70
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
combination
outdoor air temp
indoor air temperature
℃
DB
16
18
20
21
22
24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
℃
DB
℃
WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-19.8
-20
21.8
11.77
20.4
10.87
19.0
9.80
18.2
9.45
17.6
9.12
16.4
8.44
-18.8
-19
21.8
11.53
20.4
10.65
19.0
9.62
18.2
9.26
17.6
8.93
16.4
8.28
-16.7
-17
21.8
11.01
20.4
10.18
19.0
9.21
18.2
8.88
17.6
8.56
16.4
7.93
-13.7
-15
21.8
10.51
20.4
9.72
19.0
8.79
18.3
8.48
17.6
8.16
16.4
7.57
-11.8
-13
21.8
9.98
20.4
9.25
19.0
8.37
18.3
8.08
17.6
7.77
16.4
7.22
-9.8
-11
21.9
9.46
20.5
8.77
19.1
7.96
18.3
7.68
17.6
7.38
16.4
6.86
-9.5
-10
21.9
9.21
20.5
8.53
19.1
7.76
18.3
7.49
17.6
7.19
16.4
6.68
-8.5
-9.1
21.9
8.98
20.5
8.33
19.1
7.57
18.3
7.31
17.6
7.03
16.4
6.53
-7
-7.6
21.8
8.59
20.4
8.01
19.0
7.26
18.3
7.01
17.6
6.75
16.4
6.28
-5
-5.6
21.7
8.05
20.3
7.49
18.9
6.84
18.2
6.60
17.6
6.40
16.4
5.95
-3
-3.7
21.7
7.63
20.3
7.10
18.9
6.48
18.2
6.26
17.6
6.07
16.4
5.66
0
-0.7
21.7
7.00
20.3
6.52
18.9
5.98
18.2
5.77
17.6
5.60
16.4
5.23
3
2.2
21.7
6.45
20.3
6.01
18.9
5.51
18.2
5.33
17.6
5.19
16.4
4.84
5
4.1
21.7
6.12
20.3
5.70
18.9
5.24
18.2
5.07
17.6
4.93
16.4
4.61
7
6
21.7
5.81
20.3
5.42
18.9
5.00
18.2
4.83
17.6
4.69
16.4
4.40
9
7.9
21.7
5.51
20.3
5.15
18.9
4.75
18.2
4.61
17.6
4.47
16.4
4.19
11
9.8
21.7
5.24
20.3
4.90
18.9
4.53
18.2
4.39
17.6
4.26
16.4
4.00
13
11.8
21.7
4.98
20.3
4.66
18.9
4.31
18.2
4.18
17.6
4.06
16.4
3.82
15
13.7
21.7
4.74
20.3
4.45
18.9
4.12
18.2
3.99
17.6
3.88
16.4
3.64
18
16.8
21.7
4.51
20.3
4.24
18.9
3.95
18.2
3.83
17.6
3.71
16.4
3.47
20
18.5
21.7
4.30
20.3
4.06
18.9
3.80
18.2
3.69
17.6
3.56
16.4
3.32
24
20.5
21.7
4.10
20.3
3.89
18.9
3.53
18.2
3.57
17.6
3.42
16.4
3.18