7.9 Zone pump modules (ZonePumpModule, modules 

29 to 34)

A zone pump module is available for each of the six possible 
zone pumps. Its data type is 10, non-standard.

* Hydro/Control MPC-E, Multi-E/TPED model H and MAGNA3-

D.

** For Hydro Multi-E this indicates the state commanded by the 

Hydro Multi-E control. A local override command, for example 
stop, is not indicated by this bit.

*** Hydro/Control MPC-E, Multi-E, TPED and MAGNA3-D.

Byte

Bit Name

Description

Byte 1
(data type 5)

0

AccessMode*

Zone pump control:
0:Local (buttons on 
pump, Grundfos GO 
Remote or external 
digital input).
1:Controlled from 
booster system.

1

OnOff**

Zone pump on or off:
0:Off (stopped).
1:On (started).

2

Fault

Zone pump fault 
condition:
0:No fault condition.
1:Fault, alarm on 
pump.

3-7 -

-

Byte 2
(data type 5)

FaultCode***
[enum]

Alarm code from zone 
pump, see list of 
possible codes below.

Bytes 3 to 6
(data type 8)

OperationTime***
[h]

Operating time of zone 
pump.

Bytes 7 and 8
(data type 6)

Speed*
[0.01 %]

Zone pump speed.

Code

Alarm/warning description

1

Leakage current

2

Missing phase

3

External fault signal

4

Too many restarts

4

Too many restarts per 24 hours

7

Too many hardware shutdowns

10

Communication fault, pump

14

Electronic DC-link protection activated (ERP)

16

Other

29

Turbine operation, impellers forced backwards

30

Change bearings (specific service information)

31

Change varistor(s) (specific service information)

32

Overvoltage

40

Undervoltage

41

Undervoltage transient

42

Cut-in fault (dV/dt)

45

Voltage asymmetry

48

Overload

49

Overcurrent (i_line, i_dc, i_mo)

50

Motor protection function, general shutdown (MPF)

51

Blocked motor or pump

54

Motor protection function, 3 sec. limit

55

Motor current protection activated (MCP)

56

Underload

57

Dry running

64

Overtemperature

65

Motor temperature 1 (t_m or t_mo or t_mo1) 

66

Temperature, control electronics

67

Temperature too high, internal frequency converter 
module (t_m)

70

Thermal relay 2 in motor, for example thermistor

72

Hardware fault, type 1

73

Hardware shutdown (HSD)

76

Internal communication fault

77

Communication fault, twin-head pump

80

Hardware fault, type 2

83

Verification error, FE parameter area (EEPROM)

84

Memory access error

85

Verification error, BE parameter area (EEPROM)

88

Sensor fault

89

Signal fault, (feedback) sensor 1

91

Signal fault, temperature 1 sensor

91

Temperature sensor 1 signal fault 

93

Signal fault, sensor 2

96

Setpoint signal outside range

105

Electronic rectifier protection activated (ERP)

106

Electronic inverter protection activated (EIP)

148

Motor bearing temperature high (Pt100) in drive end 
(DE)

149

Motor bearing temperature high (Pt100) in non-drive 
end (NDE)

155

Inrush fault

156

Communication fault, internal frequency converter 
module

157

Real-time clock error

161

Sensor supply fault, 5 V

162

Sensor supply fault, 24 V

163

Motor drive protection function measurement fault

164

Signal fault, LiqTec sensor

165

Signal fault, analog input A1

166

Signal fault, analog input A2

167

Signal fault, analog input A3

175

Signal fault, temperature 2 sensor (t_mo2)

175

Temperature sensor 2 signal fault 

176

Signal fault, temperature 3 sensor (t_mo3)

190

Limit exceeded, sensor 1

191

Limit exceeded, sensor 2

240

Lubricate bearings (specific service information)

241

Motor phase failure

242

Automatic motor model recognition failed

Code

Alarm/warning description

Pumpland.ru

Содержание CIM 150 PROFIBUS DP

Страница 1: ...PROFIBUS and PROFINET for Grundfos boosters CIM CIU 150 PROFIBUS DP CIM CIU 500 Ethernet for PROFINET IO Functional profile and user manual GRUNDFOS INSTRUCTIONS Pumpland ru...

Страница 2: ...3 Status module StatusModule module 1 14 7 4 Illustration of closed loop control 16 7 5 Direct bus control of pumps ControlPumps module 50 16 7 6 Change feedback sensor type SelectFeedbackSensor modul...

Страница 3: ...with very high performance CIM Communication Interface Module CIU Communication Interface Unit Control MPC Grundfos pump controller and booster system CRC Cyclic Redundancy Check A data error detecti...

Страница 4: ...th earlier products CU 351 MPC Multi E model G Further you must fit CU 351 MPC with an add on module for the external GENIbus connection to connect to the unit 3 1 PROFIBUS DP CIM 150 Fig 1 Example of...

Страница 5: ...H and later is identical for TPED model H and later and MAGNA3 D In all cases mount the CIM module in the master pump placed to the left For the purpose of redundancy you can mount a second CIM module...

Страница 6: ...US connection type RS 485 two wire Conductors A B Maximum cable length 100 metres at 12 Mbits s Corresponds to 328 feet See section 5 3 1 Data transmission rates and cable length Slave address 1 126 S...

Страница 7: ...699 0908 Pos Designation Description 1 B RxD TxD P PROFIBUS terminal B positive data signal 2 A RxD TxD N PROFIBUS terminal A negative data signal 3 DGND PROFIBUS terminal DGND only for external termi...

Страница 8: ...module 2 As a result the booster system will be set to local mode and then be operating according to the local operating mode local setpoint and local control mode 5 8 Reaction to PLC Stop button If...

Страница 9: ...1013 Pos Description Designation 1 Industrial Ethernet RJ45 connector 1 ETH1 2 Industrial Ethernet RJ45 connector 2 ETH2 3 Rotary switch for protocol selection SW1 4 Data activity LED for connector 1...

Страница 10: ...ss the webserver while the selected Industrial Ethernet protocol is active Status Description Off CIM 500 is switched off Flashing green Wink function LED flashes 10 times when activated from the mast...

Страница 11: ...e change will be reflected in a bit byte value in a corresponding input module 7 2 2 Explanation to control bits RemoteAccessReq Control bit for setting the booster system in remote mode controlled fr...

Страница 12: ...3 ConstPressure 4 ConstDiffPressure 5 The setpoint of the booster system is interpreted as the setpoint for the pressure In these modes the booster system operates in closed loop control and adapts it...

Страница 13: ...is reflected in module 41 UserSetpoint with the same scaling The actual setpoint whether it has been set via Grundfos GO Remote the pump display the pump buttons or the fieldbus can be read from modul...

Страница 14: ...ig 20 Setpoint in open loop control for TPED and MAGNA3 D 7 2 7 Multi E model H and twin head pump TPED model H control For Multi E with a CIM module in the master pump only set CopyToLocal Module 2 b...

Страница 15: ...if the setpoint is influenced for example by analog input If influenced the ActualSetpoint module 29 will differ from the UserSetpoint module 37 Rotation Status bit indicating that the booster system...

Страница 16: ...nge 0 Zone pump 1 is forced to stop from PROFIBUS PROFINET 1 Zone pump 1 is in auto mode controlled from CU 352 1 ControlZonePump2 Value change 0 Zone pump 2 is forced to stop from PROFIBUS PROFINET 1...

Страница 17: ...g 10 Communication fault pump A None 80 Hardware fault IO 351 pump module A None 80 Hardware fault IO 351 I O module A None 83 Verification error EEPROM parameter area A None 88 Sensor fault general m...

Страница 18: ...s the outlet pressure measured by a pressure sensor S S 10 Level 8 m Provides the tank level Requires that a level sensor is installed It has an offset of 100 metres S S S 11 FeedTankLevel 8 m Provide...

Страница 19: ...0 Digital output 1 1 Digital output 2 2 7 Reserved 25 PumpsPresent 5 Bits One bit for each pump configured in the system Logical 1 The pump is present 0 Zone pump 1 present 1 Zone pump 2 present 2 Zo...

Страница 20: ...pm 16 gal h 3 kPa 10 C 17 gal s 4 psi 11 F 18 ft3 h 5 ft 12 19 ft3 min 6 m3 h 13 m3 min 20 ft3 s 45 FeedbackSensorMin 6 Sensor unit Minimum value for the closed loop feedback sensor 46 FeedbackSensorM...

Страница 21: ...ulti E TPED model H PROFIBUS PROFINET module FeedBackSensorUnit Measuring sensor options Primary sensor options VolumeFlow 5 3 0 1 m3 h Flow rate Flow rate Flow rate Series 2000 Head 6 16 0 01 m Diffe...

Страница 22: ...ion general shutdown MPF 51 Blocked motor or pump 54 Motor protection function 3 sec limit 55 Motor current protection activated MCP 56 Underload 57 Dry running 64 Overtemperature 65 Motor temperature...

Страница 23: ...ble for Hydro MPC E and only if the backup pump is an E pump Byte Name Description Bytes 1 to 4 data type 8 Current A Zone pump motor current Bytes 5 to 8 data type 8 Power W Zone pump motor power Byt...

Страница 24: ...7 MGE 3 phase model H and later 7 MP 204 motor protector 1 MP 204 17 Hydro Multi E model G 1 With 3 phase pumps 2 With 1 phase pumps 21 Hydro MPC Control MPC Hydro Multi B 1 Hydro MPC Control MPC CU 3...

Страница 25: ...efore the equipment is installed under real life conditions 8 1 CIM 150 product simulation Product simulation mode is entered when the hexadecimal address switch has one of the values shown in the tab...

Страница 26: ...tting the PROFIBUS address Check that the GSD file used is correct Check that the PROFIBUS cable has been fitted correctly See section 5 3 Connecting the PROFIBUS Check that the PROFIBUS termination i...

Страница 27: ...unning 8 LED1 is permanently red and green at the same time a Error in firmware download Use the webserver to download the firmware again 9 LED2 is permanently red and green at the same time a Memory...

Страница 28: ...0 7 52 3 4 97 6 1 8 0 8 53 3 5 98 6 2 9 0 9 54 3 6 99 6 3 10 0 A 55 3 7 100 6 4 11 0 B 56 3 8 101 6 5 12 0 C 57 3 9 102 6 6 13 0 D 58 3 A 103 6 7 14 0 E 59 3 B 104 6 8 15 0 F 60 3 C 105 6 9 16 1 0 61...

Страница 29: ...module 17 Performance requirement cannot be met 52 Motor slip high 87 18 Commanded alarm standby trip 53 Stalled motor 88 Sensor fault 19 Diaphragm break dosing pump 54 Motor protection function 3 se...

Страница 30: ...winding current too high single phase motors 156 Communication fault internal frequency converter module 191 Limit exceeded sensor 2 for example high level in WW application 122 Auxiliary winding curr...

Страница 31: ...ted or commanded 217 Alarm general purpose sensor high 232 Ethernet Auto disabled due to misuse 247 Power on notice device or system has been switched off 218 Alarm general purpose sensor low 233 Ethe...

Страница 32: ...Pv4 6 Select the Alternate Configuration tab 7 Configure an IP address and subnet mask to be used by your PC See fig 1 Fig 1 Example from Windows A 2 Webserver configuration The built in webserver is...

Страница 33: ...unique Subnet Mask Configure the subnet mask for CIM 500 on the PROFINET IO network Gateway Configure the default gateway for the PROFINET IO network Use DHCP CIM 500 can be configured to automatical...

Страница 34: ...34 Pumpland ru...

Страница 35: ...Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa cent...

Страница 36: ...he name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S ww...

Отзывы: