U-Match Series DC Inverter Service Manual
82
Sponge
Threaded fastener(×4)
Liquid pipe
Gas inlet pipe
Heat insulation sheath
(for the gas tube)
Heat insulation sheath
(for the liquid tube)
Figure 3-3-4
Table 3-3-1 Flare nut tightening torque
Pipe Diameter
Tightening Torque
6mm (1/4inch)
15~30N·m (11~22ft.-1b.)
9.5mm (3/8inch)
35~40N·m (26~29ft.-1b.)
12.7mm (1/2inch)
45~50N·m (33~37ft.-1b.)
16mm (5/8inch)
60~65N·m (44~48ft.-1b.)
Be sure to connect the gas pipe after connecting the liquid pipe completely.
3.1.4 Connecting the Pipe at the Outdoor Side Unit
Tighten the flare nut of the connection pipe at the outdoor unit valve connector. The tightening method
is the same as that as at the indoor side.
Gas pipe
Liquid pipe
Pipe
coupling
or
or
3-way valve
2-way valve
Figure 3-3-5
Содержание GKH18D3FI
Страница 1: ...U MATCH SERIES DC INVERTER AIR CONDITIONERS SERVICE MANUAL T1 R410A 60Hz GC201410...
Страница 4: ...U Match Series DC Inverter Service Manual 1 PRODUCT...
Страница 16: ...U Match Series DC Inverter Service Manual 13 CONTROL...
Страница 55: ...U Match Series DC Inverter Service Manual 52 INSTALLATION...
Страница 96: ...U Match Series DC Inverter Service Manual 93 MAINTENANCE...
Страница 112: ...U Match Series DC Inverter Service Manual 109 H6 DC fan error...
Страница 121: ...U Match Series DC Inverter Service Manual 118 Model GUHD24ND3FO Model GUHD30ND3FO...
Страница 122: ...U Match Series DC Inverter Service Manual 119 Model GUHD36ND3FO Model GUHD42ND3FO...
Страница 126: ...U Match Series DC Inverter Service Manual 123 Model GKH48D3FI...
Страница 191: ...U Match Series DC Inverter Service Manual 188 JF00302305...