Hydro Box
7
3.3.2 Selection of Communication Wire between Hydro Box and Mode exchanger
Material Type
Total Length L (m) of
Communication
Cable between
Indoor Unit and
Indoor (Outdoor) Unit
Wire size
(mm
2
)
Material
Standard
Remarks
Light/Ordinary
polyvinyl chloride
sheathed cord.
(60227 IEC 52
/60227 IEC 53)
L≤1000
≥
2×0.75
IEC 60227-5
1. If the wire diameter is enlarged to
2×1mm
2
, the total communication line
length can reach 1500m.
2. The cord shall be Circular cord (the
cores shall be twisted together).
3. If unit is installed in places with
intense magnetic field or strong
interference, it is necessary to use
shielded wire.
3.4 Requirements for Electrical Wiring
(1) The hydro box belongs to Category I Electric Appliance. Therefore, be sure to take
reliable earthed measures. The earthed wire shall be connected to the special earthed
device on the construction. The installation must be done by specialist technicians.
(2) The fixed circuit must be provided with leakage protection switch and air switch that have
enough capacity.
(3) The power supply must comply with the ratings on nameplate, while the special circuit for
air conditioner must be used.
(4) The diameter of power cables shall be big enough. Please select the power cables in
reference to the specifications below.
(5) Carry out installation according to national wiring rules.
(6) Do not pull the power cables with force.
Model
Type of power supply
Min. sectional area of power cable
Live
wire(mm
2
)
Neutral
wire(mm
2
)
Earthed
wire(mm
2
)
Air switch capacity(A)
NRQR16L/A-T
220-240V
~
50Hz
208-230V ~60Hz
1.5
1.5
1.5
6
NRQR30L/A-T
220-240V
~
50Hz
208-230V ~60Hz
1.5
1.5
1.5
6
Notes:
①
The power cable must be copper-core cable, and its working temperature shall not be
higher than the specified value.
②
If the power cable is longer than 15m, please increase its sectional area appropriately,
thus to avoid overloading.
③
The power cable specification refers to the specification of BV single-cord cable (2~4
cords) laid when inserting the plastic pipe and selected the working environment
temperature is 40°C. The air switch is used for a temperature of 40°C and it shall be “D”
type.
④
All electrical installation must be performed by qualified technicians in accordance with
local laws, regulations and the corresponding instruction manual.