5. PROFIBUS DP, CIM 150 setup
5.1 PROFIBUS bus topology
The PROFIBUS-preferred bus topology is daisy chaining as
illustrated in fig.
. The end devices of a physical bus segment
must be terminated (LT = Line Termination). Each device must
have a unique physical address [1-126]. Up to 32 PROFIBUS
devices can be connected to a bus segment, and by using a
repeater another 32 devices can be connected. This can be
repeated until the maximum number of addresses are used. Make
sure that each device is connected to a proper earth potential.
Fig. 7
Example of PROFIBUS bus segment with line
termination
5.2 CIM 150 PROFIBUS module
Fig. 8
CIM 150 PROFIBUS module
5.3 Connecting the PROFIBUS
5.3.1 Data transmission rates and cable length
We recommend using a cable according to IEC 61158.
Example
Siemens, 6XV1 830-0EH10.
Fitting the cable
See fig.
1. Connect the red conductor(s) to terminal B (pos. 1).
2. Connect the green conductor(s) to terminal A (pos. 2).
3. Connect the cable screens to earth via the earth clamp (pos.
3).
Fig. 9
Connecting the PROFIBUS
TM
0
4
9
635
4
810
TM
04 169
9 090
8
Pos.
Designation
Description
1
B (RxD/TxD-P)
PROFIBUS terminal B, positive data
signal
2
A (RxD/TxD-N)
PROFIBUS terminal A, negative data
signal
3
DGND
PROFIBUS terminal DGND, only for
external termination
4
VP
+5 VDC, only for external termination
5
SW1/SW2
On and off switches for termination
resistors
6
LED1
Red and green status LED for
PROFIBUS communication
7
LED2
Red and green status LED for
GENIbus communication between
CIM/CIU 150 and the Grundfos
product
8
SW3
Hexadecimal rotary switch for setting
the PROFIBUS address, four most
significant bits
9
SW4
Hexadecimal rotary switch for setting
the PROFIBUS address, four least
significant bits
The power supply (pos. 4, fig.
) must only be used
for external termination.
LT
LT
Master
Slave
Slave
Slave
2
1
3 4
5
6
7
8
9
kbits/s
Maximum cable length
[m/ft]
9.6
1200/4000
19.2
1200/4000
45.45
1200/4000
93.75
1000/3300
187.5
1000/3300
500
400/1300
1500
200/660
3000
100/330
6000
100/330
12000
100/330
For maximum safety and reliability, connect the cable
screen to earth via the earth clamp, and make sure
that all CIU 150 units are properly earthed via the
mains supply earth-wire.
TM
04
17
00
09
08
Pos.
Description
1
PROFIBUS terminal B
2
PROFIBUS terminal A
3
Earth clamp
4
+5 VDC
5
DGND
3
1
2
5
4
Pumpland.ru
Содержание CIM 150 PROFIBUS DP
Страница 34: ...34 Pumpland ru...