![Grundfos CIM 150 PROFIBUS DP Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/grundfos/cim-150-profibus-dp/cim-150-profibus-dp_functional-profile-and-user-manual_2271035021.webp)
English (GB)
21
All the data items ControlModule. Setpoint, StatusModule.
ProcessFeedback, ActualSetpoint and UserSetpoint have a
scaling relative to the feedback sensor. By using the scaling
information of the feedback sensor (FeedbackSensorUnit,
FeedbackSensorMin, FeedbackSensorMax) these data items can
be expressed in absolute units.
Many of the booster system measurement modules require a
particular sensor to be present. As a limited number of sensors
are available, only a few of the measurement modules can be
available simultaneously.
The table below shows the relation between the PROFIBUS/
PROFINET measurement modules and the sensor value selected
on CU 35X.
The table below shows the relation between the Hydro Multi-E
PROFIBUS/PROFINET measurement modules and the
measurement unit selected with Grundfos GO Remote for the
feedback sensor. Only one of the measurement module groups in
the table below is available at a time.
You can calculate, the process feedback scaled according to
ProcessFeedBackUnit from this formula:
Feedback (scaled) = ProcessFeedBack * (FeedBackSensorMax -
FeedBackSensorMin) / 100 % + FeedBackSensorMin
See also page
Hydro/Control MPC and Multi-E/TPED model H
PROFIBUS/PROFINET module FeedBackSensorUnit
Measuring sensor, options
Primary sensor, options
VolumeFlow (5)
3: 0.1 m
3
/h
Flow rate
Flow rate
Flow rate, Series 2000
Head (6)
16: 0.01 m
Differential pressure, pump
(zero is equal to -100 m)
Differential pressure, pump
Differential pressure, Series 2000
RemotePressure (7)
5: 0.001 bar
Differential pressure, external
External pressure
It has an offset of -1.000 bar.
Differential pressure, external
External pressure
InletPressure (8)
7: 0.001 bar
Differential pressure, inlet
Differential pressure, inlet
OutletPressure (9)
6: 0.001 bar
Outlet pressure
Differential pressure, outlet
Outlet pressure
Differential pressure, outlet
RemoteTemperature (14)
18: 0.01 K
Return-pipe temperature, external
Return-pipe temperature, external
AmbientTemperature (15)
22: 0.01 K
Ambient temperature
Ambient temperature
InletTemp (16)
20: 0.01 K
Return-pipe temperature
Return-pipe temperature
OutletTemp (17)
19: 0.01 K
Flow-pipe temperature
Flow-pipe temperature
TemperatureDifference (18)
21: 0.01 K
Differential temperature
Differential temperature
-
-
0-100 % signal
0-100 % signal
Hydro Multi-E model G
Sensor unit
configuration with the
Grundfos GO Remote
PROFIBUS/PROFINET data
module generated from feedback
sensor measurement
bar
Head (6)
OutletPressure (9)
mbar
m
kPa
psi
ft
m
3
/h
VolumeFlow (5)
m
3
/s
l/s
gpm
°C
RemoteTemperature (14)
°F
%
-
Pumpland.ru
Содержание CIM 150 PROFIBUS DP
Страница 34: ...34 Pumpland ru...