background image

5

5. ACtUAtOR CONNECtIONS

  Electrical and/or pneumatic connections to damper 

actuators should be made in accordance with wiring and 
piping diagrams developed in compliance with applicable 
codes, ordinances and regulations (see 

Electrical 

Guidelines

).

6. CONNECtION AND OPERAtION OF 

tEMPERAtURE RESPONSE DEVICES (Fusible 
Link, RRL OPtION, OCI OPtION, tOR OPtION, 
and PRV OPtION)

RRL -

 Dampers will be supplied with a fusible link 

temperature response device, as a standard. An optional 
thermostat type temperature response device may have 
been installed. The device is a RRL (resetable link device), 
which only incorporates one thermostat and therefore the 
damper remains closed as soon as its sensor temperature 
is reached. The RRL does not contain blade indication 
switches. Refer to

 Fig. 4

 on page 5 for wiring of the RRL 

thermostat.

OCI -

 The OCI (open or closed indicator) option contains 

a single pole, double throw switch used to indicate the 
damper blade position. The switch provides a positive open 
or closed signal when used in conjunction with remote 
indicator lights. Refer to 

Fig. 5 

on page 5 for wiring of the 

OCI option.

tOR -

 The TOR (temperature override device) option 

incorporates two thermostats with fixed settings (usually 
165°F and 350°F). The primary sensor (the sensor with the 
lower temperature setting) can be bypassed by an external 
electrical signal allowing the damper to reopen until the 
temperature reaches the setting of the secondary sensor 
(the sensor with the higher temperature setting). When 
the temperature of the secondary sensor is exceeded the 
damper closes and remains closed thereafter (

Fig. 6

)

The TOR assembly also contains a single pole, double 
throw switch used to indicate damper blade position. The 
switch provides a positive open or closed signal when used 
in conjunction with remote indicator lights. See page 6, Fig. 
6 for wiring of the TOR thermostats and indicator switches.
If either the TOR or the RRL is ordered with a pneumatic 
actuator, an EP switch is required with an appropriate 
electric power circuit to allow the electric thermostat to 
control the pneumatic actuator.

PRV -

 The PRV (pneumatic relief valve) option is heat 

responsive device used with pneumatic actuators. This 
can be used in place of EP switch where a RRL is used.  
The PRV activates when temperature in excess of the 
temperature of the fusible link are detected. When the 
fusible link melts, air from the actuator is exhausted to 
close the dampers. Pneumatic actuators are to be piped 
per local code.

Fig. 3

L1

M

L2

ELECTRIC DAMPER

ACTUATOR OR PNEUMATIC

SOLENOID  VALVE

PRIMARY TEMP

SENSOR

ELECTRICAL CAPACITY = 10 AMP  @ 120 / 240 VAC

BLACK

ORANGE

P

NC

BLACK

WHITE/RED

Fig. 4

RRL Wiring

RAtINGS  (Fig. 4 & 5) 

 
 

Integral Switch type:

   Single Pole, double throw

 

         

 Electrical:

    10 Amps, 

1

/

3

 hp, 120 or 240 Vac

 

   

1

/

2

 Amp, 125 Vdc; 

1

/

4

 Amp 250 Vdc 

 

   5 Amps, 120 Vac “L” (lamp load)

 

   1.0 Amps, 24 Vac

 

   1.5 Amps, 24 Vdc

 

temperature Limit

:   165° F (standard primary sensor)

 

  212° F (optional primary sensor)

 

  250° F (secondary sensor)

 

  350º F ( secondary sensor)

-

%".1&3

*/%*$"503

-*()54

-

$-04&%104*5*0/0'5)&%".1&3

"#-6&."3,&3*/%*$"5&5)&

5)&48*5$)8*3&483"11&%8*5)

/05&

:&--08

&-&$53*$"-$"1"$*5:".1!7"$

:&--08

:&--08

:&--08

/0

/0

4

4

#:05)&34

OCI Wiring

Fig. 5

Содержание FSDR-XXX

Страница 1: ... backcharges without prior written authorization Due to continuing research Greenheck reserves the right to change specifications without notice UL CLASSIFIED see complete marking on product UL CLASSIFIED to Canadian safety standards see complete marking on product UL Standard 555 555S Classification R13317 FSDR XXX SEFSDR XXX and SSFSDR XXX Model Dampers are intended for installation in accordanc...

Страница 2: ...ve leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to pr...

Страница 3: ...opening must be a minimum of 7 8 in larger than the outside diameter of the damper Refer to Section 4 for additional installation considerations SAFEty DANGER Electrical input may be needed for this equipment this work should be performed by a qualified electrician All wiring shall be done in accordance with the National Electrical Code ANSI NFPA 70 latest edition any local codes that may apply an...

Страница 4: ...SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall floor openings using a single retaining plate on either side of the wall floor or by using a retaining plate on both sides of the wall floor The use of a second retaining plate is allowed but is not necessary A single retaining plate is provided with the dampers A second retaining plate can be ordered as an opti...

Страница 5: ...or with the higher temperature setting When the temperature of the secondary sensor is exceeded the damper closes and remains closed thereafter Fig 6 The TOR assembly also contains a single pole double throw switch used to indicate damper blade position The switch provides a positive open or closed signal when used in conjunction with remote indicator lights See page 6 Fig 6 for wiring of the TOR ...

Страница 6: ... primary sensor 212 F optional primary sensor 250 F secondary sensor 350º F secondary sensor 8 Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown see Fig 7 Double vertical studs are not required for openings 36 in x 36 in or smaller Gypsum wall board must be fastened 12 in on center to all stud and runner flanges surrounding opening see Fig 8 All construc...

Страница 7: ...led too far into wall Move out to line designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance Damper does not fully open and or fully close Damper does not operate Actuator runs hot or makes a humming noise Link separated Heat Replace link Actuator prohibited from reaching end of stroke Disconnect linkage from jackshaft open damper power actuato...

Отзывы: