background image

2

Pre-Installation Guidelines

The basic intent of a proper installation is to secure the fire smoke or fire damper in the opening in such a manner as to 
prevent distortion and disruption of damper operation. This is accomplished by allowing the fire or fire smoke damper in 
rated separation openings to expand and for the connecting duct to separate in the event of the collapse of the hanging 
system. The following items will aid in completing the damper installation in a timely and effective manner.

1)  Check the schedules for proper damper locations within the building. Visually inspect the damper for damage and verify 

that the fusible link is in place or has not separated. If fusible link is not present or has separated, replace link. Never 
install a fire damper without the proper UL approved fusible link in place. (Fusible link is standard control option. An 
electric link may have been provided. Electric links have a button for resetting.)

2)  Lift or handle damper using the frame. Do not lift damper using blades or actuators.

3)  Do not install screws into the main body area of the damper frame as screws may interfere with and prevent damper 

blade from opening and/or closing.

4)  Damper has label indicating position of damper assembly in the wall. Install accordingly to comply with manufacturer’s 

appropriate UL Classification file number.

5)  Damper must be installed into duct or opening free of distortion or other misalignment. Damper must not be squeezed 

or stretched into duct or opening. Out of round, racked, twisted or misaligned installations can cause excessive leakage 
and/or torque requirements to exceed damper/actuator design.

6)  Damper and actuator must be kept clean and protected from dirt, dust and other foreign materials prior to and after 

installation. Examples of such foreign materials include but are not limited to:

a)  Mortar dust
b)  Drywall dust
c)  Firesafing materials
d)  Wall texture
e)  Paint overspray

7)  Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed 

within 5 feet of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or 
torque requirements to exceed damper/actuator design.

8)  Caulking is not necessary, nor is it allowed, between the damper sleeve and the wall or floor opening (annular space). 

However, caulking may be applied to the retaining plates.

9)  ACCESS: Suitable access (such that fusible links, RRL’s, actuators, and linkages can be maintained) must be provided 

for damper inspection and servicing. Where it is not possible to achieve sufficient size access, it will be necessary to 
install a removable section of duct. (Refer to NFPA 90A).

10) The Code Authority Having Jurisdiction (AHJ) must evaluate and provide approval of final installation where variations to 

these instructions are necessary.

table of Contents

Pre-Installation Guidelines ...................................................................................2
Electrical Guidelines .............................................................................................3
Installation .........................................................................................................3-7
 

• 

Clearances Required Between Fire Damper Sleeves and Wall/Floor Openings 

......3

 

• 

Sleeve Length and Wall Thickness 

.................................................................4

 

• 

Duct to Sleeve Connections 

..........................................................................4

 

• 

Securing the Damper Assembly to Wall and Floor Openings

 ..............................4

 

• 

Actuator Connections 

..................................................................................5

 

• 

Connection and Operation of Temperature Control Devices

.............................5-6

 

 FSDR-XXX and DFDR-XXX Blade Orientation

....................................................6

 

• 

Recommended Preparation of Openings in Wood and Metal Stud Walls

 ...............6

Maintenance .........................................................................................................7
Troubleshooting ....................................................................................................7

Содержание FSDR-XXX

Страница 1: ... backcharges without prior written authorization Due to continuing research Greenheck reserves the right to change specifications without notice UL CLASSIFIED see complete marking on product UL CLASSIFIED to Canadian safety standards see complete marking on product UL Standard 555 555S Classification R13317 FSDR XXX SEFSDR XXX and SSFSDR XXX Model Dampers are intended for installation in accordanc...

Страница 2: ...ve leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and after installation Examples of such foreign materials include but are not limited to a Mortar dust b Drywall dust c Firesafing materials d Wall texture e Paint overspray 7 Damper should be sufficiently covered as to pr...

Страница 3: ...opening must be a minimum of 7 8 in larger than the outside diameter of the damper Refer to Section 4 for additional installation considerations SAFEty DANGER Electrical input may be needed for this equipment this work should be performed by a qualified electrician All wiring shall be done in accordance with the National Electrical Code ANSI NFPA 70 latest edition any local codes that may apply an...

Страница 4: ...SLEEVE ASSEMBLY TO WALL AND FLOOR OPENINGS Damper assemblies must be installed in wall floor openings using a single retaining plate on either side of the wall floor or by using a retaining plate on both sides of the wall floor The use of a second retaining plate is allowed but is not necessary A single retaining plate is provided with the dampers A second retaining plate can be ordered as an opti...

Страница 5: ...or with the higher temperature setting When the temperature of the secondary sensor is exceeded the damper closes and remains closed thereafter Fig 6 The TOR assembly also contains a single pole double throw switch used to indicate damper blade position The switch provides a positive open or closed signal when used in conjunction with remote indicator lights See page 6 Fig 6 for wiring of the TOR ...

Страница 6: ... primary sensor 212 F optional primary sensor 250 F secondary sensor 350º F secondary sensor 8 Recommended Preparation of Openings in Wood and Metal Stud Walls Frame wall openings as shown see Fig 7 Double vertical studs are not required for openings 36 in x 36 in or smaller Gypsum wall board must be fastened 12 in on center to all stud and runner flanges surrounding opening see Fig 8 All construc...

Страница 7: ...led too far into wall Move out to line designated on damper label Contaminants on damper Clean with a non oil based solvent see Damper Maintenance Damper does not fully open and or fully close Damper does not operate Actuator runs hot or makes a humming noise Link separated Heat Replace link Actuator prohibited from reaching end of stroke Disconnect linkage from jackshaft open damper power actuato...

Отзывы: