7. Detailed description of data modules

7.1 Data types

Grundfos CIU 150 and CIU 500 support the following data types. 
All data types, except for data type 10, comply with specification 
IEC 61158-6 standard data types for use in PROFIBUS/
PROFINET profiles.

All multi-byte data types are transmitted with MSB (Most 
Significant Byte) first.

7.2 Control module (ControlModule, module 2)

The control module is a PROFIBUS/PROFINET output module 
used for the control of the booster system from bus. Its data type 
is 10, non-standard. If pump 2 in a Multi-E or TPED pump also 
has a CIM module mounted, for redundancy, any writings to the 
control module must be done for both pump heads.

* Not supported by Hydro Multi-E.

** Closed loop:

MPC, Multi-E: Percentage of closed-loop feedback sensor 
maximum value.
TPED, MAGNA3-D: Percentage of the setpoint range.
Open loop:

MPC, Multi-E: Percentage of the maximum performance.
TPED, MAGNA3-D: Percentage of the nominal pump frequency.

7.2.1 Explanation to event trigger

Rising edge

Control bits with a rising-edge event trigger behave like a 
command that is executed when a bit transition from "0" to "1" 
occurs. Each of them has a corresponding acknowledge bit in the 
StatusModule which is set when the command is executed and 
cleared when the control bit is written back to "0".

State

Control bits with a state event trigger behave like a "state" that is 
forced upon the booster system. In CIU 150 and 500, the "actual 
state" of the booster system as read from StatusModule is 
continuously compared with the "requested" state in 
ControlModule, and CIU 150 and 500 write the appropriate 
GENIbus command to the booster system to make the two states 
correspond to each other. Due to state restrictions or priorities, 
this might not always be possible, see the explanation to the bit in 
question.

Value change

Control bits/bytes with a change event trigger behave like a 
command that is executed when the bit/byte changes its value. 
CIM 150 andv500 will attempt to make the system operate 
according to the requested value. The change will be reflected in 
a bit/byte value in a corresponding input module.

7.2.2 Explanation to control bits

RemoteAccessReq

Control bit for setting the booster system in remote mode, 
controlled from bus, or local mode, controlled from the operating 
panel or Grundfos GO Remote:

However, certain commands from other control sources, for 
example Stop or Max. from a local source or external Stop from a 
digital input, have a higher priority and overrule the control from 
the bus.

OnOff

Control bit used to start and stop the booster system:

ResetFault

Control bit that resets alarms and warnings. 

CopyToLocal

If this bit is set, the remote setting of Control mode, Operating 
mode and the setpoint will be copied to the local setting during a 
remote to local transition. This bit is not supported by MPC, Multi-
E model G and earlier models. 

Data type

Description

1

Boolean

2

Integer 8

3

Integer 16

4

Integer 32

5

Unsigned 8

6

Unsigned 16

7

Unsigned 32

8

Floating point

9

Visible string

10

Non-standard

To control the Hydro MPC or Control MPC from bus, 
you must select the control source "From bus" on the 
CU 35X: "Settings" > "Secondary functions" > 
"Control source".

Byte

Bit

Name

Event trigger

Byte 1
(data type 5)

0

RemoteAccessReq

State

1

OnOff

State

2

ResetFault

Rising edge

3

-

-

4

CopyToLocal State

5-7 -

-

Byte 2
(data type 5)

ControlMode [enumeration] 
0: ConstSpeed*
1: ConstFreq*
2: -
3: ConstHead
4: ConstPressure
5: ConstDiffPress
6: VarDiffPress
7: ConstFlow
8: ConstTemp
9: ConstTempDiff
10: ConstLev

Byte 3
(data type 5)

OperatingMode [enumeration]
0: AutoControl
1-3: -
4: OpenLoopMin*
5: -
6: OpenLoopMax

Bytes 4 and 5
(data type 6)

Setpoint [0.01 %]**

0:

The booster system is set to local mode and operates 
according to its local operating mode and setpoint. With 
this setting, the other control bits in ControlModule will 
have no influence.

1:

The booster system is set to remote mode and operates 
according to the operating mode and setpoint set in 
ControlModule. The other control bits in ControlModule 
will also be active.

0: For stopping the booster system remotely.
1: For starting the booster system remotely.

0: Copy to local settings inactive

1:

Copy to local settings active. Switching the booster from 
remote to local will not influence the behaviour of the 
booster. 

Pumpland.ru

Содержание CIM 150 PROFIBUS DP

Страница 1: ...PROFIBUS and PROFINET for Grundfos boosters CIM CIU 150 PROFIBUS DP CIM CIU 500 Ethernet for PROFINET IO Functional profile and user manual GRUNDFOS INSTRUCTIONS Pumpland ru...

Страница 2: ...3 Status module StatusModule module 1 14 7 4 Illustration of closed loop control 16 7 5 Direct bus control of pumps ControlPumps module 50 16 7 6 Change feedback sensor type SelectFeedbackSensor modul...

Страница 3: ...with very high performance CIM Communication Interface Module CIU Communication Interface Unit Control MPC Grundfos pump controller and booster system CRC Cyclic Redundancy Check A data error detecti...

Страница 4: ...th earlier products CU 351 MPC Multi E model G Further you must fit CU 351 MPC with an add on module for the external GENIbus connection to connect to the unit 3 1 PROFIBUS DP CIM 150 Fig 1 Example of...

Страница 5: ...H and later is identical for TPED model H and later and MAGNA3 D In all cases mount the CIM module in the master pump placed to the left For the purpose of redundancy you can mount a second CIM module...

Страница 6: ...US connection type RS 485 two wire Conductors A B Maximum cable length 100 metres at 12 Mbits s Corresponds to 328 feet See section 5 3 1 Data transmission rates and cable length Slave address 1 126 S...

Страница 7: ...699 0908 Pos Designation Description 1 B RxD TxD P PROFIBUS terminal B positive data signal 2 A RxD TxD N PROFIBUS terminal A negative data signal 3 DGND PROFIBUS terminal DGND only for external termi...

Страница 8: ...module 2 As a result the booster system will be set to local mode and then be operating according to the local operating mode local setpoint and local control mode 5 8 Reaction to PLC Stop button If...

Страница 9: ...1013 Pos Description Designation 1 Industrial Ethernet RJ45 connector 1 ETH1 2 Industrial Ethernet RJ45 connector 2 ETH2 3 Rotary switch for protocol selection SW1 4 Data activity LED for connector 1...

Страница 10: ...ss the webserver while the selected Industrial Ethernet protocol is active Status Description Off CIM 500 is switched off Flashing green Wink function LED flashes 10 times when activated from the mast...

Страница 11: ...e change will be reflected in a bit byte value in a corresponding input module 7 2 2 Explanation to control bits RemoteAccessReq Control bit for setting the booster system in remote mode controlled fr...

Страница 12: ...3 ConstPressure 4 ConstDiffPressure 5 The setpoint of the booster system is interpreted as the setpoint for the pressure In these modes the booster system operates in closed loop control and adapts it...

Страница 13: ...is reflected in module 41 UserSetpoint with the same scaling The actual setpoint whether it has been set via Grundfos GO Remote the pump display the pump buttons or the fieldbus can be read from modul...

Страница 14: ...ig 20 Setpoint in open loop control for TPED and MAGNA3 D 7 2 7 Multi E model H and twin head pump TPED model H control For Multi E with a CIM module in the master pump only set CopyToLocal Module 2 b...

Страница 15: ...if the setpoint is influenced for example by analog input If influenced the ActualSetpoint module 29 will differ from the UserSetpoint module 37 Rotation Status bit indicating that the booster system...

Страница 16: ...nge 0 Zone pump 1 is forced to stop from PROFIBUS PROFINET 1 Zone pump 1 is in auto mode controlled from CU 352 1 ControlZonePump2 Value change 0 Zone pump 2 is forced to stop from PROFIBUS PROFINET 1...

Страница 17: ...g 10 Communication fault pump A None 80 Hardware fault IO 351 pump module A None 80 Hardware fault IO 351 I O module A None 83 Verification error EEPROM parameter area A None 88 Sensor fault general m...

Страница 18: ...s the outlet pressure measured by a pressure sensor S S 10 Level 8 m Provides the tank level Requires that a level sensor is installed It has an offset of 100 metres S S S 11 FeedTankLevel 8 m Provide...

Страница 19: ...0 Digital output 1 1 Digital output 2 2 7 Reserved 25 PumpsPresent 5 Bits One bit for each pump configured in the system Logical 1 The pump is present 0 Zone pump 1 present 1 Zone pump 2 present 2 Zo...

Страница 20: ...pm 16 gal h 3 kPa 10 C 17 gal s 4 psi 11 F 18 ft3 h 5 ft 12 19 ft3 min 6 m3 h 13 m3 min 20 ft3 s 45 FeedbackSensorMin 6 Sensor unit Minimum value for the closed loop feedback sensor 46 FeedbackSensorM...

Страница 21: ...ulti E TPED model H PROFIBUS PROFINET module FeedBackSensorUnit Measuring sensor options Primary sensor options VolumeFlow 5 3 0 1 m3 h Flow rate Flow rate Flow rate Series 2000 Head 6 16 0 01 m Diffe...

Страница 22: ...ion general shutdown MPF 51 Blocked motor or pump 54 Motor protection function 3 sec limit 55 Motor current protection activated MCP 56 Underload 57 Dry running 64 Overtemperature 65 Motor temperature...

Страница 23: ...ble for Hydro MPC E and only if the backup pump is an E pump Byte Name Description Bytes 1 to 4 data type 8 Current A Zone pump motor current Bytes 5 to 8 data type 8 Power W Zone pump motor power Byt...

Страница 24: ...7 MGE 3 phase model H and later 7 MP 204 motor protector 1 MP 204 17 Hydro Multi E model G 1 With 3 phase pumps 2 With 1 phase pumps 21 Hydro MPC Control MPC Hydro Multi B 1 Hydro MPC Control MPC CU 3...

Страница 25: ...efore the equipment is installed under real life conditions 8 1 CIM 150 product simulation Product simulation mode is entered when the hexadecimal address switch has one of the values shown in the tab...

Страница 26: ...tting the PROFIBUS address Check that the GSD file used is correct Check that the PROFIBUS cable has been fitted correctly See section 5 3 Connecting the PROFIBUS Check that the PROFIBUS termination i...

Страница 27: ...unning 8 LED1 is permanently red and green at the same time a Error in firmware download Use the webserver to download the firmware again 9 LED2 is permanently red and green at the same time a Memory...

Страница 28: ...0 7 52 3 4 97 6 1 8 0 8 53 3 5 98 6 2 9 0 9 54 3 6 99 6 3 10 0 A 55 3 7 100 6 4 11 0 B 56 3 8 101 6 5 12 0 C 57 3 9 102 6 6 13 0 D 58 3 A 103 6 7 14 0 E 59 3 B 104 6 8 15 0 F 60 3 C 105 6 9 16 1 0 61...

Страница 29: ...module 17 Performance requirement cannot be met 52 Motor slip high 87 18 Commanded alarm standby trip 53 Stalled motor 88 Sensor fault 19 Diaphragm break dosing pump 54 Motor protection function 3 se...

Страница 30: ...winding current too high single phase motors 156 Communication fault internal frequency converter module 191 Limit exceeded sensor 2 for example high level in WW application 122 Auxiliary winding curr...

Страница 31: ...ted or commanded 217 Alarm general purpose sensor high 232 Ethernet Auto disabled due to misuse 247 Power on notice device or system has been switched off 218 Alarm general purpose sensor low 233 Ethe...

Страница 32: ...Pv4 6 Select the Alternate Configuration tab 7 Configure an IP address and subnet mask to be used by your PC See fig 1 Fig 1 Example from Windows A 2 Webserver configuration The built in webserver is...

Страница 33: ...unique Subnet Mask Configure the subnet mask for CIM 500 on the PROFINET IO network Gateway Configure the default gateway for the PROFINET IO network Use DHCP CIM 500 can be configured to automatical...

Страница 34: ...34 Pumpland ru...

Страница 35: ...Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa cent...

Страница 36: ...he name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S ww...

Отзывы: