101
Air to Water Heat Pump
Service Manual- Versati Series
NBJOUFOBODF
C5
Indoor capacity switch error
De-energize the unit and then, energize it
again. If the malfunction is removed, the
code will be cleared.
E6
Communication
malfunction(between outdoor
and indoor mainboard)
Ɣ
The communication line of the unit is
not connected.
Ɣ
The communication line is not through.
Ɣ
The communication line of the unit is
not connected correctly.
Ɣ
The two ends of communication line
are not mounted with magnetic ring.
Ɣ
The outdoor unit is not electrically
powered
It will be cleared once communication
recovers or it will be shown all the time.
E6
Communication
malfunction(between outdoor
mainboard and wired controller)
Ɣ
The communication line of the unit is
not connected.
Ɣ
The communication line is not through.
Ɣ
The communication line of the unit is
not connected correctly.
Ɣ
The two ends of communication line
are not mounted with magnetic ring.
Ɣ
The outdoor unit is not electrically
powered
It will be cleared once communication
recovers or it will be shown all the time
Fc
High pressure sensor error
Ɣ
The sensor is damaged.
Ɣ
The wire of the sensor is loose.
Ɣ
The position of the sensor is wrong
It will be automatically cleared after the
failure is removed.
F9
Outlet temperature sensor error
Ɣ
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Ɣ
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
dH
Backup outlet temperature sensor
error
Ɣ
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Ɣ
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
F1
Lliquid pipe temperature sensor
Inside refrigerant error
Ɣ
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Ɣ
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
F8
Inlet temperature sensor error
Ɣ
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Ɣ
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
FE
The second sanitary water tank
temperature sensor error
Ɣ
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Ɣ
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
FL
T h e f i r s t s a n i t a r y w a t e r t a n k
temperature sensor error
Ɣ
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Ɣ
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
Содержание VERSATI SERIES
Страница 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL VERSATI SERIES T1 R410A 50Hz 60Hz GC201202 ...
Страница 4: ...1 Air to Water Heat Pump Service Manual Versati Series PRODUCT QSPEVDU ...
Страница 15: ...12 Air to Water Heat Pump Service Manual Versati Series CONTROL DPOUSPM ...
Страница 66: ...63 Air to Water Heat Pump Service Manual Versati Series INSTALLATION JOTUBMMBUJPO ...
Страница 92: ...89 Air to Water Heat Pump Service Manual Versati Series JOTUBMMBUJPO GRS CQ16Pd Na H ...
Страница 102: ...99 Air to Water Heat Pump Service Manual Versati Series MAINTENANCE NBJOUFOBODF ...
Страница 128: ...125 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Fig 14 ...
Страница 129: ...126 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2 ...
Страница 148: ...145 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Ɣ Exploded View of GRS CQ16Pd Na H I ...
Страница 158: ...JF00300495 ...