65
GMV6 DC Inverter VRF Units Technical Sales Guide
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
combination
outdoor air temp
indoor air temperature
℃
DB
16
18
20
21
22
24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
℃
DB
℃
WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-19.8
-20
18.3
11.13
17.1
10.26
15.9
9.25
15.3
8.91
14.9
8.68
13.9
8.04
-18.8
-19
18.3
10.91
17.2
10.07
16.0
9.08
15.3
8.73
14.9
8.49
13.9
7.87
-16.7
-17
18.4
10.42
17.2
9.62
16.0
8.70
15.3
8.36
14.9
8.15
13.9
7.55
-13.7
-15
18.4
9.94
17.2
9.18
16.0
8.31
15.3
8.00
14.9
7.76
13.9
7.21
-11.8
-13
18.4
9.44
17.2
8.75
16.0
7.91
15.3
7.62
14.9
7.39
13.9
6.87
-9.8
-11
18.4
8.96
17.2
8.29
16.0
7.52
15.3
7.23
15.0
7.07
13.9
6.52
-9.5
-10
18.4
8.71
17.2
8.07
16.0
7.33
15.4
7.05
15.0
6.89
13.9
6.36
-8.5
-9.1
18.4
8.49
17.2
7.87
16.0
7.15
15.4
6.89
15.0
6.73
13.9
6.21
-7
-7.6
18.4
8.13
17.2
7.57
16.0
6.86
15.3
6.60
15.0
6.47
13.9
5.97
-5
-5.6
18.3
7.62
17.1
7.08
15.9
6.45
15.2
6.23
15.0
6.13
13.9
5.66
-3
-3.7
18.3
7.21
17.1
6.71
15.9
6.12
15.2
5.91
15.0
5.81
13.9
5.39
0
-0.7
18.3
6.63
17.1
6.16
15.9
5.65
15.2
5.44
15.0
5.36
13.9
4.97
3
2.2
18.3
6.10
17.1
5.68
15.9
5.21
15.2
5.02
15.0
4.97
13.9
4.61
5
4.1
18.3
5.79
17.1
5.39
15.9
4.95
15.2
4.78
15.0
4.71
13.9
4.39
7
6
18.3
5.49
17.1
5.11
15.9
4.71
15.2
4.55
15.0
4.49
13.9
4.18
9
7.9
18.3
5.21
17.1
4.87
15.9
4.49
15.2
4.34
15.0
4.28
13.9
3.99
11
9.8
18.3
4.95
17.1
4.63
15.9
4.28
15.2
4.13
15.0
4.08
13.9
3.81
13
11.8
18.3
4.71
17.1
4.41
15.9
4.07
15.2
3.94
15.0
3.89
13.9
3.63
15
13.7
18.3
4.49
17.1
4.20
15.9
3.89
15.2
3.76
15.0
3.71
13.9
3.45
18
16.8
18.3
4.28
17.0
4.00
15.9
3.73
15.2
3.60
15.0
3.55
13.9
3.31
20
18.5
18.3
4.07
17.0
3.82
15.9
3.58
15.2
3.47
15.0
3.40
13.9
3.16
24
20.5
18.3
3.87
17.0
3.66
15.9
3.34
15.2
3.36
15.0
3.28
13.9
3.02