These instructions apply to 1

1

/

2

 hour rated combination fire smoke and fire dampers mounted (blades must be horizontal) in: 

1) masonry, block or stud walls and 2) concrete floors or ceilings. Specific requirements in these instructions are mandatory. 
Dampers must be installed in accordance with these instructions to meet the requirements of UL 555 and UL 555S. The 
installation of the damper and all duct connections to the damper sleeve shall conform to the latest editions of NFPA 90A, 
Standard for the Installation of Air Conditioning and Ventilating Systems, and the SMACNA Fire, Smoke and Radiation 
Damper Installation Guide, and UL Classifications R13317.

1. CLEARANCES REQUIRED BEtWEEN FIRE DAMPER SLEEVES AND WALL/FLOOR OPENINGS

  Fire damper assemblies expand during periods of intense heat. Therefore, it is essential that openings in walls or floors 

be larger than the fire damper assembly to allow for this expansion.  The wall/floor opening must be a minimum of 

7

/

 in. 

 

larger than the outside diameter of the damper. Refer to Section 4 for additional installation considerations.

SAFEty DANGER !

Electrical input may be needed for 
this equipment. this work should be 
performed by a qualified electrician.

All wiring shall be done in accordance with the National 
Electrical Code ANSI/NFPA-70 latest edition, any local codes 
that may apply, and wiring diagrams developed in compliance 
with the job or project design and specifications.

Electrical Guidelines

Installation - 

Failure to follow these instructions will void all warranties.

SAFEty CAUtION !

Verify power before wiring actuator. Greenheck is not responsible for any damage to, or failure of 

the unit caused by incorrect field wiring.

SAFEty DANGER ! :  to avoid causing death or serious bodily harm to building occupants, follow 

all instructions carefully. Dampers must close completely to preserve the 
integrity of the fire smoke separation.

Fig. 1

*/

'64*#-&
-*/,
-0$"5*0/

$-&"3"/$&'03
&91"/4*0/

5017*&80'%".1&3

*/."9

4-&&7&-&/(5)

58

%6$5
$0//&$5*0/
"3&"

"*3'-08

*/

"$56"503

*/."9

015*0/"-#-"%&104*5*0/

*/%*$"503"/%03&-&$53*$

-*/,

%6$5
$0//&$5*0/
"3&"

*/

*/

0QUJPOBM
4FDPOE
3FUBJOJOH
1MBUF

%POPUQMBDFSFUBJOFS
QMBUFJOUIJTHSPPWF

Содержание FSDR-XXX

Страница 1: ... backcharges without prior written authorization Due to continuing research Greenheck reserves the right to change specifications without notice UL CLASSIFIED see complete marking on product UL CLASSIFIED to Canadian safety standards see complete marking on product UL Standard 555 555S Classification R13317 FSDR XXX SEFSDR XXX and SSFSDR XXX Model Dampers are intended for installation in accordanc...

Страница 2: ...ve leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to pr...

Страница 3: ...opening must be a minimum of 7 8 in larger than the outside diameter of the damper Refer to Section 4 for additional installation considerations SAFEty DANGER Electrical input may be needed for this equipment this work should be performed by a qualified electrician All wiring shall be done in accordance with the National Electrical Code ANSI NFPA 70 latest edition any local codes that may apply an...

Страница 4: ...SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall floor openings using a single retaining plate on either side of the wall floor or by using a retaining plate on both sides of the wall floor The use of a second retaining plate is allowed but is not necessary A single retaining plate is provided with the dampers A second retaining plate can be ordered as an opti...

Страница 5: ...or with the higher temperature setting When the temperature of the secondary sensor is exceeded the damper closes and remains closed thereafter Fig 6 The TOR assembly also contains a single pole double throw switch used to indicate damper blade position The switch provides a positive open or closed signal when used in conjunction with remote indicator lights See page 6 Fig 6 for wiring of the TOR ...

Страница 6: ... primary sensor 212 F optional primary sensor 250 F secondary sensor 350º F secondary sensor 8 Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown see Fig 7 Double vertical studs are not required for openings 36 in x 36 in or smaller Gypsum wall board must be fastened 12 in on center to all stud and runner flanges surrounding opening see Fig 8 All construc...

Страница 7: ...led too far into wall Move out to line designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance Damper does not fully open and or fully close Damper does not operate Actuator runs hot or makes a humming noise Link separated Heat Replace link Actuator prohibited from reaching end of stroke Disconnect linkage from jackshaft open damper power actuato...

Отзывы: