Damper Maintenance

Dampers do not typically require maintenance as long as they are kept dry and clean. If cleaning is necessary, 
use mild detergents or solvents. If lubrication is desired for components such as axle bearings, jackshaft 
bearings and jamb seals, do not use oil-based lubricants or any other lubricants that attract contaminants such 
as dust.

Dampers and their electric/pneumatic actuator(s) must be maintained, cycled, and tested in accordance with:
•  The latest editions of NFPA 80, 90A, 92A, UL864, and local codes.
•  Actuator manufacturer recommendations.

Copyright © 2006 Greenheck Fan Corporation

461868 FSDR-XXX Rev. 7  March 2006

 Symptom 

          Possible Cause 

        Corrective Action  

 

 

Frame is out of round causing  

Adjust frame such that it is round

 

 

blades to bind on jamb seals 

   

 

 

Actuator linkage loose 

Close damper, disconnect power, adjust  

 

 

 

and tighten linkage

 

 

Defective motor 

Replace

 

 

Screws in damper linkage 

Locate screws and remove

 

 

Actuator linkage hitting wall or floor 

Damper installed too far into wall. Move

 

 

 

out to line designated on damper label.

 

 

Contaminants on damper 

Clean with a non-oil-based solvent

 

 

 

(see Damper Maintenance)

Damper does not 
fully open and/or 
fully close

Damper does not
operate

Actuator runs hot or 
makes a humming 
noise

Link separated

Heat

Replace link

Actuator prohibited from reaching 
end of stroke

Disconnect linkage from jackshaft, 
open damper, power actuator to end of 
spring, tighten linkage. Verify amp draw.

RRL, or TOR sensor 
tripped

Heat 

No power supplied to the actuator

Push reset button located on backside 
of RRL or TOR.

Damper trouble Shooting

The following is a possible cause and correction list for common concerns with the dampers.

Round duct connections to shall be attached with #8 sheet metal screws as follows:

  • Ducts 22 in. dia. and smaller shall have three screws.
  • Ducts larger than 22 in. dia. up to and including 24 in. dia. shall have five screws.

NOtE:

 All breakaway connections described may have duct sealant, PA2084T duct sealant adhesive manufactured by 

Precision, DP1010 water base duct sealant manufactured by Design Polymetrics, or Grey Pookie applied in accordance 
with SMACNA recommendations.

9. Round Duct Connections

Содержание FSDR-XXX

Страница 1: ... backcharges without prior written authorization Due to continuing research Greenheck reserves the right to change specifications without notice UL CLASSIFIED see complete marking on product UL CLASSIFIED to Canadian safety standards see complete marking on product UL Standard 555 555S Classification R13317 FSDR XXX SEFSDR XXX and SSFSDR XXX Model Dampers are intended for installation in accordanc...

Страница 2: ...ve leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to pr...

Страница 3: ...opening must be a minimum of 7 8 in larger than the outside diameter of the damper Refer to Section 4 for additional installation considerations SAFEty DANGER Electrical input may be needed for this equipment this work should be performed by a qualified electrician All wiring shall be done in accordance with the National Electrical Code ANSI NFPA 70 latest edition any local codes that may apply an...

Страница 4: ...SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall floor openings using a single retaining plate on either side of the wall floor or by using a retaining plate on both sides of the wall floor The use of a second retaining plate is allowed but is not necessary A single retaining plate is provided with the dampers A second retaining plate can be ordered as an opti...

Страница 5: ...or with the higher temperature setting When the temperature of the secondary sensor is exceeded the damper closes and remains closed thereafter Fig 6 The TOR assembly also contains a single pole double throw switch used to indicate damper blade position The switch provides a positive open or closed signal when used in conjunction with remote indicator lights See page 6 Fig 6 for wiring of the TOR ...

Страница 6: ... primary sensor 212 F optional primary sensor 250 F secondary sensor 350º F secondary sensor 8 Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown see Fig 7 Double vertical studs are not required for openings 36 in x 36 in or smaller Gypsum wall board must be fastened 12 in on center to all stud and runner flanges surrounding opening see Fig 8 All construc...

Страница 7: ...led too far into wall Move out to line designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance Damper does not fully open and or fully close Damper does not operate Actuator runs hot or makes a humming noise Link separated Heat Replace link Actuator prohibited from reaching end of stroke Disconnect linkage from jackshaft open damper power actuato...

Отзывы: