10
Air to Water Heat Pump
Service Manual- Versati Series
QSPEVDU
4.3 Electrical Data
Model
Power Supply
Leakage Switch
Minimum Sectional
Area of Earth Wire
Minimum Sectional Area
of Power Supply Wire
V,Ph,Hz
(A)
(mm
2
)
(mm
2
)
GRS-CQ6.0Pd/Na-K(I)
220-240V,~,50Hz
32
4
3×4
GRS-CQ8.0Pd/Na-K(I)
50
10
3×10
GRS-CQ10Pd/Na-K(I)
50
10
3×10
GRS-CQ12Pd/Na-K(I)
50
10
3×10
GRS-CQ14Pd/Na-K(I)
50
10
3×10
GRS-CQ16Pd/Na-K(I)
50
10
3×10
GRS-CQ6.0Pd/Na-K(O)
32
4
3×4
GRS-CQ8.0Pd/Na-K(O)
32
4
3×4
GRS-CQ10Pd/Na-K(O)
32
4
3×4
GRS-CQ12Pd/Na-K(O)
40
6
3×6
GRS-CQ14Pd/Na-K(O)
40
6
3×6
GRS-CQ16Pd/Na-K(O)
40
6
3×6
GRS-CQ12Pd/Na-M(I)
380-415V,3N~,50Hz
16
1.5
5×1.5
GRS-CQ14Pd/Na-M(I)
16
1.5
5×1.5
GRS-CQ16Pd/Na-M(I)
16
1.5
5×1.5
GRS-CQ12Pd/Na-M(O)
25
2.5
5×2.5
GRS-CQ14Pd/Na-M(O)
25
2.5
5×2.5
GRS-CQ16Pd/Na-M(O)
25
2.5
5×2.5
GRS-CQ16Pd/Na-H(I)
380V,3N~,60Hz
16
1.5
5×1.5
GRS-CQ16Pd/Na-H(O)
25
2.5
5×2.5
Note:
ķ
Leakage Switch is necessary for additional installation. If circuit breakers with leakage protection are in
use, action response time must be less than 0.1 second, leakage circuit must be 30mA.
ĸ
The above selected power cable diameters are determined based on assumption of distance from the
distribution cabinet to the unit less than 75m. If cables are laid out in a distance of 75m to 150m, diameter of
power cable must be increased to a further grade.
Ĺ
The power supply must be of rated voltage of the unit and special electrical line for air-conditioning.
ĺ
All electrical installation shall be carried out by professional technicians in accordance with the local
laws and regulations.
Ļ
Ensure safe grounding and the grounding wire shall be connected with the special grounding equipment
of the building and must be installed by professional technicians.
ļ
7KHVSHFL¿FDWLRQVRIWKHEUHDNHUDQGSRZHUFDEOHOLVWHGLQWKHWDEOHDERYHDUHGHWHUPLQHGEDVHGRQ
the maximum power (maximum amps) of the unit.
Ľ
7KHVSHFL¿FDWLRQVRIWKHSRZHUFDEOHOLVWHGLQWKHWDEOHDERYHDUHDSSOLHGWRWKHFRQGXLWJXDUGHGPXOWL
wire copper cable (like, YJV XLPE insulated power cable) used at 40
ć
and resistible to 90
ć
(see IEC 60364-5-
,IWKHZRUNLQJFRQGLWLRQFKDQJHVWKH\VKRXOGEHPRGL¿HGDFFRUGLQJWRWKHUHODWHGQDWLRQDOVWDQGDUG
ľ
7KHVSHFL¿FDWLRQVRIWKHEUHDNHUOLVWHGLQWKHWDEOHDERYHDUHDSSOLHGWRWKHEUHDNHUZLWKWKHZRUNLQJ
temperature at 40
ć
,IWKHZRUNLQJFRQGLWLRQFKDQJHVWKH\VKRXOGEHPRGL¿HGDFFRUGLQJWRWKHUHODWHGQDWLRQDO
standard.
Содержание VERSATI SERIES
Страница 1: ...AIR TO WATER HEAT PUMP SERVICE MANUAL VERSATI SERIES T1 R410A 50Hz 60Hz GC201202 ...
Страница 4: ...1 Air to Water Heat Pump Service Manual Versati Series PRODUCT QSPEVDU ...
Страница 15: ...12 Air to Water Heat Pump Service Manual Versati Series CONTROL DPOUSPM ...
Страница 66: ...63 Air to Water Heat Pump Service Manual Versati Series INSTALLATION JOTUBMMBUJPO ...
Страница 92: ...89 Air to Water Heat Pump Service Manual Versati Series JOTUBMMBUJPO GRS CQ16Pd Na H ...
Страница 102: ...99 Air to Water Heat Pump Service Manual Versati Series MAINTENANCE NBJOUFOBODF ...
Страница 128: ...125 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Fig 14 ...
Страница 129: ...126 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Indoor Unit 1 Front panel assy Fig 2 Fig 1 Fig 2 ...
Страница 148: ...145 Air to Water Heat Pump Service Manual Versati Series NBJOUFOBODF Ɣ Exploded View of GRS CQ16Pd Na H I ...
Страница 158: ...JF00300495 ...