 97726942 2 Socket...

Страница 17: ...ves accessory must be placed outside the building If the wastewater is discharged into a collecting line this collecting line must have a filling ratio of at least h d 0 7 The collecting line must be...

Страница 18: ...et pipe and lifting station to avoid inflow during maintenance and service We recommend an easy to handle PVC isolating valve Fig 22 Installation of isolating valve TM05 0336 1011 Caution Multilift MD...

Страница 19: ...n the discharge side To facilitate servicing of the diaphragm pump we recommend fitting a 1 1 2 isolating valve to the tank port 4 Fix the tank to the floor Fig 25 Fixing point for fixation of tank to...

Страница 20: ...ts for lifting stations except on a houseboat or pontoon boat The preset value is 0 Alarm delay High temporary inflow can cause short time high level alarm This situation may arise when a backwash fil...

Страница 21: ...diagram three phase Multilift MD MLD 12 3 4 and MD MLD 15 3 4 Fig 29 Wiring diagram three phase Multilift MD MLD 22 3 4 with contactors Fig 30 Wiring diagram three phase Multilift MD MLD 24 3 2 MD ML...

Страница 22: ...hat the cable entry is watertight and that the cables are not bent sharply and or pinched Pump parts Remove eight screws and dismantle the pump from the tank and check that the vent hole of the pump h...

Страница 23: ...Lifting eye Fig 32 Top of slotted motor shaft Fig 33 Vent holes in pump housing and collecting tank Fig 34 Alignment marks on tank and pump flange 10 3 Electrical maintenance Check the gasket of the L...

Страница 24: ...ift MD MLD Fig 35 Removing the level sensor 10 5 Contaminated lifting station or components If Grundfos is requested to service the lifting station Grundfos must be contacted with details about the pu...

Страница 25: ...range All pumps are started and high level alarm is on a Discharge valves are not all opened Open all discharge isolating valves b There is a blockage in the tank or pump Remove blockage c The pump v...

Страница 26: ...ngs NBR rubber Controller Voltage variants rated voltages 1 x 230 V 3 x 230 V 3 x 400 V Voltage tolerances for LC 221 10 6 of rated voltage Mains frequency for LC 221 50 60 Hz Supply system earthing F...

Страница 27: ...Appendix 27 Appendix 1 Fig A Dimensional sketches MD TM05 0441 1011...

Страница 28: ...Appendix 28 Fig B Dimensional sketches MLD TM05 0442 1011...

Страница 29: ...53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava b...

Страница 30: ...splayed in this material including but not limited to Grundfos the Grundfos logo and be think innovate are registered trademarks owned by The Grundfos Group All rights reserved 2018 Grundfos Holding A...

Отзывы: