60
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
combination
outdoor air temp
indoor air temperature
℃
DB
16
18
20
21
22
24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
℃
DB
℃
WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-19.8
-20
14.5
7.11
13.6
6.56
12.7
5.91
12.1
5.69
11.8
5.54
11.0
5.13
-18.8
-19
14.6
6.96
13.6
6.43
12.7
5.80
12.1
5.57
11.8
5.42
11.0
5.03
-16.7
-17
14.6
6.65
13.6
6.14
12.7
5.55
12.1
5.34
11.8
5.20
11.0
4.82
-13.7
-15
14.6
6.34
13.7
5.86
12.7
5.30
12.2
5.11
11.8
4.96
11.0
4.60
-11.8
-13
14.6
6.02
13.7
5.58
12.7
5.05
12.2
4.86
11.8
4.72
11.0
4.39
-9.8
-11
14.6
5.71
13.7
5.29
12.7
4.80
12.2
4.62
11.9
4.52
11.0
4.17
-9.5
-10
14.6
5.56
13.7
5.15
12.7
4.68
12.2
4.51
11.9
4.40
11.0
4.06
-8.5
-9.1
14.6
5.42
13.7
5.03
12.7
4.57
12.2
4.40
11.9
4.30
11.0
3.97
-7
-7.6
14.6
5.19
13.7
4.83
12.7
4.38
12.2
4.22
11.9
4.13
11.0
3.81
-5
-5.6
14.5
4.86
13.6
4.52
12.6
4.12
12.1
3.97
11.9
3.91
11.0
3.61
-3
-3.7
14.5
4.61
13.6
4.28
12.6
3.91
12.1
3.77
11.9
3.71
11.0
3.44
0
-0.7
14.5
4.23
13.6
3.93
12.6
3.60
12.1
3.47
11.9
3.42
11.0
3.18
3
2.2
14.5
3.89
13.6
3.63
12.6
3.32
12.1
3.21
11.9
3.17
11.0
2.94
5
4.1
14.5
3.70
13.6
3.44
12.6
3.16
12.1
3.05
11.9
3.01
11.0
2.80
7
6
14.5
3.51
13.6
3.27
12.6
3.01
12.1
2.90
11.9
2.87
11.0
2.67
9
7.9
14.5
3.33
13.6
3.11
12.6
2.86
12.1
2.77
11.9
2.73
11.0
2.55
11
9.8
14.5
3.16
13.6
2.95
12.6
2.73
12.1
2.64
11.9
2.61
11.0
2.43
13
11.8
14.5
3.01
13.6
2.81
12.6
2.60
12.1
2.52
11.9
2.48
11.0
2.32
15
13.7
14.5
2.86
13.6
2.68
12.6
2.48
12.1
2.40
11.9
2.37
11.0
2.21
18
16.8
14.5
2.73
13.5
2.55
12.6
2.38
12.1
2.30
11.9
2.27
11.0
2.11
20
18.5
14.5
2.59
13.5
2.44
12.6
2.29
12.1
2.22
11.9
2.18
11.0
2.01
24
20.5
14.5
2.47
13.5
2.34
12.6
2.13
12.1
2.14
11.9
2.09
11.0
1.93