10. Factory settings
This section gives an overview of the factory settings for the
individual units and functions in the Dedicated Controls system.
Users can thus use this overview to reconfigure the system using
the factory settings. Users can also note their own settings in the
overview.
10.1 Pump
Description
Factory settings
Own settings
Pump 1
Installed
In operation
Contactor feedback
IO 11x not installed
MP 204 not installed
CUE/VFD not installed
Pump 2
Installed
In operation
Contactor feedback
IO 11x not installed
MP 204 not installed
CUE/VFD not installed
Pump 3
Installed
In operation
Contactor feedback
IO 11x not installed
MP 204 not installed
CUE/VFD not installed
Pump 4
Installed
In operation
Contactor feedback
IO 111 not installed
MP 204 not installed
CUE/VFD not installed
Pump 5
Installed
In operation
Contactor feedback
IO 11x not installed
MP 204 not installed
CUE/VFD not installed
Pump 6
Installed
In operation
Contactor feedback
IO 11x not installed
MP 204 not installed
CUE/VFD not installed
10.2 Pit
Description
Factory settings
Own settings
Pit depth
5.0 m
Upper measurement level
1.5 m
Lower measurement level
0.5 m
Volume (upper ↔ lower)
0.1 m
3
Max. measurement time
3600 s
Max. start-up delay
2 s
Start → start delay
2 s
Stop ← stop delay
2 s