80
TC—Total capacity of outdoor unit; PI—Power input of outdoor unit
combination
outdoor air
temp
indoor air temperature
℃
DB
16
18
20
21
22
24
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
℃
DB
℃
WB
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
kW
50%
-19.8
-20
29.0
17.03
27.1
15.70
25.2
14.10
24.3
13.65
23.4
13.13
21.8
12.19
-18.8
-19
29.0
16.68
27.1
15.39
25.3
13.85
24.3
13.37
23.4
12.87
21.8
11.95
-16.7
-17
29.1
15.93
27.2
14.71
25.3
13.26
24.3
12.82
23.4
12.35
21.8
11.45
-13.7
-15
29.1
15.19
27.2
14.04
25.3
12.66
24.4
12.25
23.5
11.80
21.8
10.94
-11.8
-13
29.1
14.43
27.2
13.37
25.3
12.06
24.4
11.67
23.5
11.23
21.8
10.42
-9.8
-11
29.2
13.68
27.3
12.67
25.4
11.47
24.4
11.09
23.5
10.69
21.8
9.90
-9.5
-10
29.2
13.32
27.3
12.33
25.4
11.18
24.4
10.82
23.5
10.42
21.8
9.64
-8.5
-9.1
29.2
12.99
27.3
12.04
25.4
10.91
24.4
10.56
23.5
10.18
21.8
9.42
-7
-7.6
29.1
12.42
27.2
11.56
25.3
10.46
24.4
10.13
23.5
9.77
21.8
9.07
-5
-5.6
28.9
11.65
27.1
10.82
25.2
9.85
24.2
9.54
23.4
9.24
21.8
8.59
-3
-3.7
28.9
11.03
27.1
10.25
25.2
9.34
24.2
9.05
23.4
8.76
21.8
8.17
0
-0.7
28.9
10.13
27.1
9.42
25.2
8.61
24.2
8.34
23.4
8.09
21.8
7.55
3
2.2
28.9
9.33
27.1
8.68
25.2
7.95
24.2
7.71
23.4
7.49
21.8
6.99
5
4.1
28.9
8.85
27.1
8.24
25.2
7.55
24.2
7.33
23.4
7.11
21.8
6.65
7
6
28.9
8.40
27.1
7.83
25.2
7.20
24.2
6.98
23.4
6.78
21.8
6.35
9
7.9
28.9
7.97
27.1
7.44
25.2
6.84
24.2
6.66
23.4
6.46
21.8
6.05
11
9.8
28.9
7.58
27.1
7.08
25.2
6.53
24.2
6.34
23.4
6.16
21.8
5.77
13
11.8
28.9
7.21
27.1
6.73
25.2
6.21
24.2
6.04
23.4
5.86
21.8
5.51
15
13.7
28.9
6.86
27.1
6.42
25.2
5.94
24.2
5.77
23.4
5.60
21.8
5.25
18
16.8
28.9
6.53
27.1
6.14
25.2
5.70
24.2
5.53
23.4
5.36
21.8
5.01
20
18.5
28.9
6.22
27.1
5.87
25.2
5.48
24.2
5.33
23.4
5.14
21.8
4.79
24
20.5
28.9
5.93
27.1
5.63
25.2
5.10
24.2
5.15
23.4
4.94
21.8
4.59
Содержание GMV6 VRF
Страница 98: ...96 ...
Страница 99: ...97 GMV6 DC Inverter VRF Units Technical Sales Guide ...
Страница 100: ...98 ...
Страница 101: ...99 GMV6 DC Inverter VRF Units Technical Sales Guide ...
Страница 102: ...100 ...
Страница 124: ...122 ...