GMV6 DC Inverter VRF Units Technical Sales Guide
Model
Combination method
Power supply
Capacity of
circuit breaker of
each combination
module (A)
Minimum cross-
sectional area of
grounding wire (mm
2
)
Recommended wire
(cross-sectional area)
(mm
2
)
GMV-1959WM/H-X
280+504+560+615
380-415V 3N~
50/60Hz
25+50+50+50 2.5+10.0+10.0+10.0
2.5×5+10.0×5+
10.0×5+10.0×5
GMV-2015WM/H-X
280+560+560+615
380-415V 3N~
50/60Hz
25+50+50+50 2.5+10.0+10.0+10.0
2.5×5+10.0×5+
10.0×5+10.0×5
GMV-2070WM/H-X
280+560+615+615
380-415V 3N~
50/60Hz
25+50+50+50 2.5+10.0+10.0+10.0
2.5×5+10.0×5+
10.0×5+10.0×5
GMV-2125WM/H-X
280+615+615+615
380-415V 3N~
50/60Hz
25+50+50+50 2.5+10.0+10.0+10.0
2.5×5+10.0×5+
10.0×5+10.0×5
GMV-2180WM/H-X
335+615+615+615
380-415V 3N~
50/60Hz
25+50+50+50 4.0+10.0+10.0+10.0
4.0×5+10.0×5+
10.0×5+10.0×5
GMV-2245WM/H-X
400+615+615+615
380-415V 3N~
50/60Hz
40+50+50+50 6.0+10.0+10.0+10.0
6.0×5+10.0×5+
10.0×5+10.0×5
GMV-2295WM/H-X
450+615+615+615
380-415V 3N~
50/60Hz
40+50+50+50 6.0+10.0+10.0+10.0
6.0×5+10.0×5+
10.0×5+10.0×5
GMV-2349WM/H-X
504+615+615+615
380-415V 3N~
50/60Hz
50+50+50+50 10.0+10.0+10.0+10.0
10.0×5+10.0×5+
10.0×5+10.0×5
GMV-2405WM/H-X
560+615+615+615
380-415V 3N~
50/60Hz
50+50+50+50 10.0+10.0+10.0+10.0
10.0×5+10.0×5+
10.0×5+10.0×5
GMV-2460WM/H-X
615+615+615+615
380-415V 3N~
50/60Hz
50+50+50+50 10.0+10.0+10.0+10.0
10.0×5+10.0×5+
10.0×5+10.0×5
NOTES:
a. The circuit breaker and power cable specifications are selected according to the maximum unit power
(maximum current).
b. The power cable specifications are obtained under the condition that the multi-copper core cable
(such as YJV copper-core XLPE insulated PVC sheathed power cable) is laid in the wire trough in an
exposed manner (the ambient temperature of use is 40
℃
and the cable operating temperature is 90
℃
)
(IEC60364-5-523). If the use condition is different, calculate and adjust the specification according to
the corresponding national standard.
c. The copper core cable must be used.
d. The engineering wiring should meet the requirements of IEC 60364-5-52 to ensure that the line
voltage drop meets the requirements and the voltage is not lower than the lower limit of the nominal
value of equipment.
e. The circuit breaker specification is obtained under the condition that the ambient temperature is
40
℃
when the circuit breaker is operating. If the use condition is different, calculate and adjust the
specification according to the instructions on circuit breaker specifications.
f. The circuit breaker should provide the magnetic trip and thermal trip functions at the same time to
ensure protection in the cases of short circuit and overload.