116
Outdoor Model
Gas pipe size(mm)
Liquid pipe size(mm)
GMV-1845WM/H-X
Φ
44.5
Φ
22.2
GMV-1905WM/H-X
Φ
44.5
Φ
22.2
GMV-1959WM/H-X
Φ
44.5
Φ
22.2
GMV-2015WM/H-X
Φ
51.4
Φ
25.4
GMV-2070WM/H-X
Φ
51.4
Φ
25.4
GMV-2125WM/H-X
Φ
51.4
Φ
25.4
GMV-2180WM/H-X
Φ
51.4
Φ
25.4
GMV-2245WM/H-X
Φ
51.4
Φ
25.4
GMV-2295WM/H-X
Φ
51.4
Φ
25.4
GMV-2349WM/H-X
Φ
51.4
Φ
25.4
GMV-2405WM/H-X
Φ
51.4
Φ
25.4
GMV-2460WM/H-X
Φ
51.4
Φ
25.4
e.If the liquid pipe is enlarged for a situation from (2) ~ (4), please do not enlarged any more.
f.If the length between an IDU and its nearest branch is above 15m, then increase the size of the liquid
pipe (only for the pipe size that is≤6.35mm) and gas pipe (only for the pipe size that is≤9.52mm) of
IDU.
8.2 Connection pipe among outdoor modules
(1) The pipe among the outdoor modules must be at the same level or tilted upwards. Otherwise, the
refrigeration oil will remain in the pipe.