75
Air to Water Heat Pump
Service Manual- Versati Series
JOTUBMMBUJPO
After confirming that there is no leakage from the system, when the compressor is not in operation
FKDUJHDGGLWLRQDO5$ZRUNLQJÀXLGZLWKVSHFL¿HGDPRXQWWRWKHXQLWWKURXJKWKH¿OOLQJRSHQLQJRIWKHOLTXLG
pipe valve of the outdoor unit.
%HVXUHWRFKDUJHWKHVSHFL¿HGDPRXQWRIUHIULJHUDQWLQOLTXLGVWDWHWRWKHOLTXLGSLSH
Since this refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant composition to
change, preventing normal operation.
2) Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or not.
With siphon tube
No siphon tube
1.6 Connection of Pipeline
(1) Connection of Outlet Pipe for Indoor & Outdoor Unit
$OLJQWKHH[SDQVLRQHQGRIFRSSHUSLSHZLWKWKHFHQWHURIWKUHDGHGMRLQW7LJKWHQWKHÀDULQJQXWVZLWK\RXU
hands.
7LJKWHQWKHÀDULQJQXWVZLWKWRUTXHZUHQFKXQWLO\RXKHDUD³FOLFN´
%HQGRI¿WWLQJSLSHVKDOOQRWEHWRRORZRWKHUZLVHWKH¿WWLQJSLSHPLJKWFUDFN3OHDVHXVHSLSHEHQGHU
ZKHQEHQGLQJWKH¿WWLQJSLSH
When connecting outdoor and indoor unit, never pull the big and small joint of indoor unit with force, so
as to prevent the tubes of indoor unit from cracking and causing leakage.
Connecting pipe shall be supported by a rack without transmitting its weight to other units.
(2) Installation of Protective Layer on Connection Pipe
To avoid condensate dew or water leakage on connecting pipe, the air pipe and liquid pipe must be
wrapped with heat preservation material and adhesive pipe for insulation from the air.
The joints on indoor unit and outdoor unit must be wrapped with heat preservation materials and have no
clearance against the wall surface of indoor unit and outdoor unit.
Wrap the pipe with tapes.
1) Use the adhesive tape to wrap the connecting pipe and cable into one bundle. To prevent condensate
ZDWHUIURPRYHUÀRZLQJRXWRIWKHGUDLQSLSHWKHGUDLQSLSHVKDOOEHVHSDUDWHGIURPFRQQHFWLQJSLSHDQGFDEOH
2) Wrap the heat preservation tape so that each ring of tape shall press half of the previous ring.
3) Fix the wrapped pipe onto the wall with pipe clamp.
4) Do not wrap the protective tape too tightly, as this will decrease the heat insulation performance.
5) After completing the protection work and wrapping the pipe properly, close the wall holes with sealing
materials.
No clearance
Содержание VERSATI SERIES
Страница 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL VERSATI SERIES T1 R410A 50Hz 60Hz GC201202 ...
Страница 4: ...1 Air to Water Heat Pump Service Manual Versati Series PRODUCT QSPEVDU ...
Страница 15: ...12 Air to Water Heat Pump Service Manual Versati Series CONTROL DPOUSPM ...
Страница 66: ...63 Air to Water Heat Pump Service Manual Versati Series INSTALLATION JOTUBMMBUJPO ...
Страница 92: ...89 Air to Water Heat Pump Service Manual Versati Series JOTUBMMBUJPO GRS CQ16Pd Na H ...
Страница 102: ...99 Air to Water Heat Pump Service Manual Versati Series MAINTENANCE NBJOUFOBODF ...
Страница 128: ...125 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Fig 14 ...
Страница 129: ...126 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2 ...
Страница 148: ...145 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Ɣ Exploded View of GRS CQ16Pd Na H I ...
Страница 158: ...JF00300495 ...