![Grundfos CU 362 Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/grundfos/cu-362/cu-362_installation-and-operating-instructions-manual_2271080032.webp)
This ensures that the mixer operates before the pump starts.
Stop level, mixer
The stop level must be selected so that the mixer is submerged
during operation.
Start ratio, mixer
It must be set how often the mixer is to operate before the first
pump is started.
Max. runtime, mixer
The mixer stops at the end of its set operating period (minutes or
hours).
Mix while pumping
Tick the box in this field if the mixer is to operate when a pump
operates. The mixer stops when "Stop level, mixer" or "Max.
runtime, mixer" is reached.
If the box is not ticked, the mixer starts at "Start level, mixer" and
stops again when the first pump starts.
Mix on falling level only
The mixer starts only when the water level falls. If the water level
goes up again, the mixer does not start before the start level of the
mixer is reached again.
Path:
Settings > Advanced functions > Mixer configuration
TM077338
Mixer configuration
Related information
8.1.2 Pit configuration and flow calculation
8.2.5 Adjustment of counters
Counter values are set in this display. This is important for pump
replacement.
The following counters are available:
System
•
Operating hours
•
Parallel-operation time
•
Overflow time
•
Overflow volume
•
Number of overflows
•
Total volume
•
Energy
•
User-defined counter.
Pump 1 or Pump 2
•
Operating hours
•
Time since service
•
Number of starts
•
Average flow.
Mixer
Appears only if the mixer is enabled. See section about mixer
configuration.
•
Operating hours
•
Time since service
•
Number of starts.
GSM/GPRS (with inserted SIM card)
•
SMS messages sent
•
SMS messages received
•
GPRS data sent
•
GPRS data received
•
Outgoing calls
•
Incoming calls.
Example
A pump is taken out of operation when it reaches a total of 350
operating hours and a total of 700 starts. This is recorded in the
service log.
The pump is replaced by a reconditioned pump with a total of 250
operating hours and 800 starts. Enter these values, and the
system automatically continues counting the hours and starts from
this point.
Path:
Settings > Advanced functions > Adjustment of counters
4-2-5_ADJUST_COUNTERS_040
Adjustment of counters
Counter values are only stored into memory once per
hour. If counters are changed and a power cycle/reset is
done shortly afterwards, the changes may not be stored.
Related information
8.2.6 Resetting alarm log
In this display, the alarm log can be reset and it can be seen when it
was last reset.
Reset the alarm log, or see when it was last reset.
Path:
Settings > Advanced functions > Resetting alarm log
32
English (GB)