7.5 Take snow into consideration when installing the outdoor unit
When the unit is installed, the snow should be taken into consideration for the height of the base.
Note: The photo is only for reference. Please refer to the installation locale.
7.6 Installation space requirements for equipment floor
When the outdoor unit is installed in the equipment floor, it needs to connect an air exhaust duct.
The opening ratio of the shutters in the equipment floor is not less than 60%, and the horizontal angle
of louvers is less than 20°.