6. PROFINET IO, CIM 500 setup

6.1 Connecting the ethernet cable

Use RJ45 plugs and ethernet cable. Connect the cable shield to 
protective earth at both ends.

CIM 500 is designed for flexible network installation; the built-in 
two port switch makes it possible to daisy chain from product to 
product without the need of additional ethernet switches. The last 
product in the chain is only connected to one of the ethernet 
ports. Each ethernet port has its own MAC address.

Fig. 13

Example of Industrial Ethernet network

Fig. 14

Example of an ethernet connection, CIM 500

6.2 Setting the Industrial Ethernet protocol

The CIM 500 ethernet module has a rotary switch for selection of 
the Industrial Ethernet protocol. See fig. 

15

.

Fig. 15

Selecting the Industrial Ethernet protocol

6.3 Setting the IP addresses

The CIM 500 ethernet module is default set to a fixed IP address. 
It is possible to change the IP address settings from the built-in 
webserver.

WARNING

Electric shock

Death or serious personal injury
- Connect CIM 500 only to SELV or SELV-E circuits.

It is important to connect the cable shield to earth 
through an earth clamp or to connect the cable shield 
to earth in the connector.

T

M

05

 64

35

 47

11

TM

05

 74

31

 10

13

Pos.

Description

Designation

1

Industrial Ethernet RJ45 connector 1

ETH1

2

Industrial Ethernet RJ45 connector 2

ETH2

3

Rotary switch for protocol selection

SW1

4

Data activity LED for connector 1

DATA1

5

Link LED for connector 1

LINK1

6

Data activity LED for connector 2

DATA2

7

Link LED for connector 2

LINK2

8

Green and red status LED for ethernet 
communication

LED 1

9

Green and red status LED for internal 
communication between the module and 
the pump.

LED 2

Ethernet 

switch

CIM 500

CIM 500

CIM 500

CIM 500

1

2

3

8

9

4

7

5

6

TM

05 748

1 101

3

Pos.

Description

0

PROFINET IO (default)

1

Modbus TCP

2

BACnet IP

3

EtherNet/IP

4

GRM IP (requires a contract with Grundfos)

5..E

Reserved, LED1 will be permanently red to indicate an 
invalid configuration

F

Reset to factory default 
Note: The rotary switch must be set in this position for 
20 seconds before CIM 500 resets to factory default. 
During this period LED1 flashes red and green at the 
same time to indicate that a reset will occur.

Every change of the rotary switch while the module is 
powered on will cause the module to restart.

Default IP settings 
used by the 
webserver

IP address:

192.168.1.100

Subnet mask: 255.255.255.0
Gateway:

192.168.1.1

IP settings for 
Modbus TCP

Make the settings via the webserver

Device name and IP 
settings for 
PROFINET IO 

Static configuration from the webserver 
or configuration from the PROFINET IO 
configuration tool.

Pumpland.ru

Содержание CIM 150 PROFIBUS DP

Страница 1: ...PROFIBUS and PROFINET for Grundfos boosters CIM CIU 150 PROFIBUS DP CIM CIU 500 Ethernet for PROFINET IO Functional profile and user manual GRUNDFOS INSTRUCTIONS Pumpland ru...

Страница 2: ...3 Status module StatusModule module 1 14 7 4 Illustration of closed loop control 16 7 5 Direct bus control of pumps ControlPumps module 50 16 7 6 Change feedback sensor type SelectFeedbackSensor modul...

Страница 3: ...with very high performance CIM Communication Interface Module CIU Communication Interface Unit Control MPC Grundfos pump controller and booster system CRC Cyclic Redundancy Check A data error detecti...

Страница 4: ...th earlier products CU 351 MPC Multi E model G Further you must fit CU 351 MPC with an add on module for the external GENIbus connection to connect to the unit 3 1 PROFIBUS DP CIM 150 Fig 1 Example of...

Страница 5: ...H and later is identical for TPED model H and later and MAGNA3 D In all cases mount the CIM module in the master pump placed to the left For the purpose of redundancy you can mount a second CIM module...

Страница 6: ...US connection type RS 485 two wire Conductors A B Maximum cable length 100 metres at 12 Mbits s Corresponds to 328 feet See section 5 3 1 Data transmission rates and cable length Slave address 1 126 S...

Страница 7: ...699 0908 Pos Designation Description 1 B RxD TxD P PROFIBUS terminal B positive data signal 2 A RxD TxD N PROFIBUS terminal A negative data signal 3 DGND PROFIBUS terminal DGND only for external termi...

Страница 8: ...module 2 As a result the booster system will be set to local mode and then be operating according to the local operating mode local setpoint and local control mode 5 8 Reaction to PLC Stop button If...

Страница 9: ...1013 Pos Description Designation 1 Industrial Ethernet RJ45 connector 1 ETH1 2 Industrial Ethernet RJ45 connector 2 ETH2 3 Rotary switch for protocol selection SW1 4 Data activity LED for connector 1...

Страница 10: ...ss the webserver while the selected Industrial Ethernet protocol is active Status Description Off CIM 500 is switched off Flashing green Wink function LED flashes 10 times when activated from the mast...

Страница 11: ...e change will be reflected in a bit byte value in a corresponding input module 7 2 2 Explanation to control bits RemoteAccessReq Control bit for setting the booster system in remote mode controlled fr...

Страница 12: ...3 ConstPressure 4 ConstDiffPressure 5 The setpoint of the booster system is interpreted as the setpoint for the pressure In these modes the booster system operates in closed loop control and adapts it...

Страница 13: ...is reflected in module 41 UserSetpoint with the same scaling The actual setpoint whether it has been set via Grundfos GO Remote the pump display the pump buttons or the fieldbus can be read from modul...

Страница 14: ...ig 20 Setpoint in open loop control for TPED and MAGNA3 D 7 2 7 Multi E model H and twin head pump TPED model H control For Multi E with a CIM module in the master pump only set CopyToLocal Module 2 b...

Страница 15: ...if the setpoint is influenced for example by analog input If influenced the ActualSetpoint module 29 will differ from the UserSetpoint module 37 Rotation Status bit indicating that the booster system...

Страница 16: ...nge 0 Zone pump 1 is forced to stop from PROFIBUS PROFINET 1 Zone pump 1 is in auto mode controlled from CU 352 1 ControlZonePump2 Value change 0 Zone pump 2 is forced to stop from PROFIBUS PROFINET 1...

Страница 17: ...g 10 Communication fault pump A None 80 Hardware fault IO 351 pump module A None 80 Hardware fault IO 351 I O module A None 83 Verification error EEPROM parameter area A None 88 Sensor fault general m...

Страница 18: ...s the outlet pressure measured by a pressure sensor S S 10 Level 8 m Provides the tank level Requires that a level sensor is installed It has an offset of 100 metres S S S 11 FeedTankLevel 8 m Provide...

Страница 19: ...0 Digital output 1 1 Digital output 2 2 7 Reserved 25 PumpsPresent 5 Bits One bit for each pump configured in the system Logical 1 The pump is present 0 Zone pump 1 present 1 Zone pump 2 present 2 Zo...

Страница 20: ...pm 16 gal h 3 kPa 10 C 17 gal s 4 psi 11 F 18 ft3 h 5 ft 12 19 ft3 min 6 m3 h 13 m3 min 20 ft3 s 45 FeedbackSensorMin 6 Sensor unit Minimum value for the closed loop feedback sensor 46 FeedbackSensorM...

Страница 21: ...ulti E TPED model H PROFIBUS PROFINET module FeedBackSensorUnit Measuring sensor options Primary sensor options VolumeFlow 5 3 0 1 m3 h Flow rate Flow rate Flow rate Series 2000 Head 6 16 0 01 m Diffe...

Страница 22: ...ion general shutdown MPF 51 Blocked motor or pump 54 Motor protection function 3 sec limit 55 Motor current protection activated MCP 56 Underload 57 Dry running 64 Overtemperature 65 Motor temperature...

Страница 23: ...ble for Hydro MPC E and only if the backup pump is an E pump Byte Name Description Bytes 1 to 4 data type 8 Current A Zone pump motor current Bytes 5 to 8 data type 8 Power W Zone pump motor power Byt...

Страница 24: ...7 MGE 3 phase model H and later 7 MP 204 motor protector 1 MP 204 17 Hydro Multi E model G 1 With 3 phase pumps 2 With 1 phase pumps 21 Hydro MPC Control MPC Hydro Multi B 1 Hydro MPC Control MPC CU 3...

Страница 25: ...efore the equipment is installed under real life conditions 8 1 CIM 150 product simulation Product simulation mode is entered when the hexadecimal address switch has one of the values shown in the tab...

Страница 26: ...tting the PROFIBUS address Check that the GSD file used is correct Check that the PROFIBUS cable has been fitted correctly See section 5 3 Connecting the PROFIBUS Check that the PROFIBUS termination i...

Страница 27: ...unning 8 LED1 is permanently red and green at the same time a Error in firmware download Use the webserver to download the firmware again 9 LED2 is permanently red and green at the same time a Memory...

Страница 28: ...0 7 52 3 4 97 6 1 8 0 8 53 3 5 98 6 2 9 0 9 54 3 6 99 6 3 10 0 A 55 3 7 100 6 4 11 0 B 56 3 8 101 6 5 12 0 C 57 3 9 102 6 6 13 0 D 58 3 A 103 6 7 14 0 E 59 3 B 104 6 8 15 0 F 60 3 C 105 6 9 16 1 0 61...

Страница 29: ...module 17 Performance requirement cannot be met 52 Motor slip high 87 18 Commanded alarm standby trip 53 Stalled motor 88 Sensor fault 19 Diaphragm break dosing pump 54 Motor protection function 3 se...

Страница 30: ...winding current too high single phase motors 156 Communication fault internal frequency converter module 191 Limit exceeded sensor 2 for example high level in WW application 122 Auxiliary winding curr...

Страница 31: ...ted or commanded 217 Alarm general purpose sensor high 232 Ethernet Auto disabled due to misuse 247 Power on notice device or system has been switched off 218 Alarm general purpose sensor low 233 Ethe...

Страница 32: ...Pv4 6 Select the Alternate Configuration tab 7 Configure an IP address and subnet mask to be used by your PC See fig 1 Fig 1 Example from Windows A 2 Webserver configuration The built in webserver is...

Страница 33: ...unique Subnet Mask Configure the subnet mask for CIM 500 on the PROFINET IO network Gateway Configure the default gateway for the PROFINET IO network Use DHCP CIM 500 can be configured to automatical...

Страница 34: ...34 Pumpland ru...

Страница 35: ...Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa cent...

Страница 36: ...he name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S ww...

Отзывы: